LCN LCN-GBL Installation Manual

Summary of LCN-GBL

  • Page 1

    Lcn-gbl installation guide local control network 1 ® pir motion detector and light sensor for the i-connection in glass design the lcn-gbl is an indoor pir motion detector with integrated light sensor in the lcn-gt series design. Optionally a humidity sensor lcn-efs can be inserted. The pir motion d...

  • Page 2: Lcn-Gbl

    Lcn-gbl local control network - building controls in perfection 2 how the light sensor functions: after connecting, the lcn-gbl will de detected automatically and its measured value transferred into the second controller variable (r2-var) of the module. You can control the value in the status window...

  • Page 3: Lcn-Gbl

    3 how the pir motion detector functions: when an object is detected, the connected module sends out a long command (standard: key b4). The long command will only be sent once, even when the movement lasts a very long time. 5 seconds after the movement has ended the lcn-gbl triggers off the release c...

  • Page 4: 1   1    B4    R2-Var

    Letting the pir motion detector work on other keys through separating the circuit path, the light sensor will be deactivated. Then there is only one light sensor per module active! The key b4 is reserved with the integrated motion detector. As a result the fourth threshold cannot be used. Additional...

  • Page 5: Lcn-Gbl

    Lcn-gbl installation guide local control network 5 ® installing/uninstalling the lcn-gbl is delivered in a housing, which can be installed on a light outlet box (35 mm, e.G.: ). An additional screw fitting is possible and often useful. When installing on ceilings: check for a safe fixing in every ca...

  • Page 6: Lcn-Gbl

    Lcn-gbl local control network - building controls in perfection 6 ® installation guide installing the optional humidity sensor lcn-efs an optional humidity sensor lcn-efs is available to be subsequently built into the lcn- gbl. The use of the built in humidity sensor lcn-efs is only possible with mo...

  • Page 7: Lcn-Gbl

    Lcn-gbl installation guide local control network 7 ® technical data of the humidity sensor lcn-efs air humidity triggering: 1% accuracy at 20-80% air humidity: ± 4% outside the given areas: ± 6% dew point resolution: 0,1°c accuracy at 20-80% air humidity and 10-40°c environmental temperature: ± 2°c ...

  • Page 8: Installation Guide

    Installation guide local control network - building controls in perfection 8 lcn-gbl issendorff kg, 31157 sarstedt lcn-gbl d12/2012 technical information and images are non binding. Changes are reserved. Technical hotline: +49 5066 998844 or www.Lcn.De ® technical data connection power supply: power...