Majestic DBDV36IL Installation Manual - page 30
30
Majestic • DBDV36IN, DBDV36IL, DBDV42IN, DBDV42IL Installation Manual • 2397-980 Rev. B • 5/16
EXHAUST VENT PIPE
INLET AIR VENT PIPE
Figure 4.25. Coaxial/Colinear Appliance Connector
OUTSIDE FACE OF
FIREPLACE
TOP OF FIREPLACE
OPENING
SHADED AREA DEFINED AS
“INSIDE EXISTING MASONRY
FIREPLACE”
3 IN. MIN.
5 IN. MIN.
EXHAUST VENT PIPE
Figure 4.26 Existing Fireplace DV-46DVA-GCL
Clearance Requirements
Clearances to Combustibles:
Refer to Section 3 and Section 10 for clearances to the
appliance, mantel, mantel legs and wall projection.
Refer to Section 8 for pipe clearances to combustibles.
Termination Cap
For installation of termination cap see minimum vent
heights for various pitched roofs. See Section 4.
Flue Damper
Fully lock the solid fuel fi replace’s fl ue damper in the open
position, OR completely remove it.
Venting Components
The LINK-DV30B is approved for use with the coaxial/co-
linear venting application. The LINK-DV30B kit includes:
• Two 30 feet sections of fl exible vent pipe (3 inches Ø).
One section is used to draw combustion air and the other
section is used to expel exhaust gases.
• One vertical termination cap.
WARNING! Risk of Fire! Coaxial to colinear venting con-
fi guration may only be used in existing non-combustible
chimney. Installation in any other venting application
could cause fi re.
Prior to installing the gas appliance:
• Have the chimney and adjacent structure inspected
and cleaned by qualifi ed professionals. Hearth & Home
Technologies recommends that NFI or CSIA certifi ed
professionals, or technicians under the direction of certi-
fi ed professionals, conduct a minimum of a NFPA 211
Level 2 inspection of the chimney.
• Replace component parts of the chimney and fi replace
as specifi ed by the professionals.
• Ensure all joints are properly engaged and the chimney
is properly secured.
Coaxial to Colinear Venting
The coaxial to colinear adapter (DV-46DVA-GCL) is ap-
proved for installations into solid fuel masonry or factory
built fi replaces that have been installed in accordance
with the National, Provincial, State and local building
codes. The DV-46DVA-GCL must be recessed into exist-
ing masonry fi replace. See Table 4.2, and Figures 4.25
and 4.26.
Table 4.2
CLEARANCE TO COMBUSTIBLES REQUIREMENTS
DV-46DVA-GCL 3
IN.
Exhaust Vent Pipe
5 IN.
CAUTION! DO NOT use any fl ue restrictor when vent-
ing with the DV-46DVA-GCL adapter and LINK-DV30B
kit. This may result in poor fl ame appearance, sooting,
pilot malfunction, or overheating.
Summary of DBDV36IL
Page 1
1 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 installation manual installation and appliance setup installer: leave this manual with party responsible for use and operation. Owner: retain this manual for future reference. Notice: do not discard this...
Page 2
2 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 safety alert key: • danger! Indicates a hazardous situation which, if not avoided will result in death or serious injury. • warning! Indicates a hazardous situation which, if not avoided could result in ...
Page 3: Attention Installer:
3 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 installation standard work checklist customer: lot/address: model (circle one): dbdv36in dbdv36il dbdv42in dbdv42il date installed: location of fireplace: installer: dealer/distributor phone # serial #: ...
Page 4
4 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 b. Glass specifi cations hearth & home technologies appliances manufactured with tempered glass may be installed in hazardous lo- cations such as bathtub enclosures as defi ned by the consumer product sa...
Page 5
5 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 h. Requirements for the commonwealth of massachusetts for all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residentia...
Page 6
6 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 2 2 getting started a. Design and installation considerations majestic direct vent gas appliances are designed to oper- ate with all combustion air siphoned from outside of the building and all exhaust g...
