IBM UPS3000 LV Installation And Maintenance Manual

Other manuals for UPS3000 LV: Manual

Summary of UPS3000 LV

  • Page 1

    Ups3000 lv and ups3000 hv installation and maintenance guide.

  • Page 3

    Ups3000 lv and ups3000 hv installation and maintenance guide.

  • Page 4

    Before using this information and the product it supports, read the general information in appendix b, “ibm statement of limited warranty z125-4753-08 04/2004,” on page 45 and appendix c, “notices,” on page 63. First edition (april 2006) © copyright international business machines corporation 2006. ...

  • Page 5: Safety

    Safety before installing this product, read the safety information. Antes de instalar este produto, leia as informações de segurança. Pred instalací tohoto produktu si prectete prírucku bezpecnostních instrukcí. Læs sikkerhedsforskrifterne, før du installerer dette produkt. Lees voordat u dit produc...

  • Page 6

    Antes de instalar este producto, lea la información de seguridad. Läs säkerhetsinformationen innan du installerar den här produkten. Important: all caution and danger statements in this documentation end with a number. This number is used to cross reference an english caution or danger statement wit...

  • Page 7

    Danger electrical voltage and current from power, telephone, and communication cables are hazardous. To avoid a shock hazard: v do not connect or disconnect any cables or perform installation, maintenance, or reconfiguration of this product during an electrical storm. V connect all power cords to a ...

  • Page 8

    Caution: lead-acid batteries can present a risk of electrical burn from high, short-circuit current. Avoid battery contact with metal materials; remove watches, rings, or other metal objects, and use tools with insulated handles. To avoid possible explosion, do not burn. Exchange only with the ibm-a...

  • Page 9

    The following general safety information should be used for all rack-mounted devices: danger v always lower the leveling pads on the rack cabinet. V always install stabilizer brackets on the rack cabinet. V to avoid hazardous conditions due to uneven mechanical loading, always install the heaviest d...

  • Page 10

    Warning: handling the cord on this product or cords associated with accessories sold with this product, will expose you to lead, a chemical known to the state of california to cause cancer, and birth defects or other reproductive harm. Wash hands after handling. Advertencia: el contacto con el cable...

  • Page 11: Contents

    Contents safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . Iii chapter 1. Introduction . . . . . . . . . . . . . . . . . . . . . . 1 the ibm documentation cd . . . . . . . . . . . . . . . . . . . . 1 hardware and software requirements . . . . . . . . . . . . . . . . 1 using the document...

  • Page 12

    Set ip addresses of primary and secondary date server . . . . . . . . . 30 ups event actions . . . . . . . . . . . . . . . . . . . . . . 30 set ups information . . . . . . . . . . . . . . . . . . . . . . 31 set superuser name and password . . . . . . . . . . . . . . . . 31 email notification . . . ....

  • Page 13: Chapter

    Chapter 1. Introduction the ibm ® ups3000 lv (low voltage) and ups3000 hv (high voltage) models are designed to prevent blackouts, brownouts, sags, and surges from reaching your servers and other valuable electronic equipment. The uninterruptible power supply filters small utility line fluctuations ...

  • Page 14

    Using the documentation browser use the documentation browser to browse the contents of the cd, read brief descriptions of the documents, and view documents, using adobe acrobat reader or xpdf. The documentation browser automatically detects the regional settings in use in your computer and displays...

  • Page 15

    Specifications the uninterruptible power supply includes the following specifications. Table 1. Ups3000 lv and ups3000 hv specifications ups3000 lv ups3000 hv height 89 mm (3.5 in.) 89 mm (3.5 in.) width 482.6 mm (19.0 in.) 482.6 mm (19.0 in.) depth 622.3 mm (24.5 in.) 622.3 mm (24.5 in.) additional...

  • Page 16

    Notices and statements in this document the caution and danger statements that appear in this document are also in the multilingual safety information document, which is on the ibm documentation cd. Each statement is numbered for reference to the corresponding statement in the safety information doc...

