A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING
Page 7 of 21
5.3
STATUS/ALARM INDICATORS
A green pilot light indicator illuminates to indicate a.c. voltage is present to the rectifier.
A red a.c. power failure light with Form “C” contacts for customer connections.
§ Float Indicator
A green LED illuminates to indicate that the rectifier is in the float mode of operation.
§ Equalize Indicator
A yellow LED illuminates to indicate that the rectifier is in the equalize mode of operation.
5.4
PARALLELING
This rectifier will parallel with any other La Marche Model A36F-3 PHASE Charger.
5.5
LOAD SHARING
A load sharing circuit is provided on the terminal board. When connected, two (2) or more La Marche
A36F-3 PHASE units are forced to share the load equally within +/- 5%. Individual unit d.c. amp output
must be greater than 10% of nameplate rated output.
5.6
CURRENT WALK IN
Output current will gradually increase after the rectifier is initially turned on reducing current surges.
5.7
EMERGENCY RESTORATION
This rectifier may be connected to a battery, which is heavily discharged and recharge it without clearing
any protective devices while powering d.c. loads.
5.8
METERS
Digital meter is standard with “INFORMER” option.
5.9
MOUNTING
These cases are designed for floor mounting. See cabinet dimensions sheet (included in manual) for
more information.
6.0 ENVIRONMENTAL RATINGS
6.1
OPERATING AMBIENT TEMPERATURE
0-50 degrees C (32-122 degrees F)
6.2
STORAGE TEMPERATURE
-40 to +85 degrees C (-40 to +185 degrees F)
6.3
HUMIDITY
This rectifier is capable of operating in an ambient relative humidity range of 0-95% (non-condensing).