KeepRite C4A6 Installation Instructions Manual

Manual is about: Two?Stage Split System Air Conditioner

Summary of C4A6

  • Page 1

    421 01 6002 01 oct 2009 installation instructions r−410a two−stage split system air conditioner product family: h4a6, c4a6, t4a6 h4a8, c4a8, t4a8 these instructions must be read and understood completely before attempting installation. Danger, warning, caution, and note the signal words danger, warn...

  • Page 2: Caution

    Installation instructions r−410a, two−stage split system air conditioner 2 421 01 6002 01 inspect new unit after uncrating unit, inspect thoroughly for hidden damage. If damage is found, notify the transportation company immediately and file a concealed damage claim. Safety considerations consult a ...

  • Page 3

    Installation instructions r−410a, two−stage split system air conditioner 421 01 6002 01 3 figure 1 clearances (various examples) wall 6” (152mm) 24” (610mm) service wall wall wall 6” (152mm) 6” (152mm) post wall w all 18” (457mm) 18” (457mm) 18” (457mm) 18” (152mm) 6” (152mm) 6” (152mm) 6” (152mm) 1...

  • Page 4: Caution

    Installation instructions r−410a, two−stage split system air conditioner 4 421 01 6002 01 unit support note: unit must be level 2 degrees { inch rise or fall per foot of run (10mm rise or fall per 305mm of run) } or compressor may not function properly. A. Ground level installation the unit must be ...

  • Page 5: Caution

    Installation instructions r−410a, two−stage split system air conditioner 421 01 6002 01 5 figure 3 typical txv installation txv sensing bulb equalizer tube ÉÉ ÉÉ ÉÉ ÉÉ 8 o’clock 4 o’clock strap sensing bulb (either side) suction tube indoor coil suction tube liquid tube b. Refrigerant line sets the ...

  • Page 6: Caution

    Installation instructions r−410a, two−stage split system air conditioner 6 421 01 6002 01 ! Caution unit operation hazard failure to follow this caution may result in improp- er product operation. Do not bury more than 36” (1m) of line set under- ground. Refrigerant may migrate to cooler buried sect...

  • Page 7: Caution

    Installation instructions r−410a, two−stage split system air conditioner 421 01 6002 01 7 h. Evacuating line set and indoor coil the unit is shipped with a factory refrigerant charge. The liquid line and suction line service valves have been closed after final testing at the factory. Do not disturb ...

  • Page 8

    Installation instructions r−410a, two−stage split system air conditioner 8 421 01 6002 01 i. Opening service valves outdoor units are shipped with a refrigerant charge sealed in the unit. Opening the service valves releases this charge into the system. Note: open the suction service valve first. If ...

  • Page 9

    Installation instructions r−410a, two−stage split system air conditioner 421 01 6002 01 9 airflow selection two−stage compressor operation requires two different indoor airflow settings for proper operation. This outdoor unit is designed for use only with an indoor blower that can be configured for ...

  • Page 10

    Installation instructions r−410a, two−stage split system air conditioner 10 421 01 6002 01 figure 11 rating plate (required) subcooling temperature ° f ( ° c) measured liquid pressure (psig) ° f ( ° c) ° f ( ° c) ° f ( ° c) ° f (° c) f (° c) f ( ° c) 6 3 8 4 10 6 12 7 14 8 16 9 r−410a required liqui...

  • Page 11

    Installation instructions r−410a, two−stage split system air conditioner 421 01 6002 01 11 compressor operation the basic scroll design has been modified with the addition of an internal unloading mechanism that opens a by−pass port in the first compression pocket, effectively reducing the displacem...

  • Page 12

    Installation instructions r−410a, two−stage split system air conditioner 12 421 01 6002 01 two−stage compressor resistance (winding resistance) at 70 ° f +/− 20 ° f (21 °c +/− 11 ° c) winding *4a624 *4a836 *4a648 *4a660 start (s−c) 1.40 1.29 1.52 0.60 run (r−c) 1.32 0.89 0.64 0.49 note: the rectifie...

  • Page 13

    Installation instructions r−410a, two−stage split system air conditioner 421 01 6002 01 13 figure 13 comfort alert t ultratech t diagnostics status led status led description status led troubleshooting information green “power” module has power supply voltage is present at module terminals red “trip...

  • Page 14

    Installation instructions r−410a, two−stage split system air conditioner 14 421 01 6002 01 status led status led description status led troubleshooting information yellow “alert” flash code 5 open high voltage circuit 1. Outdoor unit power disconnect is open 2. Compressor circuit breaker or fuse(s) ...

  • Page 15

    Installation instructions r−410a, two−stage split system air conditioner 421 01 6002 01 15 r−410a quick reference guide • r−410a refrigerant operates at 50% − 70% higher pressures than r−22. Be sure that servicing equipment and replacement components are designed to operate with r−410a. • r−410a ref...