Legend LB 1000 Installation Operation & Maintenance - Installation Instructions

Manual is about: GAS-FIRED POWER BURNER COPPER BOILERS

Summary of LB 1000

  • Page 1

    1 place these instructions adjacent to boiler and notify owner to keep for future reference part no. 212107-000 rev. 00 warning: if the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. — do not store or use g...

  • Page 2: Rough-In Dimensions

    2 rough-in dimensions minimum clearances to combustibles: • 4” (102 mm) rear • 0” (0 mm) top & sides • 6” (152 mm) vent table 1, gas and electrical characteristics manifold pressure maximum supply pressure electrical characteristics model type of gas inches w.C. Kpa inches w.C. Kpa volts/hz a m p e ...

  • Page 3

    3 table 4, head loss at flow rates/minute and temperature rise shown input f° 18f° 20f° head loss boiler model btuh kw c° 10c° 11.1c° feet m e t r e s inlet & outlet lb/lw-500 500,000 gpm 50 45 10 2” npt natural 146 lpm 189 172 3.0 lb/lw-500 450,000 gpm 45 41 8.4 2” npt propane 132 lpm 170 155 2.6 l...

  • Page 4: Foreword

    4 foreword this design complies with the latest edition of the ansi z21.13 - csa 4.9 low-pressure boiler standard. Compliance under this standard implies that when the boiler underwent test, the gas manifold and control assembly provided on the boiler met safe lighting and other performance criteria...

  • Page 5: High Altitude Installations

    5 these are available from the canadian standards association, 8501 east pleasant valley road, cleveland, oh 44131, usa, or, canadian gas association laboratories, 55 scarsdale road, don mills, ontario m3b 2r3, canada. Grounding instructions this boiler must be grounded in accordance with the nation...

  • Page 6: Features/controls

    6 note: some gas utility companies derate their gas for altitude, making it unnecessary to install high altitude orifices. Call the local gas utility company to verify btu content. Field installed components when installing the boiler, the following components must be used, if applicable: 1) circula...

  • Page 7

    7 the bfs, the main burner is extinguished (if boiler is running) or the boiler will not start up. Blower prover switch the blower prover switch (bps) fig. 4, is similar in construction to the bfs. It is a single-pole, normally open pressure switch that will close its contacts when a rising positive...

  • Page 8

    8 circulating pump hot water supply systems, the circulating pump is integral to the lw models. This pump has been lubricated at the factory, and future lubrication should be in accordance with the motor manufacturer’s instructions provided as a supplement to this manual. For hot water heating syste...

  • Page 9: Installation Instructions

    9 if the boiler is installed above radiation level, a low water cutoff device must be installed in the boiler outlet at the time of installation. Chemical vapor corrosion water boiler corrosion and component failure can be caused by the heating and breakdown of airborne chemical vapors. Spray can pr...

  • Page 10

    10 or spaces freely communicating with the outdoors. The installation instructions for confined spaces in tightly constructed buildings must be followed to ensure adequate air supply. Confined space a. U.S. Installations when drawing combustion and dilution air from inside a conventionally construct...

  • Page 11

    11 consideration is recommended, before locating the vent termination near walkways, windows and building entrances. Direct venting into dead spaces such as; alleys, atriums and inside corners can cause recirculation of flue gases. Recirculation of flue gases will cause sooting, premature failure of...

  • Page 12

    12 notes: if the exhaust vent terminal is within 10’ (3.0 m) of a wall or parapet, it must extend a minimum of 2’ (610 mm) above the wall or parapet. Joints are not joined to show vent pipe orientation. Figure 9. Vertical termination figure 9a. Through the wall termination (twt) notes: joints are no...

  • Page 13

    13 the boot-tee drain cover is required in order to dispose of the condensate from the venting system. The plastic tube (3/8 [9 mm] id, 10 feet [3 m] long) needed to route the condensate to a suitable drain is provided with the boiler. 1. Attach the boot tee drain cover to the appropriate leg of the...

  • Page 14

    14 figure 11. Direct vent horizontal figure 11a. Direct vent vertical caution direct venting into dead air spaces such as; alleys, atriums and inside corners can cause recirculation of flue gases. Recirculation of flue gases will cause sooting, premature failure of the heat exchanger and icing of th...

  • Page 15

    15 figure 11b. Direct vent, vertical vent termination with horizontal intake figure 11c. Direct vent using twt with vertical intake caution direct venting into dead air spaces such as; alleys, atriums and inside corners can cause recirculation of flue gases. Recirculation of flue gases will cause so...

  • Page 16: System Installation

    16 twt shall not be greater than ninety (90) equivalent feet [27.4 m] of vent pipe nor less than nine (9) feet [3 m] (excluding fittings) unless the vent is through a non-combustible wall. A maximum of three (3) 90° degree elbows may be used. For standard installations where no air intake piping is ...

