Lamborghini Caloreclima Taura 24 MCS W TOP Instructions For Use, Installation And Maintenance

Manual is about: Wall-Mounting Gas Boiler

Summary of Taura 24 MCS W TOP

  • Page 1

    Taura 24 mcs w top caldaia murale a gas camera stagna, per sanitario e riscaldamento wall-mounting gas boiler airtight chamber, for hot water and heating chaudiÈre murale À gaz chambre de combustion Étanche, pour la production d’eau chaude sanitaire et le chauffage caldera mural de gas con cÁmara es...

  • Page 2

    Taura 24 mcs w top 20 1. Operating instructions ..........................................................................21 2. Installation ............................................................................................22 3. Service and maintenance ........................................

  • Page 3

    Boiler off boiler on stand-by heating operation (burner on) operation in hot water mode (burner on) test mode operation green yellow red on off blinking (fast for trouble) led key fig. 1 for other combinations, see chap. 3.4. Taura 24 mcs w top 21 1. Operating instructions 1.1 introduction dear cust...

  • Page 4

    Taura 24 mcs w top 22 1.3 turning on and off ignition • open the gas valve ahead of the boiler. • supply the unit with electricity. Turn the selector 3 onto (winter) or onto (summer) • turn the heating and hot water knob onto the required temperatures. • the boiler is ready to function automatically...

  • Page 5

    Taura 24 mcs w top 23 if the unit is enclosed in furniture or mounted alongside, there must be space for removing the casing and for normal maintenance work. 2.3 plumbing connections the heating capacity of the unit should be previously established by calculating the building’s heat requirement ac- ...

  • Page 6

    2.6 fume ducts the unit is “type c” with an airtight chamber and forced draught, the air inlet and fume outlet must be connected to one of the following extraction/suction systems. Before commencing installation, it is first necessary to check that the fume ducts do not exceed the maximum permissibl...

  • Page 7

    Diaphragms boiler operation requires fitting the diaphragms supplied with the unit as instructed in the following tables and drawings. Choosing the diaphragm using coaxial pipes choosing the diaphragm using separate pipes type length up to: diaphragm to use coaxial 60/100 1 bend + 1 metre Ø84 extern...

  • Page 8

    Connection with separate pipes remove the air inlet closing cap. Fit the two flanged sections Ø80, with their seals. If necessary, install the diaphragm under the air inlet section losses eq m component drawing suction outlet vertical outlet horizontal accessories Ø 80 pipe Ø 80 male-female 1 1 2 be...

  • Page 9

    Taura 24 mcs w top 27 3. Service and maintenance all adjustment, conversion, system start-up and maintenance operations described hereunder must be carried out solely by qualified personnel such as the personnel of the local after-sales technical service. Lamborghini declines any responsibility for ...

  • Page 10

    Taura 24 mcs w top 28 • check that the maximum pressure has not changed. • reconnect the pressure compensation tube “h”. • put the protective cap “d” back on. • to end test mode, select another mode. Key b pressure point c modureg cable d protective cap e minimum pressure adjustment g maximum pressu...

  • Page 11

    Taura 24 mcs w top 29 entry installer parameters menu selector turned to “reset” for 10 seconds: turn to “winter” when the 3 leds blink fast turn the heating knob to exit the menu (automatic exit after 2 minutes of knob inactivity) parameter no. 7 red=off - green=on - yellow=off hot water user max. ...

  • Page 12

    Taura 24 mcs w top 30 after establishing the parameter to be set, use the following conversion tables to understand the value being set, ac- cording to the blinking of the leds. Off means led off, on means led on, whereas on bl means led blinking. Red green yellow max. Heating power off off off 00-1...

  • Page 13

    Taura 24 mcs w top 31 3.2 system start-up checks to be made at first ignition, and after all maintenance operations that involved disconnecting from the systems or an intervention on safety devices or parts of the boiler: before lighting the boiler: • open any on-off valves between the boiler and th...

  • Page 14: Air

    Taura 24 mcs w top 32 a a b fig. 4 combustion analysis two sampling points have been included at the top of the boiler, one for fumes and the other for air. To take the samples: 1) insert the probes as far as the stop; 2) open a hot water tap; 3) adjust the hot water temperature to maximum. 4) wait ...

  • Page 15

    3.4 troubleshooting fault diagnosis the boiler is equipped with an advanced self-diagnosis system. In the event of trouble with the boiler, the 3 leds will indicate the code of the fault. There are faults that cause shutdown: in order to restore operation it suffices to turn the selector (ref. 3 - f...

  • Page 16

    60,5 64,5 60 60 95 60 1 2 3 4 5 4 technical characteristics and data 4.1 dimensions and connections fig. 6 top view bottom view key 1 heating system delivery Ø 3/4” 2 hot water outlet Ø 1/2” 3 gas inlet 1/2” 4 tap water inlet Ø 1/2” 5 heating system return Ø 3/4” if using the lej line plumbing kit, ...

  • Page 17

    Taura 24 mcs w top 35 4.2 general view and main components fig. 7 81 22 10 8 74 7 44 9 11 32 42 16 27 19 26 91 56 29 43 49 28 5 90 34 36 47 38 20 21 14 114 key 5 airtight chamber 7 gas inlet 8 tap water outlet 9 tap water inlet 10 system delivery 11 system return 14 safety valve 16 fan 19 combustion...

  • Page 18

    Taura 24 mcs w top 36 4.3 technical data table 4.4 diagrams pressure - power diagrams head available for the system 0 1 2 3 4 5 6 0 500 1.000 1.500 2.000 q [l/h] h [m h 2 o] mbar kw g31 lpg g20 natural gas powers pmax pmin heating power (net heat value - hi) kw 25,8 8,3 available thermal power 80°c ...

  • Page 19

    Taura 24 mcs w top 37 4.5 wiring diagram 34 43 49 mf10f a transformer 42 11 4 72 44 16 32 230v 50hz x5 x3 x7 x6 x4 1 2 1 2 3 1 2 3 4 1234567 123456789 10 1 1 fuse x1 n l 81 47 38 f 3.15a f 3.15a 139 fuse caution before connecting the room thermostat or the remote timer control, remove the jumper on ...

  • Page 20

    108 bruciatori caldaie murali e terra a gas gruppi termici in ghisa e in acciaio generatori di aria calda trattamento acqua condizionamento lamborghini calor s.P.A. Via statale, 342 44040 dosso (ferrara) italia tel. Italia 0532/359811 - export 0532/359913 fax italia 0532/359952 - export 0532/359947 ...