    Hlp-a100 series operating manual.

  • Page 4

    Hlp-a100 series hlp-a100 series operating manual index introduction 1 chapter 1 safty precautions 1 1.1 before power-up 1 1.2 during the power-up 3 1.3 during the operation 3 1.4 after the power-off 4 chapter 2 standards and specifications 5 2.1 label description 5 2.2 particular specifications 6 2....

  • Page 5

    Hlp-a100 series operating manual hlp-a100 series 6.7 parameter group 06: analog in/out 95 6.8 parameter group 07: controller 103 6.9 parameter group 08: comm. And options 106 6.10 parameter group 13: simple plc 110 6.11 parameter group 14: special functions 118 6.12 parameter group 15: drive informa...

  • Page 6

    Hlp-a100 series hlp-a100 series operating manual - 5 - 12.6 preset single register 175 12.7 force multiple coils 176 12.8 preset multiple regs 177 12.9 read/write array 178 12.10 exception code 179.

  • Page 7

    Hlp-a100 series operating manual hlp-a100 series - 6 -.

  • Page 8: Introduction

    Hlp-a100 series hlp-a100 series operating manual - 1 - caution ● check to be sure that the voltage of the main circuit ac power supply matches the input voltage of the inverter. ● install the inverter in a safe location, avoiding high temperature, direct sunlight, humid air or water. ● the inverter ...

  • Page 9

    Hlp-a100 series operating manual hlp-a100 series - 2 - danger ● be sure to turn off the power supply before wiring. ● mount the drive in the metal and other non-combustible materials to avoid the risk of fire. ● don’t install the drive in a space with explosive gas, otherwise, they lead to explosion...

  • Page 10: 1.2  During The Power-Up

    Hlp-a100 series hlp-a100 series operating manual - 3 - correct. Otherwise it will cause damages of the inverter when the power is applied to it. ● the terminal of must be grounded separately and never connected to n-line. Otherwise it will easily cause the protection or errors of the inverter. ● do ...

  • Page 11: 1.4  After The Power-Off

    Hlp-a100 series operating manual hlp-a100 series - 4 - caution ● even in the case of the main power, the other voltage inputs and the share load (linkage of dc intermediate circuit) all have been disconnected from the mains, the internal of the drive still have residual energy. Before touching any p...

  • Page 12: 2.1  Label Description

    Hlp-a100 series hlp-a100 series operating manual - 5 - chapter 2 standards and specifications 2.1 label description significance of the type code: 1-8 hlp-a100 indicate product series 9-12 0075 indicate 75kw 13-14 21 indicate 1-phase ac 220v 23 indicate 3-phase ac 220v 43 indicate 3-phase ac 380v 15...

  • Page 13

    Hlp-a100 series operating manual hlp-a100 series - 6 - 2.2 particular specifications model input voltage input current/ a output current/ a rated power/ kw suitable motor/ kw net weight/ kg hlp-a100001143 3×380-440v50/60hz 35.9 25 11 11 5.8 3×440-480v50/60hz 31.4 22.7 hlp-a100001543 3×380-440v50/60h...

  • Page 14

    Hlp-a100 series hlp-a100 series operating manual - 7 - 2.3 technical specifications item specif ication power supply supply voltage three phase 380-480v -20%-+10%; frequency 48-62hz; max. Imbalance 3%; motor output output voltage three phase 0-100% of supply voltage; output f requency v/f : 0-400hz ...

  • Page 15

    Hlp-a100 series operating manual hlp-a100 series - 8 - item specif ication protection functions missing motor phase protection; low-voltage protection; over-voltage protection; over-current protection; output phase loss protection; output short circuit protection; out put grounding fault protection;...

  • Page 16

    Hlp-a100 series hlp-a100 series operating manual - 9 - item specif ication control terminals analog output output number 2 analog outputs ( vo 、 ao ) , vo can be selected to the current output or voltage output via jumper switch in the control board. Ao can only be selected as current output . Up to...

  • Page 17

    Hlp-a100 series operating manual hlp-a100 series - 10 - item specif ication environment enclosure ip20; ambient temperature -10℃ - 40℃ ; humidity 5%-85% ( 95% without condensation); vibration test ≤75kw:1.14g;90-220kw:0.7g; max. Altitude above sea level 1000m, derating use when more than 1000 meters...

  • Page 18

    Hlp-a100 series hlp-a100 series operating manual - 11 - chapter 3 installation and wiring 3.1 checks before installation 3.2 installation dimensions 3.2.1 dimensions of lcp the inverter has been strictly and well packed before sold. In consideration of various factors during the transportation speci...

  • Page 19

    Hlp-a100 series operating manual hlp-a100 series - 12 - 3.2.2 dimensions of the inverter item model frame size and installation dimension a3 hlp-a100001143 hlp-a100001543 a4 hlp-a10018d543 hlp-a100002243 a5 hlp-a100003043 hlp-a100003743 a6 hlp-a100004543 hlp-a100005543 hlp-a100007543 a7 hlp-a1000090...

  • Page 20

    Hlp-a100 series hlp-a100 series operating manual - 13 - installation dimensions of the inverter: details of terminal tightening torques: 3.3 installation and wiring 3.3.1 electrical installation in general caution ● all cabling must comply with national and local regulations on cable cross-sections ...

  • Page 21

    Hlp-a100 series operating manual hlp-a100 series - 14 - 3.3.3 installation and direction single installation the inver ter must be installed vertically with smooth ventilation. Enough space must be lef t around the inverter to ensure good cooling, as shown below: min:100 mm min:100 mm side by side i...

  • Page 22

    Hlp-a100 series hlp-a100 series operating manual - 15 - fig. 3 upper and lower installation upper and lower installation if several inver ters need to be installed together in one cabinet, upper and lower installation can be adopted. Enough space must be reserved to ensure effective cooling, as show...

  • Page 23

    Hlp-a100 series operating manual hlp-a100 series - 16 - 3.3.4.2 i/o control terminals description of main circuit terminals: 30-75kw control and relay terminals: symbol function r 、 s 、 t power input u 、 v 、 w power output, connect to the motor -br 、 +br connect the brake resistor, make sure to set ...

  • Page 24

    Hlp-a100 series hlp-a100 series operating manual - 17 - description of i/o control terminals: symbol description specification vdd 24vpower supply max.Load 200ma, with over load and short circuit protection f unctions; +10v 10v power supply max.Load 10 ma, with over load and short circuit protection...

  • Page 25

    Hlp-a100 series operating manual hlp-a100 series - 18 - symbol description specification digital output (do1 、 do2) digital output 1 、 open collector output; 2 、 output current range: 0-50ma; 3 、 max voltage 30v; 4、 two different way to connect relay: v d d d o 1 d o 2 d c m c o m r e la y1 r e la y...

  • Page 26

    Hlp-a100 series hlp-a100 series operating manual - 19 - 3.3.5 wiring basic connection diagram of hlp-a100 series inverter: symbol description specification com digital ground isolated f rom internal gnd; relay output (ka-kb, fa- fb-fc) relay output 1 、 resistive load: 250vac 3a/30vdc 3a; 2 、 inducti...

