Jackson Systems WZ1 Installation And Operation Manual - page 5
5
If there is only one WZ-1 installed, it is not necessary to program the address as the thermostat and damper
control module default address is Zone 01.
PROGRAM ENABLE
After selecting the Zone number for the thermostat, the same address must be programmed into the damper control
module. Remove the cover on the module and apply 24 Volts power. Press the
button. The
module will accept a new address for thirty seconds. The LED on the module will alternately blink red and green while it is
waiting for a new address. When the module accepts the address, the LED will begin to flash green confirming
communications with the thermostat.
10
Programming the Module
The multi-colored LED indicator normally flashes green when no calls are active. The LED is continuously
yellow during cooling calls and red during heating calls.
9
Cooling Setpoint Limit
Press the
key to select
and press the
or
key to
set the minimum allowable cooling setpoint.
NEXT
Option 09
Up
Down
The minimum cooling setpoint range is 55 to 80F.
Option
CANCEL
NEXT
ENTER
Set To
G Y W R C
1 2 3 4 5 6 7
GREEN
LED
LED
24 VAC
PROGRAM
ENABLE
BUTTON
FLASHING LED
While the module LED is alternately blinking red and green, press and hold
the
key for seven second until the zone number is displayed. Press
until
and the zone number are displayed. Send the
zone address to the damper control module by pressing the
key.
When the module LED begins to flash green, communications with the
thermostat has be enabled.
ENTER
NEXT
Option 03 (Pr)
ENTER
Option
Zone
CANCEL
NEXT
ENTER
Cool
ON WHEN DAMPER
IS POWERED OPEN
ACTUATOR
PO / SC