Installation & Operation Manual
2. For the VS-FHP2.0, slide dip switches 1 and 2
down to the OFF position. See Figure 10.
3. Select the desired address(es) for the VS-FHP2.0
pump by setting dip switches 3 and/or 4, as shown in
Section 3.3, VS FloPro Pump Dip Switch Settings.
4. Connect the other end of the cable to an RS-485
connector on the AquaLink
®
RS (or multiplexer
interface board), matching wire colors with
connector positions as follows: 1-red, 2-black,
3-yellow, and 4-green. See Figure 10 and read
Section 3.3.
5. Restore power to the VS-FHP2.0 pump and verify
the operation of the controller.
6. Refer to the appropriate manual for set up and
operation of the pump: AquaLink RS Owner’s
Manual, 6593, AquaLink PDA Owner’s Manual,
H0572300, or AquaLink Z4 Owner’s Manual,
H0386600.
Variable-Speed
Pump
4 3 2 1
RED
BLACK
YELLOW
GREEN
RS485 Cable
BLACK YELLOW
RED
GREEN
Connect to
AquaLink RS
RS-485 Connector
(or Multiplexer
Interface Board)
S1
S2
RESET
SERVICE
TIME OUT
FIL
TER PUM
P
AUX
1
AUX
2
AUX
3
AUX
4
AUX
5
AUX
6
AUX
7
RS6 & RS8 ONLY
RS8 ONLY
HEATER
SOLAR
POOL MODE
SPA MODE
SPA DRAIN
SPA FILL
AUTO
6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1
4 3 2 1 4 3 2 1
AquaLink RS RS-485 Connectors
4-Position
DIP Switch
Figure 10. Wiring AquaLink RS Controller or
AquaLink PdA to VS-FHP2.0
Remove to
access
DIP switch
Figure 11. dIP Switch access cover on VS-FHP1.0
Motor
3.3 VS FloPro Pump dip Switch Settings
As shown in Figures 7, 9, 10 and 11, the 4- or 5-position
dip switch is located at the rear of the VS FloPro pump.
This dip switch serves two (2) functions: it selects the
pump address, and it determines what type of controller
will be used with the pump.
Table 4.
VS-FHP1.0 dip Switch Settings
Switch
1
Switch
2
Switch
5
Controller
ON
ON
ON
Factory Default
OFF
OFF
ON
AquaLink RS, AquaLink
PDA, or AquaLink Z4
ON
ON
ON
Variable Speed
Controller
Switch
3
Switch
4
Pump Address
OFF
OFF
PUMP 1 (Factory Default)
ON
OFF
PUMP 2
OFF
ON
PUMP 3
ON
ON
PUMP 4
Table 5.
VS-FHP2.0 dip Switch Settings
Switch
1
Switch
2
Controller
OFF
OFF
Factory Default
OFF
OFF
AquaLink RS, AquaLink PDA, or
AquaLink Z4
ON
ON
Variable Speed
Controller
Switch
3
Switch
4
Pump Address
OFF
OFF
PUMP 1 (Factory Default)
ON
OFF
PUMP 2
OFF
ON
PUMP 3
ON
ON
PUMP 4