  • Page 27

    Hlp-a100 series operating manual hlp-a100 series - 20 - precautions for the main circuit wiring: ● note: the drives of more than 30kw (including 30kw) do not have +br and –br terminals. ● while wiring the sizes and specifications of wires should be selected and the wiring should be executed accordin...

  • Page 28

    Hlp-a100 series hlp-a100 series operating manual - 21 - key-press lcp display action description c00.04 press key to display the first basic c00.03 c03.00 turn clockwise to select parameter group c03 c03.00 press key to shif t to f ractional part c03.10 turn clockwise to select parameter c03.10 chap...

  • Page 29

    Hlp-a100 series operating manual hlp-a100 series - 22 - key-press lcp display action description [0] press key show the first option of c03.10 0000 press key to show the value of the first option of parameter c03.10 000.5 turn clockwise to change the f ractional part to 5 000.5 press key to shif t t...

  • Page 30

    Hlp-a100 series hlp-a100 series operating manual - 23 - reference running status indicator display ≥0 rev < 0 fwd < 0 rev note: a flash light denotes the status coming, light on indicates the current state, and light off means not in this state. Example 1: the f irst line of the table indicates the ...

  • Page 31

    Hlp-a100 series operating manual hlp-a100 series - 24 - display items key-press lcp display action description motor voltage show the motor voltage (c16.12) is 380.0v, display accuracy: 0.1 motor speed show the motor speed (c16.05) is 1440rpm, display accuracy:1 dc voltage show the dc voltage(c16.30...

  • Page 32

    Hlp-a100 series hlp-a100 series operating manual - 25 - key-press lcp display action description c00.04 press key to display the first basic c00.03. C15.00 turn clockwise to select par. Group no. C15. C15.00 press to select parameter number. C15.30 turn clockwise to select c15.30 display items key-p...

  • Page 33

    Hlp-a100 series operating manual hlp-a100 series - 26 - key-press lcp display action description [0] press to show the first option of c15.30 ** press to show the first fault record. [1] press to show the second fault record, it can display up to ten recent fault records in turn. Key-press lcp displ...

  • Page 34

    Hlp-a100 series hlp-a100 series operating manual - 27 - key-press lcp display action description c16.60 press to select c16.60. 0000 press to view the value in c16.60, 0100 indicates status of for 、 di1 、 di2 is 0, and status of rev is 1. 4.2.6 led display.

  • Page 35

    Hlp-a100 series operating manual hlp-a100 series - 28 - chapter 5 parameter overview item parameter no. Function description setting range unit default setting page no. Pa ram ete r g rou p 00: o pe rat ion /d isp lay *c00.03 regional settings 0: 50 hz; 1: 60 hz; 0 54 c00.04 operating state at power...

  • Page 36

    Hlp-a100 series hlp-a100 series operating manual - 29 - item parameter no. Function description setting range unit default setting page no. Pa ra m ete r g rou p01 : l oa d/m oto r *c01.01 motor control principle 0: u/f; 1: vcc+; 1 59 *c01.03 torque characteristics 0: constant torque; 1: mutative; 3...

  • Page 37

    Hlp-a100 series operating manual hlp-a100 series - 30 - item parameter no. Function description setting range unit default setting page no. Pa ra m ete r g rou p01 : l oa d/m oto r c01.50 motor magnetisation at zero speed 0~300 % 100 63 c01.52 min speed normal magnetising [hz] 0.0~10.0 hz 0.0 63 c01...

  • Page 38

    Hlp-a100 series hlp-a100 series operating manual - 31 - item parameter no. Function description setting range unit default setting page no. C01.82 min speed for function at stop [hz] 0.0~20.0 hz 0.0 68 c01.90 motor thermal protection 0: no protection; 1: thermister warning; 2: termister trip; 3: etr...

  • Page 39

    Hlp-a100 series operating manual hlp-a100 series - 32 - item parameter no. Function description setting range unit default setting page no. Pa ram eter g rou p 0 3: r efer en ce/ r am ps c03.03 maximum reference -4999.000~4999.000 50.000 72 c03.07 main reference calculation 0: preset reference + ref...

  • Page 40

    Hlp-a100 series hlp-a100 series operating manual - 33 - item parameter no. Function description setting range unit default setting page no. Pa ram eter g rou p 0 3: r efer en ce/ r am ps c03.51 ramp 2 ramp up time 0.05~3600.00 s * 78 c03.52 ramp 2 ramp down time 0.05~3600.00 s * 79 c03.60 ramp 3 typ...

  • Page 41

    Hlp-a100 series operating manual hlp-a100 series - 34 - item parameter no. Function description setting range unit default setting page no. Pa ram ete r g rou p 04: lim its/ w arn ing s c04.30 motor feedback loss f unction 0: no f unction; 1: freeze output; 3: jog; 4: max. Speed; 5: stop and trip; 1...

  • Page 42

    Hlp-a100 series hlp-a100 series operating manual - 35 - item parameter no. Function description setting range unit default setting page no. *c05.02 digital output do mode 0: pnp; 1: npn; 0 86 c05.10 terminal for digital input 0: no operation; 1: reset; 2: coast inverse; 3: coast and reset inverse; 4...

  • Page 43

    Hlp-a100 series operating manual hlp-a100 series - 36 - item parameter no. Function description setting range unit default setting page no. C05.15 terminal di4 digital or pulse input 92: scarcity water level; 93: over run water level; 18 86 pa ram ete r g rou p 05: d igit al i n/o ut c05.30 terminal...

  • Page 44

    Hlp-a100 series hlp-a100 series operating manual - 37 - item parameter no. Function description setting range unit default setting page no. Pa ram ete r g rou p 05: d igit al i n/o ut c05.40 relay function (ka-kb,fa- fb 、 fb-fc) 36: control word bit 11; 37: control word bit12; 40: out of reference r...

  • Page 45

    Hlp-a100 series operating manual hlp-a100 series - 38 - item parameter no. Function description setting range unit default setting page no. Pa ram ete r g rou p 05: d igit al i n/o ut c05.55 terminal di4 low frequency 0.020~49.999 khz 0.020 91 c05.56 terminal di4 high frequency 0.021~50.000 khz 50.0...

  • Page 46

    Hlp-a100 series hlp-a100 series operating manual - 39 - item parameter no. Function description setting range unit default setting page no. Pa ram ete r g rou p 05: d igit al i n/o ut c06.01 live zero timeout function 0: off; 1: freeze output; 2: stop; 3: jogging; 4: max. Speed; 5: stop and trip; 0 ...

  • Page 47

    Hlp-a100 series operating manual hlp-a100 series - 40 - item parameter no. Function description setting range unit default setting page no. Pa ram ete r g rou p 05: d igit al i n/o ut c06.25 terminal ai high ref./ feedb.Value -4999.000~4999.000 50.000 98 c06.26 terminal ai filter constant 0.01~10.00...

  • Page 48

    Hlp-a100 series hlp-a100 series operating manual - 41 - item parameter no. Function description setting range unit default setting page no. C06.93 terminal ao output min scale 0.00~200.00 % 0.00 101 c06.94 termianl ao max scale 0.00~200.00 % 100.00 102 pa ram ete r g rou p0 7: c on trol ler s c07.12...