  • Page 17: Chapter

    Chapter 2. Installing the uninterruptible power supply in a rack or tower configuration this chapter describes the following tasks: v checking the package contents v installing the uninterruptible power supply in a tower configuration v connecting the internal battery v connecting the ups to ebms v ...

  • Page 18

    Tower configuration the following sections provide instructions for setting up the uninterruptible power supply and optional extended battery modules in a tower configuration. Caution: or >32 kg (70.5 lb) or 32-55 kg (70.5-121.2 lb) the weight of this part or unit is between 32 and 55 kg (70.5 and 1...

  • Page 19

    Setting up the uninterruptible power supply (with no extended battery module) if you are setting up the uninterruptible power supply with extended battery modules, see “setting up the uninterruptible power supply with an extended battery module” on page 8. To set up the uninterruptible power supply ...

  • Page 20

    Setting up the uninterruptible power supply with an extended battery module note: two sets of pedestals and two extended battery module brackets are required for this tower configuration. To set up the uninterruptible power supply with an extended battery module in a tower configuration, complete th...

  • Page 21

    6. Carefully position the chassis upright so that the air vents are at the top. Air vents 7. Attach the extended battery module brackets to the top of the uninterruptible power supply and extended battery module: a. Align each extended battery module bracket with the adjacent corner screw holes in t...

  • Page 22

    To set up the uninterruptible power supply with two or more extended battery modules in a tower configuration, complete the following steps: 1. Carefully position the chassis upright so that the air vents are at the top. Air vents 2. Attach the extended battery module brackets to the top of the unin...

  • Page 23

    3. Connect the internal battery connector. Note: a small amount of arcing might occur when connecting the batteries. This is normal and does not damage the unit or cause any safety concern. 4. Install the uninterruptible power supply front bezel. Important: before you move the uninterruptible power ...

  • Page 24

    To connect the uninterruptible power supply to the extended battery modules, complete the following steps: 1. Make sure that all battery circuit breakers on the extended battery modules are in the off position. Battery circuit breaker ups battery connector power cord web/snmp card input connector on...

  • Page 25

    Extended battery module cables extended battery module battery connectors uninterruptible power supply battery connector extended battery module brackets 2. Connect an extended battery module to the uninterruptible power supply using an extended battery module cable (see the illustration in step 1 o...

  • Page 26

    5. Press and hold the on button until you hear the uninterruptible power supply beep (approximately one second). The power-on led stops flashing and the load level leds display the percentage of load being applied to the uninterruptible power supply. The uninterruptible power supply is now in normal...

  • Page 27

    2. If installed, remove the remote emergency power-off connector from the remote emergency power-off port on the rear of the uninterruptible power supply. Remote emergency power-off port remote emergency power-off connector openings 3. Connect isolated, normally-open, dry contacts (rated to handle 6...

  • Page 28

    16 ups 3000 lv and ups3000 hv: installation and maintenance guide.

  • Page 29: Chapter

    Chapter 3. Uninterruptible power supply controls, leds, operating modes, and power this chapter describes the controls, light-emitting diodes (leds), connectors, operating modes, and how to turn the uninterruptible power supply on and off. Front view the following illustration shows the controls, le...

  • Page 30

    Alarm reset button: press this button to silence the alarm for an existing fault. Load level leds: when these leds are lit, they indicate the percentage of uninterruptible power supply load capacity being used by the connected devices. Rear view the following illustration shows the controls and conn...

  • Page 31

    V configuration normal mode during normal mode, the power-on led is lit and the front panel displays the percentage of uninterruptible power supply load capacity being used by the protected connected devices. The uninterruptible power supply monitors and charges the batteries as needed and provides ...

  • Page 32

    Led flashes and the load level leds are off, indicating that power is not available to the connected devices. The battery recharges when necessary. Note: for 200–240v models, the output receptacles might remain electrically live (up to 100–120v). Disconnect the power to the uninterruptible power sup...

  • Page 33

    The configuration mode leds and options are described in table 2. Use the following led legend for an explanation of the leds. Red flashing not lit green led legend table 2. Configuration mode leds and options configuration mode leds option led status explanation 100/200-208v nominal input voltage o...

