Jaspi YPV 40 Installation And Operation Manual

Summary of YPV 40

  • Page 1

    Installation and operation manual jaspi knows heating ypv 40 solid fuel boiler.

  • Page 2

    The warranty is two years for the boiler and one year for the components. Warranty the warranty is only valid if the boiler has been installed by an authorized representative/dealer or with consent of the latter and in accordance with this manual. Uk technical helpline 01392 247 340 contents everyda...

  • Page 3

    Dimensions and technical details water capacity 80 litres power 20-40kw tested pressure 4.0bar operating pressure 1.5bar recommended flue ø180mm max. Operating temp. 110°c min. Operating temp. 0°c weight (empty) 270kg description 1. Outer sheating 2. Insulation 3. Pressure / temp. Gauge 4. Thermosta...

  • Page 4

    • the boiler must be kept upright during the transportation, installation and use. • it must be installed on a solid, non-combustible floor out of rain or other water spray • reserve installation and operating space around the boiler • all the pipe connections and couplings must be copper, brass or ...

  • Page 5

    Y p v 4 0 b o ile r + t h e rm o s to re c o u p lin g u s in g a c g l o a d in g u n it d r a w n v e r s io n d a t e d r a w in g r e f . S s 0 3 .1 1 .2 0 1 1 g e n e r ic m a n u a l b a la n c in g va lv e ( r e c o m m e n d e d ) v e xv e a c g l o a d in g u n it w it h p u m p , th e rm o...

  • Page 6: Automix Termovar

    Automix termovar for solid fuel boiler pump control function loading unit or transfer pump between the thermal store and the boiler. From the boiler to the thermal store, heat exchanger or a radiator system. When the boiler cools down, the thermostat will cut the power to the pump and the heat trans...

  • Page 7

    The burning grate adjuster plates (18) are used to increase or degrease the active burning area. They are fitted into 45° angle against the burning chamber walls. Reducing the burning area will reduce the power output of the boiler and the consumption of logs. With these plates the boiler output can...

  • Page 8

    Ypv40 is a traditional upright burning solid fuel boiler. This means that the fire burns vertically from bottom up. The burning gases rise towards the top of the boiler and exit from the rear of the boiler. Therefore the water on the top of the boiler is always hotter than at the bottom. The high ef...