  • Page 49

    Hlp-a100 series operating manual hlp-a100 series - 42 - item parameter no. Function description setting range unit default setting page no. Pa ram ete r g rou p 08: fc po rt s ett ing s c08.01 control site 0: digital and ctrl. Word; 1: digital only; 2: control word only; 0 106 c08.02 control word so...

  • Page 50

    Hlp-a100 series hlp-a100 series operating manual - 43 - item parameter no. Function description setting range unit default setting page no. Pa ram ete r g rou p 08: fc po rt s ett ing s c08.50 coasting select 0: digital input; 1: bus; 2: logic and; 3: logic or; 3 108 c08.51 quick stop select 0: digi...

  • Page 51

    Hlp-a100 series operating manual hlp-a100 series - 44 - item parameter no. Function description setting range unit default setting page no. Pa ram ete r g rou p 1 3: s im ple pl c c13.40 logic rule boolean 1 0~64 0.0 114 c13.41 logic rule operator 1 0~8 0 114 c13.42 logic rule boolean 2 same to c13....

  • Page 52

    Hlp-a100 series hlp-a100 series operating manual - 45 - item parameter no. Function description setting range unit default setting page no. Pa ram ete r g rou p 14 : s pec ial fu nc tio ns c14.23 trip lock 0: disable, trip lock fault reset do not need power off; 1: enable, trip lock fault reset need...

  • Page 53

    Hlp-a100 series operating manual hlp-a100 series - 46 - item parameter no. Function description setting range unit default setting page no. Pa ram ete r g rou p 15 : d riv e i nfo rm atio n c15.00 operating days 0~9999 d 121 c15.01 running hours 0~60000 h 121 c15.02 kwh counter 0~65535 121 c15.03 po...

  • Page 54

    Hlp-a100 series hlp-a100 series operating manual - 47 - item parameter no. Function description setting range unit default setting page no. C15.50 sof tware id power card view software id power card 124 c15.51 frequency converter serial number view frequency converter no. 124 c15.53 power card seria...

  • Page 55

    Hlp-a100 series operating manual hlp-a100 series - 48 - item parameter no. Function description setting range unit default setting page no. Pa ram ete r g rou p 16 : d ata r ea do uts c16.37 inv. Max. Current 0.00~655.35 a 128 c16.38 slc controller state 0~255 128 c16.40 wobble length 0.000~60.000 k...

  • Page 56

    Hlp-a100 series hlp-a100 series operating manual - 49 - item parameter no. Function description setting range unit default setting page no. C16.90 alarm word 0~0xfffffffful 132 c16.91 alarm word 2 0~0xfffffffful 133 c16.92 warning word 0~0x7ffffffful 133 c16.93 warning word 2 0~0x7ffffffful 134 pa r...

  • Page 57

    Hlp-a100 series operating manual hlp-a100 series - 50 - item parameter no. Function description setting range unit default setting page no. Pa ram et er g rou p 2 5: a pp . F un ctio ns c as cad e c25.33 recovery low pressure level delay time 0.0~3600.0 s 10.0 137 c25.34 over pressure warning level ...

  • Page 58

    Hlp-a100 series hlp-a100 series operating manual - 51 - item parameter no. Function description setting range unit default setting page no. Pa ram et er g rou p 2 5: a pp . F un ctio ns c as cad e c25.61 water level signal source 0: digital input; 1: analog input vi; 2: analog input ai; 8: pulse inp...

  • Page 59

    Hlp-a100 series operating manual hlp-a100 series - 52 - item parameter no. Function description setting range unit default setting page no. Pa ram ete r g rou p 3 0: w obb le f un ct ion c30.12 centre frequency mode 0: fixed; 1: auto decrease; 0 144 c30.13 delta frequency mode 0: relative to speed h...

  • Page 60

    Hlp-a100 series hlp-a100 series operating manual - 53 - note: reference signed with “*”in parameter no. Column means this parameter can’t be modified when the motor is running. In factory setting column, “*” means the default setting for this parameter is determined by the drive type. Item parameter...

  • Page 61

    Hlp-a100 series operating manual hlp-a100 series - 54 - chapter 6 parameter description 6.1 parameter group 00: operation/display c00.0* basic settings *c00.03 function description range unit default setting regional settings 0~1 1 option: [0] 50hz, motor frequency default value is 50 hz, see c01.23...

  • Page 62

    Hlp-a100 series hlp-a100 series operating manual - 55 - *c00.06 function description range unit default setting grid type 0~132 * option: [0] 200-240v/50hz/it-grid; [1] 200-240v/50hz/it-delta; [2] 200-240v/50hz; [10] 380-440v/50hz/it-grid; [11] 380-440v/50hz/it-delta; [12] 380-440v/50hz; [20] 440-48...

  • Page 63

    Hlp-a100 series operating manual hlp-a100 series - 56 - binary bit0 set-up no. Terminal state 0 1 1 2 attention: the set-up can be switched between linked set-ups (see c00.12) or when the motor is stop. C00.11 function description range unit default setting edit set-up 1~2 1 option: [1] set-up 1; [2...

  • Page 64

    Hlp-a100 series hlp-a100 series operating manual - 57 - c00.33 function description range unit default setting lcp display option 0~2047 0 description of the choice: lcp will be fixed to display the output frequency、reference and motor current. This parameter is used to show 11 basic operating state...

  • Page 65

    Hlp-a100 series operating manual hlp-a100 series - 58 - c00.41 function description range unit default setting [off/reset] key on lcp 0~2 1 option: [0] disabled, off/reset key has no function; [1] enabled, off/reset key stop signal and reset of any fault; [2] enabled reset only, reset only (fault), ...

  • Page 66

    Hlp-a100 series hlp-a100 series operating manual - 59 - *c01.00 function description range unit default setting configuration mode 0~3 0 option: [0] speed open loop,for general applications; [3] process closed loop,feedback signal is a process unit, such as: pressure、temperature etc. When process cl...

  • Page 67

    Hlp-a100 series operating manual hlp-a100 series - 60 - function: choose suitable torque characteristics, it is possible to run low energy consuming, as well as high torque applications. *c01.07 function description range unit default setting application configuration mode 0~3 0 option: [0] no funct...

  • Page 68

    Hlp-a100 series hlp-a100 series operating manual - 61 - *c01.23 function description range unit default setting motor frequency 20~400 hz * function: enter the rated motor frequency from the nameplate data. Description of the choice: default setting depends on the inverter size. Attention: changing ...

  • Page 69

    Hlp-a100 series operating manual hlp-a100 series - 62 - *c01.35 function description range unit default setting main reactance(hh) dep.Motor data Ω * *c01.30 function description range unit default setting stator resistance(r s ) dep.Motor data Ω * function: set stator resistance value. Enter the va...

  • Page 70

    Hlp-a100 series hlp-a100 series operating manual - 63 - c01.55 function description range unit default setting v/f characteristic-v 0~999.9 v 0/vn function: this parameter is an array parameter [0-5], used for setting voltage [v0-v5] at each frequency point to manually form a v/ f characteristic mat...