  • Page 34

    Turning on the uninterruptible power supply after the uninterruptible power supply is connected to a power outlet, it enters standby mode. To turn on the uninterruptible power supply, press and hold the on button until you hear the uninterruptible power supply beep (approximately one second). The po...

  • Page 35

    The following illustration shows the three load segments in the ups3000 hv uninterruptible power supply. Load segment 2 load segment 3 load segment 1 chapter 3. Uninterruptible power supply controls, leds, operating modes, and power 23.

  • Page 36

    24 ups 3000 lv and ups3000 hv: installation and maintenance guide.

  • Page 37: Chapter

    Chapter 4. Using the web/snmp card this chapter provides detailed instructions for using the connectups web/snmp card that is located on the top left side on the rear of the uninterruptible power supply. Introduction the web/snmp card is a network device for the uninterruptible power supply that pro...

  • Page 38

    V history log files (data and events) for recording power problems. V uninterruptible power supply status information available to registered netwatch clients for automatic shutdown of microsoft windows 95/98/me/nt/2000/xp, mac os x, novell netware, and unix (various versions, including linux). V wi...

  • Page 39

    Web/snmp card leds and controls the following illustration shows the leds and controls on the web/snmp card. 10 mb network leds (yellow) dip switch reset button com connector 1 2 additional ethernet connectors 100 mb network leds (green) status led (yellow) power led (green) uplink ethernet connecto...

  • Page 40

    Connecting the card to a terminal or computer to connect the card to a terminal or computer and start the configuration utility, complete the following steps: 1. Connect the serial cable that comes with the uninterruptible power supply to the com connector on the web/snmp card. 2. Connect the other ...

  • Page 42

    Table 4. Web/snmp card configuration parameters with examples (continued) menu option number function description example 4 syscontact system contact string of mib (up to 127 characters) powerware 5 sysname system name parameter for mib (up to 127 characters web/snmp card 6 syslocation system locati...

  • Page 43

    Set ups information to enter additional information about the uninterruptible power supply including date of installation and date of last battery replacement, select option 7. You can also set timing values relating to the shutdown and restart of the uninterruptible power supply. You can modify thi...

  • Page 44

    Remote configuration the information in this section describes how to access the web/snmp configuration utility through a web browser. Note: make sure that an active 10/100base-t cable is connected to the network connector on the web/snmp card (the uplink ethernet connector on the web/snmp card). Fo...

  • Page 45

    7. Select date and time from the menu at the top of the page and enter the applicable date and time information in the specified format. 8. Select set values to save the date and time settings. The web/snmp card is now configured for operation on your network. See the online help for detailed inform...

  • Page 46

    34 ups 3000 lv and ups3000 hv: installation and maintenance guide.

  • Page 47: Chapter

    Chapter 5. Hardware maintenance information this chapter contains information about ibm customer replaceable units (crus) and field replaceable units (frus) for the uninterruptible power supply and instructions for replacement parts that are not installed during a typical installation. Replaceable u...

  • Page 48

    Storing the uninterruptible power supply and batteries if you store the uninterruptible power supply for a long period, recharge the battery every 6 months by connecting the uninterruptible power supply to a power outlet. The batteries charge to 90% capacity in approximately 3 hours. However, you sh...

  • Page 49

    6. Secure the electronics module to the uninterruptible power supply chassis with the screws that you removed in step 4 on page 36. 7. Replace the front bezel. 8. Reconnect any cables that you removed in step 1 on page 36. Replacing the battery module (for trained service technician only) caution: l...

  • Page 50

    3. Unscrew three nuts (one in the upper left corner and two on the bottom of the bracket) and set aside the battery retaining bracket. 4. Pull the battery out onto a flat, stable surface. For information about recycling the battery, see “battery return program” on page 65. 5. Slide the new battery m...

  • Page 51: Chapter

    Chapter 6. Troubleshooting this chapter provides basic troubleshooting information to help you resolve some common problems that might occur while you are using the uninterruptible power supply. Audible alarms and uninterruptible power supply conditions the uninterruptible power supply has an audibl...

