Lochinvar NSF SSB-i & s--01 Installation And Service Manual

Manual is about: Lochinvar Electric Booster Water Heaters Installation and Service Manual

Summary of NSF SSB-i & s--01

  • Page 1

    Electric booster water heaters are available for operation on standard power systems. Check the nameplate for the proper power supply. All internal electrical connections have been made at the factory. See circuit breaker and fuse sizing chart for supply wire size, fuse, breaker and conduit recommen...

  • Page 2

    Pressure reducing valve proper operation of the dishwater rinse nozzles requires available water pressure at the nozzle be between 15 and 25 psi when nozzle is operated. 20 psi is recommended. If water pressure available to the booster heater inlet is over 20 psi, a pressure reducing valve should be...

  • Page 3

    Outlet using a 3/4 in. Union and piping connect the booster heater water outlet to the dishwasher sanitizing rinse pipe connection. Install a temperature/pressure gauge in outlet line. Water temperature at outlet should be 180°f (82°c). The temperature sensing element must be in water stream. Manufa...

  • Page 4

    Cause c thermostats may not be functioning correctly or may be improperly set. Solution - inspect thermostats for proper operation and correct settings. If setting is below the maximum, reset to 190ºf(88ºc) if defective and not functioning, replace. Cause d contactors are not performing. Solution - ...

  • Page 5

    Cause b control thermostat may be set too high or be defective. Solution - reset thermostat(s). If condition is not corrected, replace thermostat(s). Chattering contactor(s) or noisy relay. Cause a contactors chatter or hum excessively when pulled in. Solution - accumulation of dirt will prevent pro...

  • Page 6

    6 high temperature limit switch recalibration if the temperature in the heater exceeds 210ºf (99ºc), the high temperature limit will shut off the power. The switches must be manually reset by pushing the red buttons. The limit switch has been calibrated at the factory and should not require adjustin...

  • Page 7

    7 circuit breaker and fused disconnect switch sizes kw volts ph l1 l2 l3 breaker or fuse size copper wire size conduit size 6 208 1 29 29 — 40 8 1/2” 208 3 14 25 14 40 8 3/4” 240 1 25 25 — 40 8 1/2” 240 3 13 22 13 30 10 1/2” 480 3 6 11 6 15 14 1/2” 9 208 1 43 43 — 60 6 3/4” 208 3 22 38 22 50 8 3/4” ...

  • Page 8

    8 dimensions hanging support.

  • Page 9

    9 plumbing connections.

  • Page 10

    10

  • Page 11

    11.

  • Page 12