Lattner Boiler Company SPACE SAVER Operating Instructions Manual

Summary of SPACE SAVER

  • Page 1

    1 installation, maintenance, and service instruction manual space saver electric hot water boilers general information …………………………….Page 1 installation ………………………...……………..Page 2 start up …………………………………………..Page 3 maintenance ……………………….……………..Page 3 control ……………………………………………..Page 4 service instruction...

  • Page 2

    2 installation 1. Install drain valve furnished with boiler. 2. Set boiler in position to conform to local codes. Minimum clearances: front – 6 inches to door or 3 feet to wall; back – 1 inch; left side – 1 inch; right side – 10 inches. A minimum distance of 34 inches must be maintained above the bo...

  • Page 3

    3 start up 1. Place disconnect switch and control circuit switch in the off position. Fill system with water to pre-determined cold fill pressure (one pound of pressure is required for every 2.31 feet of piping system height above the pressure gauge). 2. Purge all air at the highest point in the sys...

  • Page 4

    4 controls controls –all basic controls and terminals are located in an integral ventilated control cabinet, factory wired and functionally tested. Controls include class k fuses with 50,000 ampere interrupting capacity, magnetic contactors ul listed for 100,000 cycles, 120v control transformer with...

  • Page 5

    5 service instructions disconnect all sources of power before servicing unit. If it is necessary to replace a factory installed part, be sure to use lattner replacement part. Replacement parts are available through authorized lattner representatives or directly from the factory. When ordering replac...

  • Page 6

    Lattner boiler limited warranty a lattner boiler shell is guaranteed to be constructed in accordance with the asme code. An independent asme boiler inspector inspects the construction of each boiler and: (1) checks mill test reports on all materials used to ensure that the chemical and physical anal...

  • Page 7

    Standard terms & conditions limitation on quotation unless otherwise stated in the quotation, the quotation will remain valid for a period of thirty (30) days from the date hereof, at which time it will automatically expire unless extended by a signed document issued by the company, from its headqua...