3
Note
When connecting the cable, confirm the terminal number of indoor and
outdoor units carefully. If wiring is not correct, proper operation can not
be carried out and will cause defect.
1. If the supply cord is damaged, it must be replaced by the manufacturer or its
service agent or a similar qualified person. The type of connecting wire is H05RN-F
or H07RN-F.
2. If the fuse on PC board is broken please change it with the type of T. 3.15A/250V.
3. The wiring method should be in line with the local wiring standard.
4. After installation, the power plug should be easily reached.
5. A breaker should be incorporated into fixed wiring. The breaker should be all-pole
switch and the distance between its two contacts should be not less than 3mm.
Outdoor unit
Install according to
Drawing for the installation of indoor and outdoor units
To bend a pipe, give the roundness as large as possible not to crush the pipe ,
ƽ
and the bending radius should be 30 to 40 mm or longer.
Connecting the pipe of gas side first makes working easier.
ƽ
The connection pipe is specialized for R410A.
ƽ
Installation of Outdoor Unit
Half union
Flare nut
Torque wrench
Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.
The standard pipe length is 5m. If it is over 7m, the function of the unit will be
affected. If the pipe has to be lengthened, the refrigerant should be charged,
according to 20 g/m. But the charge of refrigerant must be conducted by profes-
sional air conditioner engineer. Before adding additional refrigerant, perform air
purging from the refrigerant pipes and indoor unit using a vacuum pump,then
Spanner
Forced fastening without careful centering may
damage the threads and cause a leakage of gas.
Pipe Diameter(ǿ)
Fastening torque
Liquid side6.35mm(1/4")
18N.m
Liquid/Gas side9.52mm(3/8")
42 N.m
Gas side 12.7mm(1/2")
55N.m
Gas side 15.88mm(5/8")
60 N.m
Connection of pipes
charge additional refrigerant.
Use the same method on indoor unit. Loosen the screws on
ƽ
terminal block and
insert the plugs fully into terminal block, then tighten the screws.
Insert the cable according to terminal number in the same manner as the indoor
unit.
ƽ
If wiring is not correct, proper operation can not be carried out and controller
may be damaged.
ƽ
Fix the cable with a clamp.
ƽ
CAUTION
Max.Elevation:
●
In case the elevation A is more
●
than 5m, oil trap shoud be
installed every 5~7m
Max. Length:
●
In case the pipe length B is
●
more than 7m, the refrigerant
should be charged, according
to 20 g/m.
Connection
If the drain-elbow is used,
ƽ
please attach it as figure. (Note:
Only for heat pump unit.)
Detach the service port’s cap of
1.
3-way valve, the valve rod’s cap for 2-way valve
and 3-way’s, connect the service port into the projection of charge hose (Iow)
for gaugemanifold. Then connect the projection of charge hose (center) for gau-
gemanifold into vacuum pump.
Open the handle at Iow in
2.
gaugemanifold, operate vacuum pump. If the scale-
moves of gause (Iow) reach vacuum condition in a moment, check 1. again.
Attaching Drain-Elbow
Purging Method:To use vacuum pump
A1max=10m
B1max=15m
A
B
Outdoor unit
Indoor unit
A1
B1
Indoor unit
A2
B2
Outdoor unit
Indoor unit
Oil trap
Outdoor unit
Indoor unit
A1
B1
Indoor unit
A2
B2
A2max=10m
B2max=15m
Insert the cable from the back
ƽ
side of the unit, then pull it out on the front side.
Loosen the screws and insert
ƽ
the cable ends fully into terminal block, then
tighten the screws.
Pull the cable slightly to
ƽ
make sure the cables have been properly inserted and
tightened.
After the cable connection,
ƽ
never fail to fasten the connected cable with the
wiring cover.
When connecting the cable before installing the indoor unit
Power cable:
3G2.5mm
Outdoor unit
R
E
W
O
P
1
3
2
1
2
Indoor unit A
Indoor unit B
{
4G0.75mm
2
4G0.75mm
2
ı
ı
L
N
1
)
(
2
)
(
H2SM-(9+9)HEA03/R2
H2SM-(9+12)HEA03/R2
H2SM-(9+9)HRA03/R2
H2SM-(9+12)HRA03/R2
H2SM-(9+12)HEK03/R2
(C)
3
(C)
1. Insert from outside the room cable into left side of the wall
hole, in which the pipe has already existed.
2. Pull out the cable on the front side, and connect the cable
making a loop.
When connecting the cable after installing the indoor unit
H2SM-(9+9)HEK03/R2
CAUTION
For multi model , the indoor units A and B should be
connected with corresponding valves A and B of out-
door exactly. Any mixed connection is forbidden.
ƽ