Haier HB4800VD1M22-P Installation & Operation Manual

Other manuals for HB4800VD1M22-P: Service Manual
Manual is about: Air Handler, HB-D series Central Air Conditioning

Summary of HB4800VD1M22-P

  • Page 1

    13 seer 2 3 4 5 ton installation & operation manual air handler warning when this appliance is installed in an enclosed area, such as a garage or utility room, with any carbon monoxide producing devices (i.E. Automobile, space heater, water heater,etc.) insure that the enclosed area is properly vent...

  • Page 2

    Index topic page index physical dimensions replacement parts source installation requirements air flow orientation horizontal left-hand instructions refrigerant tubing condensate removal electrical connections thermostat wiring orifice change circulating air duct blower performance start-up regular ...

  • Page 3

    D c 1" [2.54 cm] plastic breaker cover primary & secondary condensate drains- horizontal 3/4" npt 2" [5.1 cm] 3.3" [8.3 cm] 2" [5.1 cm] typical f k g 1.1" [2.9 cm] 5" [12.7 cm] h 2.4" [ 6 cm] 1.2" [3 cm] inlet front view primary & secondary condensate drains- upflow 3/4" npt-female 1" [2.54 cm] j in...

  • Page 4

    Physical dimensions 4 of 3 ton plastic breaker cover electrical power supply low volt supply electrical power supply inlet bottom side view suction line liquid line outlet top side view.

  • Page 5

    Physical dimensions 5 of 4,5 ton inlet bottom side view electrical power supply plastic breaker cover low volt supply electrical power supply suction line liquid line low volt supply outlet top side view.

  • Page 6

    Replacement parts source replacement parts are available through local distributors.When ordering replacement parts, give the complete model and serial numbers shown on the rating plate. Installation requirements before installing this appliance insure that it is properly sized and adequate power is...

  • Page 7

    Air flow orientation *horizontal right discharge tube and drain conn. Front horizontal left discharge tube and drain conn. Front (see page 6) important: remove the horizontal pan when unit is installed in unconditioned i.E. (garage, attic ) application, or downflow applications, and install insulati...

  • Page 8

    Horizontal left-hand instructions important: read instructions below carefully. Warning: if incorrect knockouts are removed, flooding will occur. 5) reinstall in the airhandler, the "a" coil pan assembly with the horizontal drain pan on the left-hand side. Note: push the assembly completely to the r...

  • Page 9

    Refrigerant tubing condensate removal refrigerant tubing should be installed as to avoid undue stress. They must be supported or routed to avoid strain or vibration. To avoid damage that can be caused by condensate, insulate the suction tube with a closed cell insulation with the seams sealed. The i...

  • Page 10

    Electrical connections the required electrical power supply information is located on the series and rating plate on the exterior of the unit. Wiring selection must be in accordance with local codes, or in absence of local code, the national electrical code. A disconnect means should be installed wi...

  • Page 11

    Thermostat wiring 11 for thermostat control environment-temperature and air conditioning open/stop, the wiring diagram as shown diagram 1. Thermostat can be mechanical type or programmable type. Note: thermostat c : com. R : ac24v y : compressor g : fan o : 4 -way valve for detailed thermostat, plea...

  • Page 12

    12 for thermostat control environment-temperature and air conditioning open/stop, the wiring diagram as shown diagram 4. Thermostat can be mechanical type or programmable type. Note: thermostat c: com. R : ac24v y : compressor g : fan for detailed thermostat, please connect corresponding terminal ac...

  • Page 13

    Suction line with spin closure rubber grommet orifice change the restrictor (orifice) included in this unit match the comparable capacity of the outdoor unit. If the indoor unit is greater in capacity than the outdoor condenser, the orifice must be changed to match the outdoor unit capacity. The res...

  • Page 14

    Blower performance cfm versus static pressure (inches of water column dry coil w/ filter) 4% reduction for wet coil. The air delivery can be varied by changing the blower speeds. This can allow for differences encountered in installations. The cfm can be checked by the following method; (the optiona...

  • Page 15

    Start-up prior to initial start-up insure that all electrical connections are properly sized and tightened. All panels must be in place and secured. Tubing should be leak free. Unit should be elevated, trapped and pitched to allow for drainage. Low voltage wiring is connected. Auxiliary drain is ins...

  • Page 16

    16 model number explanation h b 24 00 v d 1 m 20 haier brand symbol blower unit b:blower unit; c:evaporater unit nominal capacity in (000) btu/h 24:24000btu/h; 60: 60000btu/h electric heater 00:no; 01:1kw; 02:2kw; 15:15kw electric designation y :575v -3ph-60hz; v :208/230v -1ph-60hz; c:208/230v -3ph...