KUSSMAUL AUTO-TROL 091-36 Instruction Manual - page 3
Manual is about: A CONTROL TO PROTECT ALTERNATING CURRENT LOADS FROM LOW FREQUENCY POWER INPUT
of
5
TEST:
1.0 Start the engine and operate the generator at it normal speed and frequency (60 Hz). The Green
LED indicator on the side of the AUTO-TROL should be lit. The relay is closed and the load
energized.
2.0 Set the engine to low idle to produce a generato frequency less than 50 Hz. The Green LED
indicator will be “off” and the load disconnected.
SPECIFICATIONS:
Relay energize frequency: 58 +/-2 Hz
Relay deenergize frequency: 55 +/-2 Hz
Relay Current Rating: 75 Amp. resistive 60 Amp. inductive 250 Amp. (1 sec.)
Wire Size: #6 AWG