Page 7
7 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 d. Inspect appliance and components • carefully remove the appliance and components from the packaging. • the vent system components and decorative fronts may be shipped in separate packages. • if packag...
Page 8
8 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 3 3 framing and clearances appliance dimensions table a. Appliance/decorative front dimension diagrams dimensions are actual appliance dimensions. Use for reference only. For framing dimensions and clear...
Page 9
9 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 figure 3.2 decorative front dimensions a b c d e f g a b c d e f g dbm36bk dbdv36in/il in. 34-1/16 24-1/4 35-15/16 1-1/2 7-1/16 30-11/16 33-7/16 mm 865 616 913 38 179 779 849 dbm42bk dbdv42in/il in. 41 2...
Page 10
10 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 b. Clearances to combustibles when selecting a location for the appliance it is important to consider the required clearances to walls (see figure 3.3). Warning! Risk of fire or burns! Provide adequate ...
Page 11
11 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 figure 3.4 clearances to combustibles * adjust framing dimensions for interior sheathing (such as sheetrock) c** add 12 inches for rear venting with one 90º elbow. F g h i j e c b d a * minimum framing ...
Page 12
12 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 c. Constructing the appliance chase a chase is a vertical box-like structure built to enclose the gas appliance and/or its vent system. In cooler climates the vent should be enclosed inside the chase. N...
Page 13
13 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 a. Vent termination minimum clearances roof pitch h (min.) ft. Flat to 6/12...........................................................1.0* over 6/12 to 7/12 ................................................
Page 14
14 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 b. Chimney diagram figure 4.3 minimum clearances for termination o n p r q x = air supply inlet a = 12 inches.................Clearances above grade, veranda, porch, deck or balcony b = 12 inches..........
Page 15
15 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 c. Approved pipe this appliance is approved for use with hearth & home technologies dvp or slp venting systems. Refer to sec- tion 12.A for vent component information and dimensions. Do not mix pipe, fi...
Page 16
16 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 d. Use of elbows diagonal runs have both vertical and horizontal vent as- pects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect. See figure 4.4. ...
Page 17
17 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 e. Measuring standards vertical and horizontal measurements listed in the vent diagrams were made using the following standards: • pipe measurements are shown using the effective length of pipe. See sec...
Page 18
18 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 top vent - horizontal termination fire risk. Explosion risk. Do not pack insulation or other combustibles between ceiling fi restops. • always maintain specifi ed clearances around venting and fi restop...
Page 19
19 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 top vent - horizontal termination figure 4.10 one elbow note: for corner installations: a 6 inch (152 mm) section of straight pipe may need to be attached to the appliance before a 90º elbow, to allow t...
Page 20
20 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 figure 4.11 two elbows top vent - horizontal termination - (continued) dbdv36in dbdv36il v 1 minimum h 1 + h 2 maximum elbow only not allowed 6 in. 152 mm not allowed 1 ft. 305 mm 2 ft. 610 mm 1-1/2 ft....
Page 21
21 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 figure 4.12 top vent - horizontal termination - (continued) three elbows v 1 min. H 1 max. V 2 min. H 2 max. Elbow only 2 ft. 610 mm 0 in. 0 mm 1 ft. 305 mm 6 in. 152 mm 3 ft 914 mm 6 in. 152 mm 2 ft. 6...
Page 22
22 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 top vent - vertical termination no elbow figure 4.13 note: if installing a vertical vent/ termination off the top of the ap- pliance, the fl ue restrictor should be used. V 1 = 40 ft. Max. (12.4 m) v 1 ...
Page 23
23 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 exhaust baffle flue restrictor (set on either top or rear vent opening; shown on rear) flue restrictor instructions 1. Remove exhaust baffl e using a 1/4 inch nut driver by removing the two screws secur...
