Janus 120V 1000VA User Manual

Summary of 120V 1000VA

  • Page 1

    □ tower and rack-mount convertible ups user’s manual 750/1000/1500/2200/3000 1 table of contents 1 introduction ------------------------------------------------------------------------------------2 2 important safety instruction -------------------------------------------------3 2.1 an important not...

  • Page 2

    2 1 introduction the ups featured with tower/rack convertible design, single avr boost and single buck, pure sine wave output, user’s friendly lcd display, built-in customer option slot, hot swappable battery, and usb/rs232 communication interface, provides a flexible from factor for most of busines...

  • Page 3

    4 14. It should be recharged every 2-3 months if unused. If this is not done, then the warranty will be null and void. When installed and being used, the batteries will be automatically recharged and kept in top condition. 15. This ups supports electronic equipment in offices, telecommunications, pr...

  • Page 4

    6 3.3 unpacking 1. Take the ups out of the pe foam. 2. Remove the packing materials. 3. Standard package includes: a. User's manual b. 1pc x ac input power cord ( not available for hard wiring connection models) c. (1pc for 750/1k/1.5kva, 2pcs for 2.2k/3kva)x iec output cables ( for the ups with iec...

  • Page 5

    8 3.6 tower setup stand alone unit 9 3.7 rack-mount setup step1 step2.

  • Page 6

    10 step3 step4 step5 11 3.8 ups front panel.

  • Page 7

    12 3.9 lcd display panel 1. Utility led 2. Fault led 3. On switch 4. Off switch 5. Battery replacement 6. Battery backup led 7. Battery low 8. Bypass 9. Utility low, ups boost 10. Utility high, ups buck 11. Ups output indicator 12. Polarity error or ground fault 13. Overload 14. Load/battery level (...

  • Page 8

    14 2200va 120v(1920va/1920w for ul) item description 1 data line connectors 2 voltage configuration switch 3 usb port 4 rs232 (db-9) port 5-1 15a output circuit breaker for 6-1 5-2 20a output circuit breaker for 6-2 6-1 nema 5-15r output receptacles 6-2 nema 5-20r output receptacles 7 cooling vents ...

  • Page 9

    16 750/ 1000/ 1500va 230v item description 1 data line connectors 2 voltage configuration switch 3 usb port 4 rs232 (db-9) port 6 iec-320-c13 output receptacles 7 cooling fan 8 7a input circuit breaker (750 model only) 8a input circuit breaker (1000 model only) 10a input circuit breaker (1500 model ...

  • Page 10

    18 4 installation 4.1 connect utility and load first, connect the ups with utility, then plug the loads into the outlets on the rear of the ups. To use the ups as a master “on/off” switch, make sure that all of the loads are switched “on”. These ups outlets provide battery backup and surge protectio...

  • Page 11

    20 4.4 repo switch the ups is equipped with an emergency power off (epo) switch. The user must supply a means of interfacing with the epo circuit to allow disconnecting the ups input feeder breaker to interrupt all sources of power to the ups and connected equipment to comply with national and local...

  • Page 12

    22 5.4 auto-restart if the input power cord is connected to the wall receptacle properly and utility is back to normal, the ups will automatically restart to provide energy to the output after battery cut. 5.5 alarm silence 1. The alarm might be turned off by pressing the “on” switch for approximate...

  • Page 13

    24 6.2 how to replace battery step 1 step 2 25 step 3 step 4 1000/ 1500va.

  • Page 14

    26 2200/ 3000va 6.3 recycling the used battery contact your local recycling or hazardous waste center for information on proper disposal of the used battery. 27 7 communication 7.1 db-9 connector the ups has a db-9 (9 pin female) connector on the rear to allow ups status communications with a comput...

  • Page 15

    28 8 optional communication cards 8.1 dce (dry contact) card 8.1.1 the pin assignments of 10-pin terminal : 1 Æ n/a 2 Æ utility abnormal 3 Æ utility normal 4 Æ avr on 5 Æ battery low 6 Æ n/a 7 Æ n/a 8 Æ common 9 Æ shutdown ups positive(+ ) signal 10 Æ shutdown ups negative( - ) signal 8.1.2 the shut...

  • Page 16

    30 9 specifications 9.1 120v model number 1000va 1500va 2200va 3000va power rating, va/w 1000va/900w 1500va/1350w 1920va/1920w 3000va/2700w dimensions, w x d x h, in (mm) unit 440x405x88 440x405x88 440x650x88 440x650x88 shipping 560x526x228 560x526x228 560x833x228 560x833x228 weight, lbs (kg) unit 1...

  • Page 17

    32 9.2 230v model number 750va 1000va 1500va 2200va 3000va power rating, va/w 750va/675w 1000va/900w 1500va/1350w 2200va/1980w 3000va/2700w dimensions, w x d x h, in (mm) unit 440x405x88 440x405x88 440x650x88 440x650x88 shipping 560x526x228 560x526x228 560x770x228 560x770x228 weight, lbs (kg) unit 1...

  • Page 18

    34 35 192321372001003.