  • Page 52

    Table 6. Troubleshooting guide (continued) alarm or condition possible cause action the uninterruptible power supply does not provide the expected backup time. The batteries need charging or service. Connect the uninterruptible power supply into a power outlet for 24 hours to charge the battery. If ...

  • Page 53

    Table 6. Troubleshooting guide (continued) alarm or condition possible cause action power requirements exceed uninterruptible power supply capacity (103 to 110% for 30 seconds) or the load is defective. Turn off and disconnect the uninterruptible power supply. Remove some of the connected devices fr...

  • Page 54

    42 ups 3000 lv and ups3000 hv: installation and maintenance guide.

  • Page 55: Appendix

    Appendix a. Getting help and technical assistance if you need help, service, or technical assistance or just want more information about ibm products, you will find a wide variety of sources available from ibm to assist you. This appendix contains information about where to go for additional informa...

  • Page 56

    Getting help and information from the world wide web on the world wide web, the ibm web site has up-to-date information about ibm systems, optional devices, services, and support. The address for ibm system x, xseries ® , and bladecenter ® information is http://www.Ibm.Com/eserver/xseries/. The addr...

  • Page 57: Appendix

    Appendix b. Ibm statement of limited warranty z125-4753-08 04/2004 part 1 - general terms part 1 - general terms this statement of limited warranty includes part 1 - general terms, part 2 - country-unique terms, and part 3 - warranty information. The terms of part 2 replace or modify those of part 1...

  • Page 58

    The warranty is voided by removal or alteration of identification labels on the machine or its parts. Ibm does not warrant uninterrupted or error-free operation of a machine. Any technical or other support provided for a machine under warranty, such as assistance with “how-to” questions and those re...

  • Page 59

    Your additional responsibilities before ibm or your reseller exchanges a machine or part, you agree to remove all features, parts, options, alterations, and attachments not under warranty service. You also agree to: 1. Ensure that the machine is free of any legal obligations or restrictions that pre...

  • Page 60

    Or damage to, data; 3) special, incidental, or indirect damages or for any economic consequential damages; or 4) lost profits, business revenue, goodwill or anticipated savings. Some states or jurisdictions do not allow the exclusion or limitation of incidental or consequential damages, so the above...

  • Page 61

    Colombia jurisdiction: the following is added after the first sentence: any litigation arising from this statement of limited warranty will be settled exclusively by the judges of the republic of colombia. Equador jurisdiction: the following is added after the first sentence: any litigation arising ...

  • Page 62

    Canada limitation of liability: the following replaces item 1 of this section: 1. Damages for bodily injury (including death) or physical harm to real property and tangible personal property caused by ibm’s negligence; and governing law: the following replaces “laws of the country in which you acqui...

  • Page 63

    Post of chairman shall be filled by the president of the siac. Other vacancies shall be filled by the respective nominating party. Proceedings shall continue from the stage they were at when the vacancy occurred. If one of the parties refuses or otherwise fails to appoint an arbitrator within 30 day...

  • Page 64

    Governing law: the following sentence is added to this section: any doubts concerning this statement of limited warranty will be initially resolved between us in good faith and in accordance with the principle of mutual trust. Malaysia limitation of liability: the word “special” in item 3 of the fif...

  • Page 65

    If one of the parties refuses or otherwise fails to appoint an arbitrator within 30 days of the date the other party appoints its, the first appointed arbitrator shall be the sole arbitrator, provided that the arbitrator was validly and properly appointed. All proceedings shall be conducted, includi...

  • Page 66

    The phrase “the laws of the country in which you acquired the machine” is replaced by: 1) “the laws of austria” in albania, armenia, azerbaijan, belarus, bosnia-herzegovina, bulgaria, croatia, georgia, hungary, kazakhstan, kyrgyzstan, fyr macedonia, moldova, poland, romania, russia, slovakia, sloven...

