KeepRite C4A3 Installation Instructions Manual - Caution

Manual is about: R-410A Split System Air Conditioner

Summary of C4A3

  • Page 1

    421 01 5100 01 october 2006 installation instructions r−410a split system air conditioner model series: n4a3, h4a3, c4a3, t4a3 n4a4, h4a4, c4a4, t4a4 these instructions must be read and understood completely before attempting installation. Danger, warning, caution, and note the signal words danger, ...

  • Page 2: Caution

    Installation instructions r−410a split system air conditioner 2 421 01 5100 01 inspect new unit after uncrating unit, inspect thoroughly for hidden dam- age. If damage is found, notify the transportation compa- ny immediately and file a concealed damage claim. Safety considerations consult a qualifi...

  • Page 3

    Installation instructions r−410a split system air conditioner 421 01 5100 01 3 figure 1 clearances (various examples) wall 6” 24” service wall wall wall 6” 6” post wall w all 18” 18” 18” 18” 6” 6” 6” 18” 18” 18” 18” 24” service 24” service 24” service 24” service 24” service 24” service 4” 4” wide f...

  • Page 4: Caution

    Installation instructions r−410a split system air conditioner 4 421 01 5100 01 unit support note: unit must be level 2 degrees ( inch rise or fall per foot of run) or compressor may not function properly. A. Ground level installation the unit must be level and supported above grade by beams, platfor...

  • Page 5: Caution

    Installation instructions r−410a split system air conditioner 421 01 5100 01 5 when installing a hard shut−off txv on an indoor coil, fol- low the instructions provided with the new txv. A typical hard shut−off txv installation is shown in figure 3. Figure 3 typical txv installation hard shut−off tx...

  • Page 6: Caution

    Installation instructions r−410a split system air conditioner 6 421 01 5100 01 c. Routing and suspending refrigerant lines run refrigerant lines as straight and direct as possible, avoiding unnecessary bends and turns. Always insulate the entire suction line. Both lines should be insulated when rout...

  • Page 7: Caution

    Installation instructions r−410a split system air conditioner 421 01 5100 01 7 e. Liquid line filter−drier outdoor units are shipped with an appropriate filter−drier for installation in the liquid line. Leave the plugs in the tube ends until the filter−drier is installed. The optimal location for th...

  • Page 8

    Installation instructions r−410a split system air conditioner 8 421 01 5100 01 deep vacuum method the deep vacuum method requires a vacuum pump ca- pable of pulling a vacuum to 500 microns and a vacuum gauge capable of accurately measuring this vacuum lev- el. The deep vacuum method is the most posi...

  • Page 9

    Installation instructions r−410a split system air conditioner 421 01 5100 01 9 electrical wiring ! Warning electrical shock hazard failure to turn off the main (remote) electrical dis- connect device could result in personal injury or death. Before installing, modifying or servicing system, turn off...

  • Page 10

    Installation instructions r−410a split system air conditioner 10 421 01 5100 01 refrigerant charge outdoor units are shipped with a refrigerant charge to match a specific indoor coil and 15 feet of refrigerant line. If shorter or longer refrigerant lines or a different indoor coil are used, the char...

  • Page 11

    Installation instructions r−410a split system air conditioner 421 01 5100 01 11 troubleshooting some models are factory equipped with the comfort alertt diagnostics device in the control box (refer to fig- ure 13). Comfort alert provides around−the−clock moni- toring for common electrical problems, ...

  • Page 12

    Installation instructions r−410a split system air conditioner 12 421 01 5100 01 figure 14 comfort alertt diagnostics (some models) status led status led description status led troubleshooting information green “power” module has power supply voltage is present at module terminals red “trip” thermost...

  • Page 13

    Installation instructions r−410a split system air conditioner 421 01 5100 01 13 r−410a quick reference guide • r−410a refrigerant operates at 50% − 70% higher pressures than r−22. Be sure that servicing equipment and replacement components are designed to operate with r−410a. • r−410a refrigerant cy...