ICP C9MPT050F12C1 Technical Support Manual - page 11
11
440 04 2023 02
Specifications are subject to change without notice
Circulation Air Blower Data - *9MPV075
Cooling CFM Adjustment
Heating Rise Adjustment
DIP Switch
5 & 6
High Cool @
0.50 in wc
Low Cool
(80% of High
Cool)
** Adjust
Jumper
Setting
DIP Switch
3 & 4
High Heat
Rise Change
@ 0.20 in wc
Low Heat
Rise Change
at Resultant
Static
00
1342
1074
+
00
--4
--4
*00
1210
968
*NOM
*00
0
0
00
1053
842
--
00
5
4
01
1135
908
+
01
1
1
01
1020
816
NOM
01
6
5
01
872
698
--
01
12
10
10
965
772
+
10
--1
--1
10
840
672
NOM
10
3
3
10
680
544
--
10
9
8
11
708
566
+
11
--6
--6
11
590
472
NOM
11
--2
--3
11
488
390
--
11
3
2
Airflow performance includes 1” washable filter media.
*Factory Setting
**Adjust Jumper Setting (+, NOM, --) is applied to both Cooling and Heating
Note 1: HP Mode Jumper provides a 10% reduction in airflow when in Comfort position and a call for low or high cooling is
present with the ”O” line off. This feature is to provide lower airflow for running in HP Heating Mode if desirable.
Note 2: DEHUM mode (24VAC on DEHUM terminal) provides a 20% airflow reduction during cooling calls.
Note 3: Low Heat ESP is a result of High Heat ESP (-- is decrease in rise).
Note 4: High and low heat rise values are approximate air temperature change from return air temperature when at factory
default settings.
Table 2
Continuous Fan @
0.10 in wc ESP
DIP Switch 1 & 2
Airflow (CFM)
*00
612
01
1096
10
1403
11
1403
* Factory Setting
Table 3
SW2 DIP Assignments
DIP Switch
Blower Parameter
1 & 2
Cont Fan Adj
3 & 4
Heat Speed Adj
5 & 6
Cool Speed Adj
7 & 8
Cool On/Off Delay
Table 4
Cooling Delay Options (SW2 -- 7, 8)
ON DELAY
OFF DELAY
DIP SW2 -- 7/8
Timed ON (sec)
Airflow during on
delay
Timer OFF (sec)
Airflow during off
delay
*00
5
OFF
90
100%
01
5
OFF
0
OFF
10
30
50%
30
100%
11
30
50%
180
50%
Airflow % is of High Cool airflow demand determined from SW2--5/6 Table 1
Airflow resumes to 100% after on delay time is completed
Airflow stops (or switches to continuous fan speed) after off delay time is completed
* Factory Setting
MAX CFM’s for Factory Washable Filters
Dimensions
Airflow (CFM)
14” x 25”
1400
16” x 25”
1600
20” x 25”
2000
24” x 25”
2500
MAX CFM based on 600 FPM
Note 1: Disposable filters are typically rated at 300 FPM. These filters only allow half the airflow when compared to 600 FPM
filters. (example, 20 x 25 @ 600 FPM = 2000CFM, @ 300 FPM = 1000 CFM)