Intermatic IG1201EH Installation Instructions

Summary of IG1201EH

  • Page 1

    Caution: turn off power to the electric service or panel and to equipment to be protected before installing any surge protection device. All wiring should be done by a qualified electrician and comply with the national electric code and local electric codes. Installation 1. Test and verify system vo...

  • Page 2

    Wiring configurations note: all ‘eh’ units must be installed downstream from breaker or fuse of 400 amps or less capacity. A 30-amp breaker is recommended as a convenient connection point when installing on a breaker panel. 120 volt single phase transformer secondary model ig1201eh use 30 amp breake...

  • Page 3

    120/240 volt three phase delta high leg delta l1 g n load center black/negro noir white/blanco blanc green/verde vert red/rojo rouge l2 black/negro noir l3 use 30 amp breakers (optional) model ig2403deh transformer secondary 277/480 volt three phase wye l1 g n load center black/negro noir white/blan...

  • Page 4

    Ten year limited product warranty for intermatic ® hardwired surge protection devices (1) what is covered by this limited warranty repair or replacement of product intermatic incorporated ("intermatic") warrants to the original purchaser only, intermatic models ig250la, ig251, ig1201lh, ig2401lh, ig...