  • Page 71

    Hlp-a100 series operating manual hlp-a100 series - 64 - c01.56 function description range unit default setting v/f characteristic-f 0~400 hz 0/fn function: this parameter is an array parameter [0-5], used for setting frequency points [f0-f5] to manually form a v/f characteristic matching motor. Volt...

  • Page 72

    Hlp-a100 series hlp-a100 series operating manual - 65 - c01.62 function description range unit default setting slip compensation -400~399 % 100 function: dynamically adjust the output frequency of the motor, maintain the motor approaching a constant speed, and doesn’t vary with load changes. Descrip...

  • Page 73

    Hlp-a100 series operating manual hlp-a100 series - 66 - c01.63 function description range unit default setting slip compensation time constant 0.05~5.00 s 0.10 function: enter the slip compensation reaction speed. A high value results in slow reaction, and a low value results in quick reaction. If l...

  • Page 74

    Hlp-a100 series hlp-a100 series operating manual - 67 - c01.8* stop adjustments c01.80 function description range unit default setting function at stop 0~1 0 option: [0] coast, the inverter is off; [1] dc hold, the motor is energized with a dc current. See par. C02.00 dc hold current for more inform...

  • Page 75

    Hlp-a100 series operating manual hlp-a100 series - 68 - description of choice: this f unction is active in the following situations: stop command is given and output speed is ramped down to min. Speed for activating functions at stop; start command is removed (standby), and output speed is ramped do...

  • Page 76

    Hlp-a100 series hlp-a100 series operating manual - 69 - vi; [6] digital input di4, connect thermistor to digital input terminal di4; function: select the thermistor input terminal. Attention: analog input can’t be selected for other purpose when selected as thermistor resource. Digital input di4 can...

  • Page 77

    Hlp-a100 series operating manual hlp-a100 series - 70 - c02.02 function description range unit default setting dc braking time 0.0~60.0 s 10.0 function: this parameter defines dc brake current (c02.01) time during which dc-brake current is applied to the motor. Function: this parameter is for settin...

  • Page 78

    Hlp-a100 series hlp-a100 series operating manual - 71 - function: enter the maximum permissible current when using ac brake to avoid overheating of motor windings. 100% equals motor current set in c01.24. C02.17 function description range unit default setting over-voltage control 0~2 0 option: [0] d...

  • Page 79

    Hlp-a100 series operating manual hlp-a100 series - 72 - 6.4 parameter group 03: reference/ramps c03.0* reference limits c03.00 function description range unit default setting reference range 0~1 0 option: [0] min-max, reference set point ranges can have positive values only. [1] -max~+max, ranges ca...

  • Page 80

    Hlp-a100 series hlp-a100 series operating manual - 73 - c03.07 function description range unit default setting actual reference calculation 0~1 0 option: [0] preset reference + reference source 1,2,3 [1] preset reference priority description of choice: [0], actual reference = preset reference + refe...

  • Page 81

    Hlp-a100 series operating manual hlp-a100 series - 74 - c03.11 function description range unit default setting jog speed 0.0~400.0 hz 5.0 function: jog frequency is a fixed frequency that the drive supplies to the motor after the jog function is actived. Please refer to c05.1*, select [14]. Descript...

  • Page 82

    Hlp-a100 series hlp-a100 series operating manual - 75 - c03.13 function description range unit default setting speed up/down value 0.01~50.00 hz 0.10 function: enter the speed up/down value. To the actual reference constituting new setting at which the frequency converter is going to run, calculated...

  • Page 83

    Hlp-a100 series operating manual hlp-a100 series - 76 - c03.15 function description range unit default setting reference resource1 0~21 1 c03.16 function description range unit default setting reference resource2 0~21 2 c03.17 function description range unit default setting reference resource3 0~21 ...

  • Page 84

    Hlp-a100 series hlp-a100 series operating manual - 77 - c03.19 function description range unit default setting save speed up/down value 0~2 0 option: [0] no function; [1] stop save; [2] power down save; function: this parameter is used for setting whether to save the data changed in the up/down f un...

  • Page 85

    Hlp-a100 series operating manual hlp-a100 series - 78 - c03.41 function description range unit default setting ramp1ramp up time 0.05~3600.00 s * function: enter the ramp-up time f rom 0 hz to rated motor speed in c01.25. Attention: choose a rame-up time such that the output current does not exceed ...

  • Page 86

    Hlp-a100 series hlp-a100 series operating manual - 79 - c03.51 function description range unit default setting ramp2 ramp up time 0.05~3600.00 s * function: enter the ramp-up time f rom 0hz to rated motor speed in c01.25. Attention: choose a ramp-up time such that the output current does not exceed ...

  • Page 87

    Hlp-a100 series operating manual hlp-a100 series - 80 - c03.72 function description range unit default setting ramp4 ramp down time 0.05~3600.00 s * c03.70 function description range unit default setting ramp4 type 0~2 0 option: [0] linear: motor ramp up to the preset f requency with a constant acce...

  • Page 88

    Hlp-a100 series hlp-a100 series operating manual - 81 - description of choice: quick stop ramp down time is applicable when quick stop ramp time is activated, see c05.1*, choose [4]. 6.5 parameter group 04: limits/warnings c04.1* motor limits *c04.10 function description range unit default setting m...

  • Page 89

    Hlp-a100 series operating manual hlp-a100 series - 82 - c04.30 function description range unit default setting motor feedback loss function 0~11 1 4 c04.21 function description range unit default setting max output frequency resource 0~21 0 1 *c04.19 function description range unit default setting m...

  • Page 90

    Hlp-a100 series hlp-a100 series operating manual - 83 - c04.31 function description range unit default setting motor feedback speed error 1~600 rpm 300 function: select the max allowed tracking error in speed f rom calculated and the actual mechanical motor shaf t output speed. C04.32 function descr...

  • Page 91

    Hlp-a100 series operating manual hlp-a100 series - 84 - c04.55 function description range unit default setting warning reference high -4999.000~4999.000 50.000 function: enter the upper reference limit, when the actual reference exceeds this limit, the display reads ref high. C04.56 function descrip...

  • Page 92

    Hlp-a100 series hlp-a100 series operating manual - 85 - c04.6* speed bypass c04.61 function description range unit default setting bypass speed from 0.0~400.0 hz 0.0 array: [3] function: this parameter is a dyadic array, [0] is used to set the bypass speed f rom of bypass speed range 1, [1] is used ...

  • Page 93

    Hlp-a100 series operating manual hlp-a100 series - 86 - c05.10 function description range unit default setting terminal for digital input 0~93 8 *c05.02 function description range unit default setting digital output do mode 0~1 0 option: [0] pnp, action on positive directional pulse; [1] npn, action...

  • Page 94

    Hlp-a100 series hlp-a100 series operating manual - 87 - [1] reset, reset the f requency converter af ter a trip/alarm; [2] coast inverse, no output, leaving the motor coasting to stop; [3] coast and reset inverse, the f requency converter resets leaving the motor coasting to stop. [4] quick stop inv...

  • Page 95

    Hlp-a100 series operating manual hlp-a100 series - 88 - c05.30 function description range unit default setting terminal do1 digital ouput 0~108 0 c05.3* digital output attention: because the do1 also can be used as pulse output, so select [0] digital output in c05.60 to make this parameter active; c...

