Modine Manufacturing SCW Installation And Service Manual - Warning
INSTALLATION
6
8-504.6
Figure 6.1
Hot/Chilled Water Coil Piping Installation
Piping Insulation
Refrigerant, chilled water and condensate pipes should be
insulated right up to the unit chassis to prevent condensation
which can damage the ceiling and objects located below the
piping. Chilled water valves must also be insulated to
prevent sweating.
Wiring
WARNING
1. Disconnect power supply before making wiring
connections to prevent electrical shock and
equipment damage.
2. All appliances must be wired strictly in accordance
with the wiring diagram furnished with the appliance.
Any wiring different from the wiring diagram could
result in a hazard to persons and property.
3. Any original factory wiring that requires replacement
must be replaced with wiring material having a
temperature rating of at least 105°C.
4. Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% greater than
rated voltage.
CAUTION
Ensure that the supply voltage to the appliance, as
indicated on the serial plate, is not 5% less than the rated
voltage.
Installation of wiring must conform with local building codes,
or in the absence of local codes, with the National Electric
Code ANSI/NFPA 70 – Latest Edition. Unit must be
electrically grounded in conformance to this code. In
Canada, wiring must comply with CSA C22.1, Electrical
Code.
Electric wiring must be sized to carry the full load amp draw
of the motor, starter and any controls that are used with the
unit. See Table 19.1 for Electrical Data.
This equipment in its standard form is designed for an
electrical supply of 208-230V, 1Ph, 60Hz. When connection
to a 115V, 1Ph, 60Hz supply is necessary, a factory
mounted step up transformer must be fitted to the unit.
Any damage to or failure of units caused by incorrect wiring
of the units is not covered by warranty.
Once the refrigeration pipe work is complete, the electrical
supply can be connected by routing the cable through the
appropriate casing hole and connecting the supply and
ground cables to the unit’s power terminals. A plastic sleeve
is provided inside the control panel. Low voltage control
wiring must run through the plastic sleeve on the inside of
the control panel.
Terminal Strip Connections
The terminal strip connections are designed to clamp down
on the wires. To properly connect the wires to the terminal
strip:
1. Push a small flat head screwdriver into the square hole
on the terminal. Press firmly until the screwdriver hits
the back stop and opens the terminal. See Figure 6.2.
2. Remove approximately 3/8” of insulation from the end of
the wire and push the stripped wire into the oval hole in
the terminal.
3. Remove the screwdriver. Pull on the wire to make sure
that it is securely clamped in the terminal.
4. Make sure that the terminal clamp is in contact with bare
wire (insulation removed).
Figure 6.2
Terminal Strip
Fascia Assembly
Once the services have been connected, the four (4) fascia
mounting bolts can be unscrewed approximately 1” from the
condensate tray support channels.