Macurco SS102H Installation & Operating Instructions

Summary of SS102H

  • Page 1

    1 macurco inc. Controllers & carbon monoxide detectors ss103-3a, ss103-10a ss102h, ss102hc-1 installation & operating instructions www.Macurco.Com note: suggested wire size vs length of wire between each sensor & control panel size maximum distance #18 500 feet #16 800 feet #14 1250 feet general inf...

  • Page 2

    2 macurco controllers & detectors (cont.) ss102hc-1 sensor operation the ss102hc-1 is a microcomputer controlled sensor. It has a 2 1/2 minute warm up cycle, during which its outputs progressively increase from 1.0 to 2.1 volts. The internal switch must be set to volts. The green led type light turn...

  • Page 3

    3 macurco controllers & detectors (cont.) ss103 operation start-up turn the fan sensitivity level pots to the center of their ranges. When power is first applied to the ss103, only the green “power” light should be on. If ss102hc-1 sensors are used, the appropriate green sensor lights on the ss103 w...

  • Page 4

    4 macurco controllers & detectors (cont.) setting the controls if your installation has no pre-determined fan and alarm set points, macurco makes the following suggestions: set the fan 1 level 50% higher than the average time weighted average of carbon monoxide (co), usually 50 ppm, that is desired ...

  • Page 5

    5 englewood, colorado 80110 www.Macurco.Com rev. 2/99.