Page 24
24 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 two elbows figure 4.16 top vent - vertical termination - (continued) v 1 h 1 maximum v 2 v 1 + v 2 min. Elbow only 2 ft. 610 mm * * * 6 in. 152 mm 6 ft. 1.8 m * * * 2 ft. 610 mm 11 ft. 3.4 m * * * 3 ft....
Page 25
25 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 top vent - vertical termination - (continued) three elbows v 1 h 1 + h 2 v 2 v 1 + v 2 minimum h 1 + h 2 maximum elbow only 1 ft. 305 mm * * * 1 ft. 305 mm 6 in. 152 mm 2 ft. 610 mm * * * 2 ft. 610 mm 1...
Page 26
26 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 figure 4.18 rear vent - horizontal termination no elbow h 1 = 16 in. (406 mm) maximum h 1.
Page 27
27 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 rear vent - horizontal termination - (continued) two elbows figure 4.20 three elbows figure 4.19 h 1 maximum v 1 minimum h 2 h 1 + h 2 maximum 1 ft. 305 mm back to back 90º elbows 1 ft. 305 mm 2 ft. 610...
Page 28
28 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 figure 4.21 rear vent - vertical termination one elbow figure 4.22 two elbows v 1 minimum h 1 maximum 6 in. 152 mm 2 ft. 610 mm 1 ft. 305 mm 3 ft. 914 mm 2 ft. 610 mm 5 ft. 1.5 m 3 ft. 914 mm 7 ft. 2.1 ...
Page 29
29 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 rear vent - vertical termination - (continued) three elbows figure 4.24 three elbows figure 4.23 v 2 v 1 h 2 h 1 installed horizontally h 3 h 1 h 2 v 1 h 1 h 2 h 3 v 1 minimum h 1 + h 2 + h 3 maximum * ...
Page 30
30 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 exhaust vent pipe inlet air vent pipe figure 4.25. Coaxial/colinear appliance connector outside face of fireplace top of fireplace opening shaded area defined as “inside existing masonry fireplace” 3 in...
Page 31
31 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 figure 4.27 existing chimney hearth floor existing chimney exhaust air vent pipe inlet air vent pipe to minimize cold air drafts, seal with non-combustible insulation. Termination cap direct vent firepl...
Page 32
32 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 a. Pipe clearances to combustibles warning! Risk of fire! Maintain air space clearance to vent. Do not pack insulation or other combustibles: • between ceiling fi restops • between wall shield fi restop...
Page 33
33 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 b. Wall penetration framing/firestops combustible wall penetration whenever a combustible wall is penetrated, you must frame a hole for the wall shield fi restop(s). The wall shield fi restop maintains ...
Page 34
34 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 c. Ceiling firestop/floor penetra- tion framing a ceiling fi restop must be used between fl oors and attics. • dvp pipe only - frame an opening 10 in. By 10 in. (254 mm by 254 mm) whenever the vent pene...
Page 35
35 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 caution! Risk of cuts, abrasions or flying debris. Wear protective gloves and safety glasses during instal- lation. Sheet metal edges are sharp. Notice: once appliance is set up for top or rear venting,...
Page 36
36 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 rear vent caution! Risk of cuts, abrasions or flying debris. Wear protective gloves and safety glasses during instal- lation. Sheet metal edges are sharp. Notice: once appliance is set up for top or rea...
Page 37
37 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 b. Securing and leveling the appliance warning! Risk of fire! Prevent contact with: • sagging or loose insulation • insulation backing or plastic • framing and other combustible materials block openings...
Page 38
38 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 7 7 venting and chimneys a. Assemble vent sections (dvp pipe only) attach vent to the firebox assembly note: the end of the pipe sections with the lanced tabs will face toward the appliance. Attach the ...
Page 39
39 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 assemble vent sections (slp only) to attach the fi rst vent component to the starting collars of the appliance: • attach a dvp-slp24 adapter to the starting collar of the appliance. • lock the vent comp...
Page 40
40 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 notice: when installing a vent system with an hrc termination cap, all pipe system joints shall be sealed using a high temperature silicone sealant (300º f minimum continuous exposure rating). • apply a...