  • Page 96

    Hlp-a100 series hlp-a100 series operating manual - 89 - array: [0]-[1] array[0] indicates relay1, array[1] indicates relay2. Option: [0] no operation; [1] control ready, inverter control card have received supply voltage; [2] drive ready, frequency converter is ready for operation and applies supply...

  • Page 97

    Hlp-a100 series operating manual hlp-a100 series - 90 - [26] bus ok. Local bus communication is normal; [28] brake-no warning. Brake is active, and no warnings are present; [29] brake ready/no fault. Brake is ready for operation, and no fault is present; [30] brake fault (igbt) . Brake igbt module f...

  • Page 98

    Hlp-a100 series hlp-a100 series operating manual - 91 - [104] low water warning. See par. C25*; [105] high water warning. See par. C25*; [106] low voltage warning. See par. C25*; [107] over-voltage warning. See par. C25*; [108] sleep, see par. C25*;.

  • Page 99

    Hlp-a100 series operating manual hlp-a100 series - 92 - c05.57 function description range unit default setting terminal di4 low ref./feedback 4999.000~4999.000 0.000 c05.55 function description range unit default setting terminal di4 low frequency 0.020~49.999 khz 0.020 c05.5* pulse input function: ...

  • Page 100

    Hlp-a100 series hlp-a100 series operating manual - 93 - c05.58 function description range unit default setting terminal di4 high ref. /feedback 4999.000~4999.000 50.000 function: enter high ref./feedback corresponding to value in c05.56. C05.59 function description range unit default setting termina...

  • Page 101

    Hlp-a100 series operating manual hlp-a100 series - 94 - function: define the mnimum possible f requency for pulse output. C05.61 function description range unit default setting pulse output min. Freq. 0.020~49.999 khz 0.020 function: enter max. F requency for pulse output. C05.62 function descriptio...

  • Page 102

    Hlp-a100 series hlp-a100 series operating manual - 95 - c05.7* encoder input *c05.70 function description range unit default setting encoder per revolution 256~4096 1024 function: encoder resolution (pulses for each revolution of the motor shaf t, see c05.70) is determined by the maximum f requency ...

  • Page 103

    Hlp-a100 series operating manual hlp-a100 series - 96 - function: enter vi low voltage corresponding to min. Reference/feedback set in c06.14. C06.1* analoge input 1 c06.10 function description range unit default setting terminal vi low voltage 0.00~9.99 v 0.07 function: enter vi high voltage corres...

  • Page 104

    Hlp-a100 series hlp-a100 series operating manual - 97 - function: enter vi high ref./feedb. Corresponding to max voltage or max current set in c06.11 or c06.13. C06.15 function description range unit default setting terminal vi high ref. /feedb. -4999.000~4999.000 50.000 c06.16 function description ...

  • Page 105

    Hlp-a100 series operating manual hlp-a100 series - 98 - description of choice: point a as shown in the figure is the analog value that corresponds to a setpoint that equals 0. It is calculated via analog low、 high values and low、 high references. Uab=uac=c06.18/2 option: [0] voltage mode; [1] curren...

  • Page 106

    Hlp-a100 series hlp-a100 series operating manual - 99 - c06.26 function description range unit default setting terminal ai filter time constant 0.01~10.00 s 0.01 function: this reference signal should correspond to max. Reference/feedback value set in c06.25. C06.23 function description range unit d...

  • Page 107

    Hlp-a100 series operating manual hlp-a100 series - 100 - option: [0] voltage mode; [1] current mode; function: select the input to be present on analog input ai. C06.29 function description range unit default setting terminal ai mode 0~1 0 option: [0] 0-20ma; [1] 4-20ma; [3] 0-10v; function: select ...

  • Page 108

    Hlp-a100 series hlp-a100 series operating manual - 101 - c06.81 function description range unit default setting lcp potmeter low ref. -4999.000~4999.000 0.000 [22] value on analog input vi, (0-10v) or (0/4-20ma) corresponding to references f rom c06.10、 c06.12 to c06.11、 c06.13; [23] value on analog...

  • Page 109

    Hlp-a100 series operating manual hlp-a100 series - 102 - c06.82 function description range unit default setting lcp potmeter high ref. -4999.000~4999.000 50.000 function: this reference value corresponding to potentiometer turned f ully clockwise. Option: [0] 0-20ma; [1] 4-20ma; function: select the...

  • Page 110

    Hlp-a100 series hlp-a100 series operating manual - 103 - function: scale maximum output of selected analog signal at terminal ao as percentage of maximum signal value. Function: torque pi proportional gain, choose a higher value causes the controller response more quickly, but too high will cause th...

  • Page 111

    Hlp-a100 series operating manual hlp-a100 series - 104 - c07.30 function description range unit default setting process pi normal/ inverse control 0~1 0 option: [0] normal, f requency converter is to reduce/increase the output f requency if the feedback signal is larger/lower than reference; [1] inv...

  • Page 112

    Hlp-a100 series hlp-a100 series operating manual - 105 - c07.41 function description range unit default setting process pi output low -100-100 % 0 function: the proportional gain indicates the number of times the error between the set point and the feedback signal is to be applied. Quick control is ...

  • Page 113

    Hlp-a100 series operating manual hlp-a100 series - 106 - c08.03 function description range unit default setting control word time out time 0.1~6500.0 s 1.0 c07.42 function description range unit default setting process pi output high -100-100 % 100 function: process pi controller output high limit, ...

  • Page 114

    Hlp-a100 series hlp-a100 series operating manual - 107 - c08.06 function description range unit default setting reset control word time out 0~1 0 option: [0] no f unction control word timeout is not reset; [1] do reset control word timeout is reset; function: resetting control word timeout will remo...

  • Page 115

    Hlp-a100 series operating manual hlp-a100 series - 108 - c08.33 function description range unit default setting fc port parity 0~3 2 option: [0] even parity (1 stop bit); [1] odd parity (1 stop bit); [2] no parity (1 stop bit); [3] no parity (2 stop bit); function: this parameter only effective for ...

  • Page 116

    Hlp-a100 series hlp-a100 series operating manual - 109 - c08.52 function description range unit default setting dc brake select 0~3 3 option: [0] digital input, aciviate via a digital input; [1] bus, activate via serial communication port; [2] logic and, activate via serial communication port and a ...

  • Page 117

    Hlp-a100 series operating manual hlp-a100 series - 110 - [3] logic or, activate via serial communication port or a digital input; function: select control of set-up select f unction via digital input or bus. C08.56 function description range unit default setting preset reference select 0~3 3 option:...

  • Page 118

    Hlp-a100 series hlp-a100 series operating manual - 111 - c13.01 function description range unit default setting start event 0~54 39 option: [0] false, enter “false” in logic rule; [1] true, enter “true” in logic rule; [2] running, for detailed information, please refer to c05.4*[5]; [3] in range-no ...

  • Page 119

    Hlp-a100 series operating manual hlp-a100 series - 112 - [25] comparator 3, output of comparator 3 is used in logic rules; [26] logic rule 0, result of logic rule 0 is used in logic rules; [27] logic rule 1, result of logic rule 1 is used in logic rules; [28] logic rule 2, result of logic rule 2 is ...