  • Page 67

    Madrid for spain; and 9) in the united kingdom, both of us agree to submit all disputes relating to this statement of limited warranty to the jurisdiction of the english courts. Arbitration: the following is added under this heading: in albania, armenia, azerbaijan, belarus, bosnia-herzegovina, bulg...

  • Page 68

    Limitation of liability: the following replaces the terms of this section in its entirety: except as otherwise provided by mandatory law: 1. Ibm’s liability for any damages and losses that may arise as a consequence of the fulfillment of its obligations under or in connection with this statement of ...

  • Page 69

    The provisions of this statement of limited warranty replace any applicable statutory warranties. What this warranty covers: the following replaces the first sentence of the first paragraph of this section: the warranty for an ibm machine covers the functionality of the machine for its normal use an...

  • Page 70

    The warranty for an ibm machine covers the functionality of the machine for its normal use and the machine’s conformity to its specifications. The following paragraphs are added to this section: the minimum warranty period for machines is twelve months. In case ibm or your reseller is unable to repa...

  • Page 71

    You, whether in contract or tort. A number of defaults which together result in, or contribute to, substantially the same loss or damage will be treated as one default occurring on the date of occurrence of the last such default. Circumstances may arise where, because of a default, you are entitled ...

  • Page 72

    This section sets out the extent of ibm’s liability and your sole remedy. 1. Ibm will accept unlimited liability for: a. Death or personal injury caused by the negligence of ibm; and b. Any breach of its obligations implied by section 12 of the sale of goods act 1979 or section 2 of the supply of go...

  • Page 73

    Types of warranty service if required, ibm provides repair or exchange service depending on the type of warranty service specified for your machine in the above table and as described below. Warranty service may be provided by your reseller if approved by ibm to perform warranty service. Scheduling ...

  • Page 74

    When a 5, 6 or 7 type of warranty service is listed, ibm will determine which type of warranty service is appropriate for the repair. * this type of service is called thinkpad easyserv or easyserv in some countries. The ibm machine warranty world wide web site at http://www.Ibm.Com/servers/ support/...

  • Page 75: Appendix

    Appendix c. Notices this information was developed for products and services offered in the u.S.A. Ibm may not offer the products, services, or features discussed in this document in other countries. Consult your local ibm representative for information on the products and services currently availab...

  • Page 76

    Microsoft, windows, and windows nt are trademarks of microsoft corporation in the united states, other countries, or both. Linux is a trademark of linus torvalds in the united states, other countries, or both. Red hat, the red hat “shadow man” logo, and all red hat-based trademarks and logos are tra...

  • Page 77

    Remarque : cette marque s’applique uniquement aux pays de l’union européenne et à la norvège. L’etiquette du système respecte la directive européenne 2002/96/ec en matière de déchets des equipements electriques et electroniques (deee), qui détermine les dispositions de retour et de recyclage applica...

  • Page 78

    For taiwan: please recycle batteries. Electronic emission notices federal communications commission (fcc) statement note: this equipment has been tested and found to comply with the limits for a class a digital device, pursuant to part 15 of the fcc rules. These limits are designed to provide reason...

  • Page 79

    European union emc directive conformance statement this product is in conformity with the protection requirements of eu council directive 89/336/eec on the approximation of the laws of the member states relating to electromagnetic compatibility. Ibm cannot accept responsibility for any failure to sa...

  • Page 80

    68 ups 3000 lv and ups3000 hv: installation and maintenance guide.

  • Page 81: Index

    Index a alarm reset button 18 attention notices 4 audible alarm, silencing 39 b battery care 35 storing 36 battery mode 19 battery module, replacing (trained service technician only) 37 battery return program 65 battery service led 17 battery, connecting internal 10 buttons alarm reset 18 off 17 on ...

  • Page 82

    On button 17 online documentation 1 operating modes battery 19 bypass 19 configuration 20 normal 19 standby 19 p power-on led 17 product recycling and disposal 64 r rack installation 5 rear view controls and power 18 recycling battery 65 recycling products 64 remote emergency power-off connecting a ...

  • Page 84

    Part number: 40k9691 printed in usa (1p) p/n: 40k9691.