Page 41
41 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 e. Vertical termination requirements install metal roof flashing • see minimum vent heights for various pitched roofs (figure 7.12) to determine the length of pipe to extend through the roof. • slide th...
Page 42
42 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 install vertical termination cap • attach the vertical termination cap by sliding the inner collar of the cap into the inner fl ue of the pipe section while placing the outer collar of the cap over the ...
Page 43
43 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 figure 7.16 venting through the wall note: when using termination caps with factory-supplied heat shield attached, no additional wall shield fi restop is required on the exterior side of a combustible w...
Page 44
44 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 a. General information warning! Risk of shock or explosion! Do not wire 110-120 vac to the valve or to the appliance wall switch. Incorrect wiring will damage controls. Notice: this appliance must be el...
Page 45
45 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 b. Wiring requirements intellifire™ plus ignition system wiring • wire the appliance junction box to 110-120 vac for proper operation of the appliance. Warning! Risk of shock or explosion! Do not wire i...
Page 46
46 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 wall switch installation for fan (optional) if the box is being wired to a wall mounted switch for use with a fan (see figure 8.3): • the power supply for the appliance must be brought into a switch box...
Page 47
47 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 a. Fuel conversion • make sure the appliance is compatible with available gas types. • conversions must be made by a qualified service technician using hearth & home technologies specifi ed and approved...
Page 48: Air Shutter
48 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 figure 9.1 air shutter air shutter settings (factory set to minimum vent run e. Air shutter setting air shutter settings should be adjusted by a qualifi ed ser- vice technician at the time of installati...
Page 49
49 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 10 10 finishing a. Facing material • metal front faces may be covered with non-combustible materials only. • facing and/or fi nishing materials must not interfere with air fl ow through louvers, operati...
Page 50
50 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 b. Mantel and wall projections warning! Risk of fire! Comply with all minimum clear- ances as specifi ed. Framing closer than the minimums list- ed must be constructed entirely of noncombustible materia...
Page 51
51 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 c. Decorative front dimensions for finish- ing decorative front fit finish material thickness see figure dbm36bk dbm42bk inside any 10.8 crd36 crd42 overlap 1 inch or less 10.6 inside 1-4 inches 10.7 no...
Page 52
52 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 decorative front finishing material finishing material a (includes 1/8 in. Opening each side of decorative front) finishing material thickness, 1-4 inches maximum b = bottom of finishing material to bot...
Page 53
53 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 finishing strips removed figure 10.9 removing finishing strips. Removal of finishing strips notice: remove fi nishing strips before fi ring appliance. Remove glass frame assembly to access fi nishing st...
Page 54
54 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 11 11 appliance setup figure 11.1 fixed glass assembly b. Remove the shipping materials/inspect grate remove shipping materials from inside or underneath the fi rebox. • the splatter guard is a piece of...
Page 55
55 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 e. Ember placement warning! Risk of explosion! Follow ember place- ment instructions. Do not place ember directly over burner ports. Replace ember material annually. Improp- erly placed ember material i...
Page 56: Log Placement Instructions
56 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 f. Install the log assembly log placement instructions log set assembly: logsdbdv36, logsdbdv42 models: dbdv36in, dbdv36il dbdv42in, dbdv42il figure 1. Log a, log b, log c placement for logsdbdv36 model...
Page 57
57 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 1. (log a): locate the two pin holes on the bottom of log a. Hold the log so that the fl at spot is facing the rear of the appliance and the pin holes are facing the base pan. Place log a over the two p...
Page 58
58 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 c c 5. (log e): log e will utilize two fl at spots for its placement as shown in figure 7. The fl at spots are located on log a and on log c. Place the “bark” end of log e on the fl at spot on log a. Re...
Page 59
59 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 placement for logsdbdv42 models: dbdv42in/dbdv42il log a: srv2397-701 log b: srv2397-702 log c: srv2397-703 log d: srv2397-704 log e: srv2397-705 (qty 3) log f: srv2397-706 caution: logs are fragile, ha...
