M-system R3-ND1 Instruction Manual
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8353 Rev.11 P. 1 / 6
INSTRUCTION MANUAL
DeviceNet INTERFACE MODULE
(for 16-point analog signals)
MODEL
R3-ND1
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■
PACKAGE INCLUDES:
Network interface module ............................................... (1)
■
MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
■
INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
■
EDS FILE
EDS files are downloadable at M-System’s web site:
http://www.m-system.co.jp
POINTS OF CAUTION
■
CONFORMITY WITH EU DIRECTIVES
•The equipment must be mounted inside the instrument
panel of a metal enclosure.
•The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrat-
ed in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
■
HOT INSERTION/REMOVAL OF MODULES
•It is possible to replace the module with the power is sup-
plied. Be sure to replace it when the module is not com-
municating with a host, as it is possible to affect the sys-
tem. However, replacing multiple modules at once may
greatly change line voltage levels. We recommend that
you replace them one by one.
■
POWER INPUT RATINGS
•Operational range & power consumption: Check the pow-
er rating for the unit on the specification label.
Rating 100 – 120V AC: 85 – 132V, 47 – 66 Hz, approx. 20VA
Rating 200 – 240V AC: 170 – 264V, 47 – 66 Hz, approx. 20VA
Rating 24V DC: 24V ±10%, approx. 12W
■
ENVIRONMENT
•Indoor use
•When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
•Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
•Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■
WIRING
•Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
•Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■
AND ....
•The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
INSTALLATION
Use the Installation Base Model R3-BS, or Model R3-BSW
for free I/O address capability.
Before mounting the Network Interface Module onto the
Base, be sure to configure the module as explained below.
■
DATA ALLOCATION
The setting determines the data area size assigned to each
I/O module mounted on the base.
The data sent/received via DeviceNet is mapped according
to this setting.
See “COMPONENT IDENTIFICATION”.
■
NODE ADDRESS & BAUD RATE
See “COMPONENT IDENTIFICATION”.
■
NETWORK SLOTS ON THE BASE
I/O 1
I/O 2
I/O n
With Model R3-BS base, mount the I/O Modules from the
left end (I/O 1) to the right in order that the Network Mod-
ule assigns data areas from I/O 1.
Network Module(s) and Power Module are mounted basi-
cally at the right end though technically they could be
mounted in any position.
With Model R3-BSW base, there is no limitation in mount-
ing positions as I/O address can be assigned freely to each
module using rotary switches equipped on the base.