Hager 2-679-0630 Installation Instructions Manual - page 4
Delayed Egress Wall Controller
Installation Instructions
I-EA00052
Rev 2, Rev Date: 02/06/15
Always visit www.hagerco.com for the latest Installation Instructions
HAGER COMPANIES 139 Victor Street, St. Louis, MO 63104 • (800) 325-9995
**JUMPER J1 (DOOR PROP)
INSTALLED: The 4500 DE will enter the alarm mode if the
door is held open past the request to exit period.
REMOVED: The 4500 DE will remain unlocked if the door
is held open past the request to exit period. No alarm will
sound.
For the 4500 DE to relock and rearm upon closure of the
door, DPS is required.
*Door Contact or Power Transfer Hinge by DPS required for
Anti-Tailgate and Door Prop operation.
WARNING!
CONTACT THE AUTHORITY HAVING JURISDICTION FOR APPROVAL
PRIOR TO SELECTING DELAY TIME OR PWR-UP SETTINGS
DIP SWITCH
SETTINGS
15
30
1
2
15
20
30
1
N/C
N/O
UNLOCKED
LOCKED
VOICE/
TONE
TONE
ONLY
FEMALE
MSG
MALE
MSG
O
N
DELAY
TIME
[ON]
[OFF]
1
2
3
4
5
6
7
8
NUISANCE
DELAY
REX
PERIOD
TRIGGER
TYPE
PWR UP
STATE
ALARM
TYPE
MESSAGE
JUMPER J1**
PWR LOCK RED R
NO C
TRIG REX RESET
C NO
C NO
C NO
To
Power
Supply
- +
- +
TANDEM UNIT
(PAIR OF DOORS)
WHT
WHT
BLK
RED
WHT
WHT
BLK
RED
POWER
TRANSFER HINGE
POWER
TRANSFER
HINGE
*DPS
*DPS
To
Power
Supply
PWR LOCK
RED R
NO
C
N
TRIG REX RESET
C NO
C NO
C NO
WHT
WHT
BLK
RED
POWER
TRANSFER
HINGE
SINGLE
DOOR
DPS
*
- + - +
2-679-0630
2-679-0630
Wiring Diagrams and Options
Optional Features
External Request to Exit: The REX TERMINAL is a
wet 12/24VDC output to be used with a keypad such as
a 2915.
External Reset: The RESET TERMINAL is a wet 12/
24VDC output to be used with a keypad such as a
2915.
Lock/Unlock Monitoring: The GRN RLY TERMINAL
is a dry relay that is activated when the LOCK output is
activated.
Alarm Monitoring: The RED RLY TERMINAL is a dry
relay that is activated when the Alarm is activated.
Page 4 of 7