Lochinvar TNR-I&S-02 Installation & Service Manual

Manual is about: HIGH EFFICIENCY COMMERCIAL GAS WATER HEATER

Summary of TNR-I&S-02

  • Page 1

    1 tnr-i&s-02 high efficiency commercial gas water heater table of contents general information ...................................................... 1 installation .................................................................. 2 locating the water heater ...........................................

  • Page 2

    2 tnr-i&s-02 warning do not attempt to light any gas appliance if you are not certain of the following: • liquefied petroleum gases/propane gas and natural gas have an odorant added by the gas supplier that aids in detection of the gas. • most people recognize this odor as a “sulfur” or “rotten egg”...

  • Page 3

    3 tnr-i&s-02 air requirements 1. Do not obstruct the flow of combustion and ventilating air. 2. For safe operation, adequate air is needed for combustion and ventilation. Sooting may result in serious damage to the water heater and risk of fire or explosion. It can also create a risk of asphyxiation...

  • Page 4

    4 tnr-i&s-02 caution if sweat fittings are to be used, do not apply heat to the nipples in front or side of the water heater. Sweat the tubing to the adapter before fitting the adapter to the water connections. It is imperative that heat is not applied to the nipples containing a plastic liner. Warn...

  • Page 5

    5 tnr-i&s-02 from thermal expansion such as pressure bulges and/or deformities.Your water supplier or local plumbing inspector should be contacted on how to control this situation. 3. After installation of the water lines, open the main water supply valve and fill the water heater. While the water h...

  • Page 6

    6 tnr-i&s-02 venting caution the vent shall terminate a minimum of 12 inches above expected snowfall level to prevent blockage of vent termination. The horizontal centerline of the exhaust vent terminal (if applicable) must not be located lower than the horizontal centerline of the air intake termin...

  • Page 7

    7 tnr-i&s-02 direct vent terminal location plan the vent system layout so that proper clearances are maintained from plumbing and wiring. Before the vent is installed, determine the vent pipe termination location as shown below in figure 10. Vent terminals must terminate at least 3 feet (0.9 m) abov...

  • Page 8

    8 tnr-i&s-02 3. For horizontal, the venting system shall terminate 4 foot below, 4 foot horizontally from or 1 foot above any door, window, or gravity air inlet into building. 4. The manufacturer also recommends the vent system terminations not be installed closer than 3 feet from an inside corner o...

  • Page 9

    9 tnr-i&s-02 through the wall venting with low ground clearance: when venting cannot exit through the wall at a height greater than or equal to 12" (30.5 cm) (and above expected snow level) from the ground, then the installation must be modified as shown below (see figure 13). Determining required v...

  • Page 10

    1 0 tnr-i&s-02 horizontal installation: in a horizontal application, it is important that condensate not be allowed to buildup in the exhaust vent pipe. To prevent this from happening, the pipe should be installed with an slight upward slope. The vent system should be supported every 5 feet of verti...

  • Page 11

    1 1 tnr-i&s-02 coaxial venting installation procedure vertical installation (recommended) 1. Become familiar with coaxial vent kit. 2. Determine the best location for the termination kit. 3. Cut the recommended 5" diameter hole. Through the wall venting with low ground clearance: when venting cannot...

  • Page 12

    1 2 tnr-i&s-02 4. Partially assemble vent kit by performing the following: a. Cement concentric y fitting to larger diameter pipe. (see figure 18). B. Cement rain cap to smaller diameter pipe. (see figure 19). 5. Install concentric y fitting and pipe assembly through the structure’s hole and field-s...

  • Page 13

    1 3 tnr-i&s-02 warning do not attempt to start this water heater until vent pipe solvent fumes completely clear from the room and inside the vent piping. Vent pipe preparation initial preparation 1. Make sure the solvent cement you are planning to use is designed for the specific application you are...

  • Page 14

    1 4 tnr-i&s-02 caution the water heater and individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of ½ psi (3.5 kpa). The water heater must be isolated from the gas supply piping system by closing its man...

  • Page 15

    1 5 tnr-i&s-02 caution do not energize the electric circuit before the water heater tank is filled with water. This controller is polarity sensitive. If the hot and neutral supply voltage is reversed, the controller will not sense flame and the water heater will not operate. Verify polarity before c...

  • Page 16

    1 6 tnr-i&s-02 lighting instructions figure 24 lighting instruction label.

  • Page 17

    1 7 tnr-i&s-02 temperature adjustment the temperature selector knob of the thermostat has been adjusted to 120° f when shipped from the factory. During the winter season or any cold period, you may desire a higher temperature setting to adjust for the colder incoming water. This adjustment, however,...

  • Page 18

    1 8 tnr-i&s-02 flushing water heater 1. Turn off the water heater electrical disconnect switch. 2. Open the drain valve and allow water to flow until it runs clean. 3. Close the drain valve when finished flushing. 4. Turn on the water heater electrical disconnect switch. Draining water heater the wa...

  • Page 19

    1 9 tnr-i&s-02 anode inspection and replacement this water heater is equipped with multiple sacrificial anodes. Anodes protect the glass-lined tank from corrosion by sacrificing themselves through electrolysis. When the anode material is consumed, there is no more protection and corrosion of the tan...

  • Page 20

    2 0 tnr-i&s-02 make sure that water heater is plugged in. When the switch is on, is there 120vac between l1 and n on the terminal block? If not, then check for loose wire connections on the “power switch wire harness.” if connections are ok, then replace the switch. If there is voltage between l1 an...