Kemlan Power Flue Horizon Gas Fireplaces Installation Instructions Manual

Summary of Power Flue Horizon Gas Fireplaces

  • Page 1

    ---- fireplaces ---- installation instructions power flue horizon gas fireplaces.

  • Page 2: Following Models:

    Single sided models suitable gas burner option cantilever 700 cantilever 700 mk2 pebble 700 mk2 coal 700 ironbark log mk4 1100 cantilever 1000 mk2 pebble 1000 mk2 coal 850 ironbark log mk4 1500 low line 1400 mk2 pebble 1400 mk2 coal double sided models 2 power flue approved for the following models:...

  • Page 3

    3 installation instructions kemlan power flue horizon gas fireplaces t = flue termin al i = m echanical air in le t m = gas meter p = e le ctricity meter or fuse box shading in d icates prohibit e d areas for flue term i nals a below eaves, b alconie s or other pro j ections: appli a nces u p t o 50...

  • Page 4

    4 before installation the natural draft electronic ignition (n.D.E.I.) flue system shall be installed by authorized personnel in accordance with the manufacturer’s installation instructions, local gas fitting regulations, municipal building codes, electrical wiring regulations, and any other statuto...

  • Page 5

    E c b* d c *opening dimensions on/off switch to burner *opening dimensions internal fan cantilever – rear exit g f c a b b1 a1 measurement and specifications of fan power flue external fan casing 3 pin plug 240 volt 10 amp isolating switch 3 pin plug 240 volt 10 amp isolating switch 3 pin plug 240 v...

  • Page 6

    Power flue with internal fan heat transfer box silencer 8 ” x 900 reducer 7” – 6” 8” – 6” 9” – 6” 10” – 6” 12” – 6” 14”-- 6” gas cowl cooling rotor inbuilt thermal overload cooling impeller 6 ” x 900 12” x 900 installation instructions kemlan power flue horizon gas fireplaces 12” x 200 vented flue.

  • Page 7

    Power flue with external fan silencer 8 ” x 900 reducer 7” – 6” 8” – 6” 9” – 6” 10” – 6” 12” – 6” 14 ”-- 6” wall mounted fan 2x 8” 45 deg 12” – 8” reducing cap 6 ” x 900 12” x 900 installation instructions kemlan power flue horizon gas fireplaces 2x 6” 45 deg 12” x 200 vented flue 10mm gap between e...

  • Page 8: Framing Dimensions

    Framing dimensions single sided double sided c b b c 8 a a double sided a b b* c c* 700 low line 1056 480 500 750 1050 850 low line 1145 480 500 845 1145 1100 low line 1408 480 500 845 1145 1500 low line 1796 490 510 980 1280 2000 low line 2293 490 510 980 1280 * including 10mm plasterboard c* - int...

  • Page 9

    9 sections 25mm min. Flue clearance to timber 80mm horizon gas fireplace 10mm compressed fibre cement sheet 25mm min. Flue clearance to timber cantilever horizon fireplace 80mm 150mm min . Gas burner framework and 10mm wall lining by installer selected facing by installer elevation of fan power flue...

  • Page 10

    10 gas installation 1 check unit is suitable for intended gas supply. 2 note position on gas appliance on drawing specification on right hand side of appliance. 3 a gas cock has to be fitted prior to gas burner to allow unit to be removed for servicing. 4 if material has been installed around firebo...

  • Page 11: Laying The Fire

    11 laying the fire – coal & pebble mark 2 coals 700/800 – 600 x 155 mark 2 pebbles 1000 – 992 x 135 mark 2 coals 1400 – 1400 x 64 mark 2 pebbles 1400 – 1400 x 64 mark 2 coals 1800 – 1800 x 64 mark 2 pebbles 1800 – 1800 x 64 mark 2 coals 1000 – 992 x 135 mark 2 pebbles 700/800 – 600 x 155 installatio...

  • Page 12

    12 laying the fire - 850 ceramic log p o s i t i o n i n g o f a l l l o g s • it is important to follow the log recommended positioning. • log no. 6, 10, 9 and 4 must be pinned to rear log with pins provided. • not doing so can adversely effect the operation of the appliance. • this diagram shows t...

  • Page 13

    13 laying the fire - 850 ceramic log 4 . Locate log no. 4. Place it on the left side of the rear log. Charred end facing inwards. Locate log no. 5 . This log is placed with the thinner edge on the smaller coal. The charred effect is facing towards the front of the burner. The whole log is positioned...

  • Page 14: Laying The Fire

    14 laying the fire – 700 ceramic log 2. Locate l o g n o. 1 : this is the largest log that is positioned at the rear of the grate.Two locating pins are positioned at the rear of the burner. The large log has two holes on the underside to position in place 1 . L o c at e 4 c e r a m i c coals: four c...

  • Page 15

    15 laying the fire - 700 ceramic log 6 . L o c at e l o g n o. 7 : the charred effect of the log is positioned on the smaller coal in the centre of the burner on the right hand side. The right hand side of the log is positioned between the front metal upright on the side . 5 . L o c at e l o g n o ’...

  • Page 16

    16 commissioning procedure installed correctly the burner should not emit any fumes into the room. The following procedure should be undertaken to test that the unit is operating correctly. 1 after unit has been operating for a short period a smoke match, smoke tube, carbon dioxide analyser or simil...

  • Page 17

    17 wiring diagram for further service information contact kemlan australia installation instructions kemlan power flue horizon gas fireplaces head office –13 french avenue, brendale, queensland 4500 telephone –ph: (07) 3490 5500

  • Page 18

    18 service instructions for direct ignition and power flue horizon fireplaces. Power flue service instructions problem possible cause corrective action pilot will not light with fan 1) no gas - check for gas supply and turn on working all connections - check gas pressure - check pilot and clean inje...

  • Page 19: Direct Ignition

    19 problem possible cause corrective action pilot will not light 1) no gas - check for gas supply and turn on all connections - check gas pressure - check pilot and clean injector 2) no spark at pilot - check electric supply and turn on all switches - check all connections - check spark electrode co...

  • Page 20

    20 1 2 pressure switch off pressure switch contacts. Have not closed. Check if fan starts. If fan starts ok, check pressure switch. 1 3 pressure switch on pressure switch contacts pressure switch is faulty and is stuck on, or fan has have not opened after not turned off. Last heat cycle. Trouble sho...

  • Page 21

    21 3 1 pressure switch fail check combustion fan. Check unit has started and during heat cycle the pressure switch has opened pressure switch and connections. Check flue for obstructions notes: the ignition unit is polarity sensitive. If the active and neutral cables are not wired correctly, the uni...

  • Page 22

    22 flash code (long flashes – short flashes) description 0-2 normal start up operation 1-0 normal running state 1-1 flame failure 1-2 waiting for pressure switch on 1-3 waiting for pressure switch to go off 1-4 waiting for flame sense to go off 1-5 post purge in progress 2-1 maximum retries exceeded...