  • Page 17

    17 manifold headers are recommended for split systems with or without zone values and also those installations with zone circulators. If the system is to be split at remote points, good practice requires special attention be given to main pipe sizing to allow balancing of water flow. 5. Cooling pipi...

  • Page 18

    18 danger temperature setting should not exceed safe use temperature at fixtures. See water temperature control warning on page 28. If higher preheat temperatures are necessary to obtain adequate booster output, add an anti-scald valve for hot water supplied to fixtures. One legend (model lw) hot wa...

  • Page 19

    19 hard water conditions where hard water conditions exist, water softening or the threshold type of water treatment is recommended. This will protect the dishwashers, coffee urns, water heaters, water piping and other equipment. When water softening or water treatment is not practical, a comparativ...

  • Page 20

    20 size of gas supply piping may be larger than heater connection on installations where a significant run of piping is required. To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to boiler gas inlet. Fittings and unions in the gas line must be of the ...

  • Page 21

    21 t a ble 8. Suggested pipe size for multiple gas appliances (prop ane gas). Nominal maximum cap acity of pipe in btu/hr and kw for gas pressures of 14 in. W .C. (0.5 p si) or less and iron pipe a pressure drop of 0.5 in. W .C. (based on 0.60 s pecific gravity gas w/heating v alue of 1,000 btu's/ft...

  • Page 22

    22 figure 16. Connection diagram.

  • Page 23

    23 figure 17 - schematic diagram.

  • Page 24: General

    24 lighting and operating instructions are included with this manual. By using these instructions, the user may be able to make minor operational adjustments and save unnecessary service calls. However the user should not attempt repairs, but should contact a service technician or gas supplier. Gene...

  • Page 25: Operating Instructions

    25 lighting & operation instructions for models lb/lw-500 only: stop ! Follow “b” in the safety information above on this label. If you don’t smell gas, go to the next step. 8. Turn top knob of gas control counter- clockwise to “on” position, (fig. B). 9. Replace top cover. 10. Turn power switch to ...

  • Page 26: Operating Instructions

    Lighting & operation instructions for models lb/lw-750 and 1000 only: . For your safety read before operating operating instructions to turn off gas to appliance warning: if you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss ...

  • Page 27

    In the combustion chamber to clear. If you detect gas odor at the end of this period do not proceed with lighting. Recognize that gas even if it seems weak, may indicate presence of accumulated gas someplace in the area with risk of fire or explosion. See the front page for steps to be taken. Inlet ...

  • Page 28

    28 for lb/lw-750 and lb/lw-1000 models: 1. Manually shut off the gas supply by one of the two methods. On boilers that have a manual shutoff valve downstream from the automatic gas valves, turn the manual shut off valve to the “off” position. On boilers that do not have the manual shut off valve loc...

  • Page 29: Maintenance

    29 2. If the ignition control determines the actual water temperature at the outlet temperature sensing probe is below the programmed temperature set-point less the switching differential, and the thermostat circuit is closed, a call for heat is activated. 3. The control then performs selected syste...

  • Page 30: Dia-Scan II

    30 flame pattern should have hard, uniform blue flames surrounding the burner, see figure 19. If the flame is pulsing, floating, yellow and/or lifting off the burner, check the manifold gas pressure and combustion air supply; maintain a clear area around the boiler at all times. If the aforementione...

  • Page 31

    31 figure 20. The ignition control continuously performs various diagnostic tests to verify proper appliance and control operation. Should an unsafe condition occur, the control will shut down the burner and illuminate the appropriate diagnostic indicators on the display board, figure 20, indicating...

  • Page 32

    32 options/features setting procedures: • set appliance temperature set-point value • set appliance switching differential value • select appliance post-circulate time • set appliance circulating pump mode • check appliance cycle count • control the water temperature in a storage tank green status l...

  • Page 33

    33 display total cycle count the main control board counts the number of cycles the appliance has operated. In the main control board, a cycle is counted every time the gas valve is energized. To access this number, perform the following procedure: 1. Press the select push-button on the display boar...

  • Page 34: Troubleshooting

    34 if the adjust push-button is held down long enough, the set-point will reach 110°f (43°c), the minimum value (or 190°f [88°c], the maximum value) and stop. At this point, if the desired set-point is not obtained, release the adjust push-button and depress it again. The set-point value will now re...

  • Page 35

    35 note: under certain circumstances, a problem with the low gas pressure switch (and/or high gas pressure switch on csd-1 models) may cause an error code of circulation fail or inducor fail depending on when the failure occurred in the cycle. Note: upon lockout, manually push the enter/reset button...

  • Page 36: Limited Warranty

    36 limited warranty a. O. Smith corporation, the warrantor, extends the following limited warranty to the owner of this boiler: 1. If within ten years after initial installation of the boiler, a coiled heat exchanger or gas burner shall prove upon examination by the warrantor to be defective in mate...