  • Page 120

    Hlp-a100 series hlp-a100 series operating manual - 113 - c13.10 function description range unit default setting comparator operand 0~31 0 array: [4] ; option: [0] disabled; [1] reference [hz] ; [2] feedback [%], feedback signal (0-10v) or (0/4-20ma) corresponds to -200% ~ 200%; [3] motor speed [hz] ...

  • Page 121

    Hlp-a100 series operating manual hlp-a100 series - 114 - c13.12 function description range unit default setting comparator value -9999.0~9999.0 0.0 c13.20 function description range unit default setting simple plc timer 0.00~3600.00 s 0.00 array: [8]; function: enter the value to define the duration...

  • Page 122

    Hlp-a100 series hlp-a100 series operating manual - 115 - c13.42 function description range unit default setting logic rule boolean 2 0~64 0 array: [4]; option: please refer to c13.01; function: select the second boolean (“true or false”) input for the selected logic rule. C13.43 function description...

  • Page 123

    Hlp-a100 series operating manual hlp-a100 series - 116 - c13.44 function description range unit default setting logic rule boolean 3 0~64 0 array: [4]; option: please refer to c13.01; function: select the third boolean (“true or false”) input for the selected logic rule. C13.51 function description ...

  • Page 124

    Hlp-a100 series hlp-a100 series operating manual - 117 - [24] stop, issues a stop command to the f requency converter; [25] qstop, issues a quick stop command to the f requency converter; [26] dcstop, issues a dc stop command to the f requency converter; [27] coast, the f requency converter coasts i...

  • Page 125

    Hlp-a100 series operating manual hlp-a100 series - 118 - c14.01 function description range unit default setting switching frequency 0~10 4 option: [2] - [6] 2-6khz; [7] 8khz; [8] 10khz; [9] 12khz; [10] 16khz; description of choice: switching f requency of the f requency converter has a signif icant ...

  • Page 126

    Hlp-a100 series hlp-a100 series operating manual - 119 - c14.12 function description range unit default setting function at mains imbanlance 0~3 0 c14.16 function description range unit default setting low voltage mode 0~1 0 option: [0] trip, f requency converter trips; [1] warning, f requency conve...

  • Page 127

    Hlp-a100 series operating manual hlp-a100 series - 120 - c14.27 function description range unit default setting action at inverter fault 0~1 0 option: [0] trip, inverter trips if it detects an inverter fault; [1] warning, inverter issues an alarm if it detects an inverter fault; function: select how...

  • Page 128

    Hlp-a100 series hlp-a100 series operating manual - 121 - *c14.40 function description range unit default setting vt level 40~90 % 90 function: selection of a proper value reduces energy loss in the motor. *c14.41 function description range unit default setting aeo min. Magnetisation 40~75 % 66 funct...

  • Page 129

    Hlp-a100 series operating manual hlp-a100 series - 122 - *c14.55 function description range unit default setting output filter 0~3 0 option: [0] off; [1] sine-wave filter; [3] sine-wave filter with feedback; function: select desired output filter. *c14.50 function description range unit default sett...

  • Page 130

    Hlp-a100 series hlp-a100 series operating manual - 123 - *c14.63 function description range unit default setting min. Switching frequency 2~10 khz 2 option: [2] - [6] 2-6khz; [7] 8khz; [8] 10khz; [9] 12 khz; [10] 16 khz; function: enter the minimum switching f requency. C14.6* min. Switching frequen...

  • Page 131

    Hlp-a100 series operating manual hlp-a100 series - 124 - c15.05 function description range unit default setting over voltages 0~65535 function: view the number of drive overvoltages that have occurred. This parameter can’t be reset. C15.06 function description range unit default setting reset kwh co...

  • Page 132

    Hlp-a100 series hlp-a100 series operating manual - 125 - c15.40 function description range unit default setting fc type 0~255 description of choice: view fc type. C15.41 function description range unit default setting power section 0~255 description of choice: view the power size of the f requency c...

  • Page 133

    Hlp-a100 series operating manual hlp-a100 series - 126 - c15.50 function description range unit default setting software id power card description of choice: view the power card id number. C15.51 function description range unit default setting fc serial number description of choice: view the drives ...

  • Page 134

    Hlp-a100 series hlp-a100 series operating manual - 127 - c16.01 function description range unit default setting reference -4999.000~4999.000 d c16.00 function description range unit default setting control word 0~65535 d function: view latest valid control word that sent to f requency converter via ...

  • Page 135

    Hlp-a100 series operating manual hlp-a100 series - 128 - c16.02 function description range unit default setting reference (%) -200.0~200.0 % function: view total remote reference in percentage, the total reference is sum of pulse, analog, preset, lcp potmeter, local bus and f reeze reference. C16.03...

  • Page 136

    Hlp-a100 series hlp-a100 series operating manual - 129 - c16.05 function description range unit default setting motor speed [rpm] 0~9999 hz function: view motor speed. C16.09 function description range unit default setting custom readout 0.000~9999.00 function: view the value of user-def ined readou...

  • Page 137

    Hlp-a100 series operating manual hlp-a100 series - 130 - c16.15 function description range unit default setting frequency(%) 0.0~200.0 % function: view actual output f requency that is set in percentage. C16.18 function description range unit default setting motor thermal 0~100 % function: view calc...

  • Page 138

    Hlp-a100 series hlp-a100 series operating manual - 131 - c16.52 function description range unit default setting feedback -4999.000~4999.000 function: view sum of all external references in percent. C16.40 function description range unit default setting wobble length 0.000~60.000 km c16.4* applicatio...

  • Page 139

    Hlp-a100 series operating manual hlp-a100 series - 132 - option: [0]: 0-20ma; [1]: 0-10v; function: view actual state of analog input vi. C16.61 function description range unit default setting terminal vi setting 0~1 function: view actual input voltage or current value on analog input vi. C16.62 fun...

  • Page 140

    Hlp-a100 series hlp-a100 series operating manual - 133 - c16.67 function description range unit default setting encoder input -9999.000~9999.000 hz function: view input f requency on pulse input terminal di4 c16.68 function description range unit default setting pulse input di4 0.020~50.000 khz func...

  • Page 141

    Hlp-a100 series operating manual hlp-a100 series - 134 - function: view the last received reference f rom the fc port. C16.86 function description range unit default setting fc port reference -32768~32767 c16.8* field bus/fc port function: view the alarm word sent via the serial communication port i...

  • Page 142

    Hlp-a100 series hlp-a100 series operating manual - 135 - c16.91 function description range unit default setting alarm word 2 0~0xffffffffuf function: view the alarm word sent via serial communication port in hex code. C16.92 function description range unit default setting warning word 1 0~0x7fffffff...

  • Page 143

    Hlp-a100 series operating manual hlp-a100 series - 136 - c16.93 function description range unit default setting warning word 2 0~0x7fffffffuf function: view warning word 2 sent via serial communication port in hex code. C25.00 function description range unit default setting cascade mode 0~1 0 option...