Page 60
60 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 1. (log a): locate the two pin holes on the bottom of log a. Hold the log so that the fl at spot is facing the rear of the appliance and the pin holes are facing the base pan. Place log a over the two p...
Page 61
61 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 2397-935b c c c c 5. (log e1): log e will utilize two fl at spots for its placement as shown in figure 7. The fl at spots are located on log a and on log c. Place the “bark” end of log e1 on the fl at s...
Page 62
62 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 figure 11.4 placement of lava rock and embers g. Place the lava rock see figure 11.4. Lava rock should be evenly spread on fi rebox bottom, it is not necessary to use the entire bag. Save the remaining ...
Page 63
63 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 12 12 reference materials a. Vent components diagrams figure 12.1 dvp vent components pipe effective length inches millimeters dvp4 4 102 dvp6 6 152 dvp12 12 305 dvp24 24 610 dvp36 36 914 dvp48 48 1219 ...
Page 64
64 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 dvp-hpc1 dvp-hpc2 dvp-trap1 dvp-trap2 dvp-trapk2 dvp-trapk1 dvp-trap horizontal termination cap 15-1/8 in. (384 mm) 12 in. (305 mm) 8 in. (203 mm) max effective length note: heat shields must overlap by...
Page 65
65 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 13-1/4 in. (337 mm) 24-5/8 in. (625 mm) 27-1/2 in. (699 mm) rf6 roof flashing 31 in. (787 mm) 24-5/8 in. (625 mm) 13-1/4 in. (337 mm) rf12 roof flashing cap shield drc-radius 13-7/8 in. (352 mm) 9-1/2 i...
Page 66
66 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 a. Vent components diagrams (continued) figure 12.4 dvp vent components 7-1/4 in. 12 in. 305 mm (184 mm) 5-1/4 in. (133 mm) 12-1/2 in. (318 mm) dvp-tvhw verticaltermination cap (highwind) 14 in. (356 mm...
Page 67
67 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 a. Vent components diagrams (continued) optional wire harness description part number 10 ft pv wire harness pvi-wh10 20 ft pv wire harness pvi-wh20 40 ft pv wire harness pvi-wh40 60 ft pv wire harness p...
Page 68
68 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 a. Vent components diagrams (continued) required wire harness description part number 10 ft pv wire harness pvi-wh10 20 ft pv wire harness pvi-wh20 40 ft pv wire harness pvi-wh40 60 ft pv wire harness p...
Page 69
69 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 a. Vent components diagrams (continued) figure 12.7 slp series vent components 8-3/4 in. 222 mm 6-1/2 in. 165 mm 6-5/8 in. 168 mm 6 in. 152 mm 6-1/2 in. 165 mm 6-5/8 in. 168 mm 9-7/8 in. 251 mm 6-1/2 in...
Page 70
70 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 a. Vent components diagrams (continued) figure 12.8 slp series vent components slp-wt-bk wall thimble-black 26 in. 660 mm dvp-hsm-b extended heat shield slp-trap horizontal termination cap 15-1/8 in. (3...
Page 71
71 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 a. Vent components diagrams (continued) figure 12.9 slp series vent components fire risk. • when using slp-hrc-ss termination cap on top vented fi replaces, a one foot minimum vertical vent section is r...
Page 72
72 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 link-dv30b flex liner kit dv-46dva-gcl coaxial/colinear appliance connector 768-380a stainless steel flex pipe dvp-2sl adapter coaxial to colinear venting figure 12.11 coaxial to colinear vent component...
Page 73
73 majestic • dbdv36in, dbdv36il, dbdv42in, dbdv42il installation manual • 2397-980 rev. B • 5/16 b. Accessories remote controls, wall controls and wall switches follow the instructions supplied with the control installed to operate your fi replace: for safety: • install a switch lock or a wall/remo...