Hager 2958 Delayed Egress MagLock Installation Instructions Manual

Summary of 2958 Delayed Egress MagLock

  • Page 1

    2958 operational description (nfpa-101) the 2958 operation complies with the following building and fire codes: nfpa 101; nfpa 1-ufc; ubc; ibc; ifc; sbc; california building code. Listings: ul listed: special locking arrangements and auxiliary locks; california state fire marshal (csfm) listed. The ...

  • Page 2

    Included in package maglock housing assy. & mounting plate trigger & armature base armature armature screw pack maglock screw pack template 1/2” dia for wire first install mounting plate at two slot locations only and make proper adjustments before marking remaining five mounting hole locations. Fol...

  • Page 3

    Door and frame reference door and frame preparation instructions hinge side of frame (opposite from lock) paper template step 1. Locate the paper template and fold along the dotted line. Place the folded edge of the template against the door stop and door at the header while against the vertical sto...

  • Page 4

    Step 1. Mount armature to door. (see figures 2a, 2b & 2c.) step 2. Install the mounting plate (filler plate and/or angle bracket if needed – see figures 1a, 1b & 1c) to header with only the two screws at the slotted hole locations at this time. Snug the screws down lightly (do not torque) so the mou...

  • Page 5

    Typical system wiring – single door (model 2958) + - c no (optional) + - + - (optional) red grn blk wht blk blu red l3 optio n c nc - + - + nc no no c c nc no c no c no c no c no c nc no c nc [ bas ] [ dps ] [reset] [rm trig] [rex] [red rly] [grn rly] [ lock ] [ fp ] [ pwr ] j6 j7 j2 [ibo] [ext spkr...

  • Page 6

    3 or 5 conductors 8 or 10 conductors power supply to fire panel ac mains 2 conductors 4 conductors (2958t only) push until alarm sounds. Door can be opened in 15 seconds. Push until alarm sounds. Door can be opened in 15 seconds. + - 2900 series power supply red grn blk wht blu blk blk l3 opti on di...

  • Page 7

    + - c no (optional) 3 or 5 conductors 8 or 10 conductors power supply to fire panel ac mains 2 conductors push until alarm sounds. Door can be opened in 15 seconds. Key switch or access control (optional) remove j6 only if a fire panel or smoke detection system is connected to [fp] input (pg. 8) to ...

  • Page 8

    Wiring details & functions (all options shown) request to exit key switch or access control system (optional) remote reset switch (optional) remote status panel (optional) fire alarm input (optional) power supply 12vdc or 24vdc dry, n/c blk rmb x l3 red external trigger switch or sdc rex push bar (o...

  • Page 9

    Dip switch settings request to exit period – the request to exit (rex) time is selectable for 1, 15, 20, or 30 seconds. The rex time is the period of time the lock will remain “bypassed”, after a remote normally open contact switch is momentarily activated. When activated with an access control syst...

  • Page 10

    Step 1. After the lock has been mounted to the door and frame per the provided template, feed the wiring through the access hole and out to the controller board. Re-install the lock front cover onto the lock. Ensure that the trigger sensor is aligned with the hole in the cover. The sensor is preset ...

  • Page 11

    Standard features 1650 lbs. Holding force 15 or 30 second exit delay when activated. 1 or 2 second nuisance delay 75db alarm tone with digital display & selectable voice instruction choice of activation trigger: - door movement - exit device w/ rex switch - touch sense bar w/rex switch vandal resist...

  • Page 12

    Sense bar trigger non-latching 4801 power wall mount reset station (optional) power a pair of doors requires the 2958t power pushing either door triggers the delayed release of both doors. Latching exit device with built-in switch kit trigger power etw hinge switch kit push until alarm sounds. Door ...