  • Page 144

    Hlp-a100 series hlp-a100 series operating manual - 137 - c25.20 function description range unit default setting cascade low frequency 0.000~400.000 hz 20.000 function: in cascade control systems, due to less consumption, the inverter output f requency is low, when output f requency is below the “cas...

  • Page 145

    Hlp-a100 series operating manual hlp-a100 series - 138 - c25.25 function description range unit default setting cascade high frequency 0.000~400.000 hz 50.000 function: in cascade controller systems, due to larger amount of water consumption, the inverter output f requency is high, when the output f...

  • Page 146

    Hlp-a100 series hlp-a100 series operating manual - 139 - c25.33 function description range unit default setting recovery low pressure 0.0~3600.0 s 10.0 function: this parameter used together with “recovery low pressure level” (c25.32). C25.34 function description range unit default setting over pres...

  • Page 147

    Hlp-a100 series operating manual hlp-a100 series - 140 - c25.41 function description range unit default setting pump continous run time 0.0~3600.0 h 12.0 function: when only one of the two auxiliary pump running, in order to balance the two auxiliary pump run time, when one of the two lag pumps cont...

  • Page 148

    Hlp-a100 series hlp-a100 series operating manual - 141 - c25.52 function description range unit default setting sleep pressure delay 0.0~300.0 s 20.0 function: def ine the sleep pressure duration before the main pump enter sleep mode. C25.53 function description range unit default setting sleep freq...

  • Page 149

    Hlp-a100 series operating manual hlp-a100 series - 142 - c25.60 function description range unit default setting pump type selection 0~1 0 option: [0] feed pump; [1] draining pump; function: there are two kinds of water level control, one is used for feed pump, and the other is used for draining pump...

  • Page 150

    Hlp-a100 series hlp-a100 series operating manual - 143 - c25.62 function description range unit default setting scarcity water level 0~100 % 0 function: set the scarcity water level, the setting rang is f rom 0 to low water level. 100% corresponding to the pool water level at10v voltage. C25.63 func...

  • Page 151

    Hlp-a100 series operating manual hlp-a100 series - 144 - c25.69 function description range unit default setting water level di delay time 0~3600.0 s 20.0 c25.68 function description range unit default setting water level dead band 0~100 % 5 function: when the “water level signal source” selects “ana...

  • Page 152

    Hlp-a100 series hlp-a100 series operating manual - 145 - option: [0]auto; [1]: manul; function: if [0] is selected, dirve must stay at dwell stage for a period of dwell time if no wobble cycle start command, but if wobble cycle start command occurs (lantched input type can be accepted also), dwell s...

  • Page 153

    Hlp-a100 series operating manual hlp-a100 series - 146 - disappeared, drive will ramp to dwell stage and wait for wobble cycle start command to end dwell stage. In auto mode, there are running on center f requency and running on dwell f requency two ways to select for wobble reset. But in manul mode...

  • Page 154

    Hlp-a100 series hlp-a100 series operating manual - 147 - c30.13 function description range unit default setting delta frequency mode 0~1 0 option: [0]: relative to speed high; [1]: relative to center f requency; delta can change with the center f requency. The relative percentage will be set in c30....

  • Page 155

    Hlp-a100 series operating manual hlp-a100 series - 148 - c30.20 function description range unit default setting random function mode 0~1 0 option: [0] : disable; [1] : enable; function: if [0] is selected, wobble up time and wobble down time are not randomized. If [1] is selected, the actual wobble ...

  • Page 156

    Hlp-a100 series hlp-a100 series operating manual - 149 - c30.32 function description range unit default setting length setting 0.000~60.000 km 10.000 function: when wobble length reaches to the value set in this parameter, setting length reached action becomes active. C30.33 function description ran...

  • Page 157

    Hlp-a100 series operating manual hlp-a100 series - 150 - chapter 7 quick application guide 7.1 motor parameter adaption 7.2 using lcp to control the drive [hand] 1. Parameter initialization. (c14.22 =2); 2. Resboot the drive; 3. Enter motor nameplate data to c01.20 to c01.25. 4. Choose option [2] of...

  • Page 158: 7.4 Set-Up Selection

    Hlp-a100 series hlp-a100 series operating manual - 151 - 7.3 using digital in terminals to control the drive [auto] 7.4 set-up selection 1. Parameter initialization (c14.22=2); 2. Press “auto” key on lcp (digital control and communication control are only active in auto mode); 3. Frequency source: p...

  • Page 159

    Hlp-a100 series operating manual hlp-a100 series - 152 - 7.5 potentiometer reference 7.6 connect two-wire transductor to terminal ai par. Code reference parameter description c03.15 1 reference resource 1 c06.14 ** terminal vi low reference c06.15 ** terminal vi high reference note: **indicates this...

  • Page 160: 7.8 Multi-Speed

    Hlp-a100 series hlp-a100 series operating manual - 153 - 7.7 reference for pulse input 7.8 multi-speed par. Code reference parameter description c03.15 8 select reference c07.20 8 select feedback value c05.15 32 reference/feedback resource par. Code reference parameter description c05.12 15 preset r...

  • Page 161: 7.9 Speed Up/down

    Hlp-a100 series operating manual hlp-a100 series - 154 - correspondence between speed and the binary code as below: bit3 bit2 bit1 bit0 -speed 0 0 0 0 1 0 0 0 1 2 0 0 1 0 3 0 0 1 1 4 0 1 0 0 5 0 1 0 1 6 0 1 1 0 7 0 1 1 1 8 1 0 0 0 9 1 0 0 1 10 1 0 1 0 11 1 0 1 1 12 1 1 0 0 13 1 1 0 1 14 1 1 1 0 15 1...

  • Page 162: 7.10 Pulse Start/stop

    Hlp-a100 series hlp-a100 series operating manual - 155 - corresponding relation between ramp time and the binary code as below: 7.10 pulse start/stop 7.11 digital speed up/down bit1 bit0 ramp 0 0 1 0 1 2 1 0 3 1 1 4 par. Code reference parameter description c05.10 9 lantched start c05.11 6 stop inve...

  • Page 163: 7.12 Configuration Mode

    Hlp-a100 series operating manual hlp-a100 series - 156 - par. Code reference parameter description c05.10 8 start c05.11 19 freeze reference c05.12 21 speed up c05.13 22 speed down 7.12 configuration mode there is a choice of the following configurations: 1. Speed control, open loop; 2. Process cont...

  • Page 164

    Hlp-a100 series hlp-a100 series operating manual - 157 - parameter code reference parameter description c01.00 3 processcontrol, closed loop c07.20 process cl feedback resource c06.22 4ma terminal ai low current c06.23 20ma terminal ai high current c06.24 ** terminal ai low ref./ feedb. Value c06.25...

  • Page 165: 7.13 Simple Plc

    Hlp-a100 series operating manual hlp-a100 series - 158 - 7.13 simple plc 7.13.1 order execution the following figure shows order execution mode of four events/actions: use order execution to achieve eight-speed internal control function : parameter ref. Function parameter ref. Function c03.10[0] 20 ...

  • Page 166

    Hlp-a100 series hlp-a100 series operating manual - 159 - parameter ref. Function parameter ref. Function c03.10[6] 10 preset reference 6 c13.20[6] 3 timer 6 time c03.10[7] 80 preset reference 7 c13.20[7] 6 timer 7 time c03.40 0 ramp 1 type c03.50 0 ramp 2 type c03.41 0.5 ramp 1 ramp up time c03.51 3...

  • Page 167

    Hlp-a100 series operating manual hlp-a100 series - 160 - 7.13.2 parallel execution the following figure shows parallel execution mode of four events/actions: example: 1. Start event c13.01 = [33] enter the start event via digital input terminal for; c13.00) = [2] simple plc parallel control mode; c1...

  • Page 168: 8.1 Braking Resistor

    Hlp-a100 series hlp-a100 series operating manual - 161 - chapter 8 accessory specification 8.1 braking resistor when the motor acts as a generator, the braking resistor consumes surplus energy resulting from motor braking to achieve fast stop. And to prevent the intermediate circuit voltage is too h...

  • Page 169: 8.2 Lcp Mounting Kit

    Hlp-a100 series operating manual hlp-a100 series - 162 - 63 95.7 63 95.7 63 95.7 8.2 lcp mounting kit external lcp communication cable is network cable. Length should not exceed 15m. More than five types of shielded cable is recommended for use in the presence of electromagnetic interference environ...

  • Page 170: Chapter 9 Emc

    Hlp-a100 series hlp-a100 series operating manual - 163 - chapter 9 emc 9.1 emc–correct installation hlp-a100 serials drive implement the latest international standards, following these guidelines is advised, iec/en61800-3: 2004 (adjustable speed electrical power drive systems part 3: emc requirement...

  • Page 171: 10.1 Fault List

    Hlp-a100 series operating manual hlp-a100 series - 164 - the hlp-a100 drive has three different fault types: warning, alarm and error. When a fault happens, the drive shows a specific code to indicate it. When a warning happens, it means that the drive is close to its design limits for some reason, ...

  • Page 172

    Hlp-a100 series hlp-a100 series operating manual - 165 - e.11 motor over temperature thermistor damage, uncorrectly installed or motor cooling equipment failure. A.12 e.12* torque limit torque exceeds the max. Torque limit. A.13 e.13* over current inverter peak current limit is exceeded. A.14 e.14* ...

  • Page 173

    Hlp-a100 series operating manual hlp-a100 series - 166 - e.46* gate drive voltage fault power card fault e.47* 24v power card fault 24v voltage power card failure e.48* vdd low voltage vdd voltage is too low. E.51 ama check unom and inom motor voltage and motor current error setting. E.52 ama low in...

  • Page 174

    Hlp-a100 series hlp-a100 series operating manual - 167 - a.76 e.76 igbt temperature sensor error u igbt temperature sensor error u a.77 e.77 igbt temperature sensor error v igbt temperature sensor error v a.78 e.78 igbt temperature sensor error w igbt temperature sensor error w a.79 e.79 undefined f...

  • Page 175

    Hlp-a100 series operating manual hlp-a100 series - 168 - 10.2 fault indication and trouble shooting the inverter of hlp-a100 serials is relatively perfective with protection f unctions of overload, inter-phase short circuit, earth short circuit, and over- current etc. When a protection f unction occ...

  • Page 176

    Hlp-a100 series hlp-a100 series operating manual - 169 - fault process method 5. Motor can’t rotate and screen display is normal without fault message press [enter] on lcp; make sure whether the screen is active i.E. The screen display can’t be switched or parameter can’t be edited; suppose screen i...

  • Page 177: Chapter 11 Maintenance

    Hlp-a100 series operating manual hlp-a100 series - 170 - chapter 11 maintenance 11.1 note 11.2 storage and transport conf irm the main circuit power supply has been turned off, and the display has disappeared before carry out inspection and maintenance. Make sure the system is in dynamic state, plea...

  • Page 178: 12.1 Format Specification

    Hlp-a100 series hlp-a100 series operating manual - 171 - chapter 12 communication protocol 12.1 format specification 12.2 coil addressing 1)address: 1-247 2)function: hlp-a100 support following f unction code 01: read coil status 03: read holding registers 05: force single coil 06: preset single reg...

  • Page 179

    Hlp-a100 series operating manual hlp-a100 series - 172 - status word coil address 0 1 00 preset reference bit0 01 preset reference bit1 02 dc brake no dc brake 03 coast stop no coast stop 04 quick-stop ramp 05 freeze freq no freeze freq 06 ramp stop start 07 no reset reset 08 no jog jog 09 ramp 1 ra...

  • Page 180: 12.3 Read Coil Status

    Hlp-a100 series hlp-a100 series operating manual - 173 - 44 reserved 45 no voltage warning voltage warning 46 not in current limit current limit 47 no thermal warning thermal warning register description 00000-00006 reserved 00007 the most recent error code from fc data interface 00008 parameter ind...

  • Page 181

    Hlp-a100 series operating manual hlp-a100 series - 174 - field description 01 fc address 01 function 02 the read byte number is 2 00 20 ouput frequency.Swap high and low, the data is 0x2000, so the output frequency is 50% of c03.03. Why does 0x2000 correspond to 50%, please see 12.6. B8 24 crc check...

  • Page 182: 12.5 Force Single Coil

    Hlp-a100 series hlp-a100 series operating manual - 175 - field description 01 fc address 05 function 00 40 0x0040 convert to decimal number is 64.The register address 64 is parameter write control ff 00 0000-parameter changes are written to the ram; ff00- parameter changes are written to the ram and...

  • Page 183: 12.7 Force Multiple Coils

    Hlp-a100 series operating manual hlp-a100 series - 176 - field description 01 fc address 06 function 03 f1 the register address of c01.01 is 101*10-1=1009(0x03f1) 00 01 the parameter value is 1 19 bd crc check field description 01 fc address 06 function 03 f1 the register address of c01.01 is 101*10...

  • Page 184: 12.8 Preset Multiple Regs

    Hlp-a100 series hlp-a100 series operating manual - 177 - 9a 19 frequency reference.“9a 19” swap high byte and low byte, the value is 0x199a.Frequency is 40% of c03.03(see the following frequency conversion specification). 37 b3 crc check frequency conversion specification: if you want to set the fre...

  • Page 185: 12.9 Read/write Array

    Hlp-a100 series operating manual hlp-a100 series - 178 - field description 01 fc address 06 function 00 08 register address(addrh addrl),the register address of parameter index is 0x0008 00 02 the index is 2(0x0002) 89 c9 crc check field description 01 fc address 06 function 00 08 register address(a...

  • Page 186: 12.10 Exception Code

    Hlp-a100 series hlp-a100 series operating manual - 179 - field description 01 fc address 10 function 0c 1b the register address of c03.10 is 310*10-1=3099(0x0c1b) 00 01 register number 02 byte number 00 00 the value of 310[2] is 0 69 bb crc check field description 01 fc address 10 function 0c 1b the...

  • Page 187

    Hlp-a100 series operating manual hlp-a100 series - 180 - 0x06 only use for reset 0x07 cannot be changed 0x0b not allowed to write 0x11 data cannot be changed in the current mode(some parameter cannot be changed when the inverter is running) 0x12 other exception 0x40 invalid data address 0x41 invalid...