    5/17/2007 1 100 series media converter & industrial ethernet switches user manual & installation guide.

  • Page 2

    5/17/2007 2 industrial media converter installation guide 102mc-xx 102mce-xx-yy 104tx 105tx 108tx where: xx = st or sc and yy = -15, -40, or -80

  • Page 3

    5/17/2007 3 copyright, © n-tron corp., 2007 820 s. University blvd., suite 4e mobile, al usa 36609 all rights reserved. Reproduction, adaptation, or translation without prior written permission from n-tron corp. Is prohibited, except as allowed under copyright laws. Ethernet is a registered trademar...

  • Page 4

    5/17/2007 4 general safety warnings warning: do not operate the equipment in the presence of flammable gasses or fumes. Operating electrical equipment in such an environment constitutes a definite safety hazard. Warning: if the equipment is used in the manner not specified by n-tron corp., the prote...

  • Page 5

    5/17/2007 5 hazardous location installation requirements 1. This equipment is suitable for use in class i, div 2, groups a, b, c, and d, or unclassified or non- hazardous locations. 2. Warning: explosion hazard - substitution of components may impair suitability for class i, division 2. 3. Warning: ...

  • Page 6

    5/17/2007 6 100 series industrial ethernet switches the 100 series unmanaged industrial ethernet switches support high speed layer 2 switching between ports. This series of switches are housed in a ruggedized aluminum enclosure, and provide category-5 compliant 10/100-baset connections for high perf...

  • Page 7

    5/17/2007 7 package contents please make sure the serial over ethernet package contains the following items: 1. 100 series media converter or ethernet switch 2. Instruction sheet contact your carrier if any items are damaged. Unpacking remove all the equipment from the packaging, and store the packa...

  • Page 8

    5/17/2007 8 din-rail mounting install the unit in a standard din rail. Recess the unit to allow at least 2” of horizontal clearance for cat5e cable bend radius. To install the unit to 35mm industrial din rail, place the top edge of the included mounting bracket on the back of the unit against the di...

  • Page 9

    5/17/2007 9 front panel 102mc/mce from top to bottom: spd speed led lnk/act link/activity led rj45 ports auto sensing 10/100baset connection green led lights when power is connected note: the rj45 data port has two led’s located at the left side of the connector. The top led indicates activity (act)...

  • Page 10

    5/17/2007 10 applying power (top view) unscrew & remove the dc voltage input plug from the top header. Install the dc power cables into the plug (observing polarity on unit). Plug the voltage input plug back into the top header. Tightening torque for the terminal block power plug is 0.22 nm/0.162 po...

  • Page 11

    5/17/2007 11 n-tron switch grounding techniques for 100 series the grounding philosophy of any control system is an integral part of the design. N-tron switches are designed to be grounded, but the user has been given the flexibility to float the switch when required. The best noise immunity and emi...

  • Page 12

    5/17/2007 12 connecting the unit for the 100basefx fiber optic port, remove the dust cap(s) from the fiber optic connector and connect the fiber optic cables. The tx port on the local unit should be connected to the rx port of the far end device, and the rx port should be connected to the tx port of...

  • Page 13

    5/17/2007 13 fcc statement this product complies with part 15 of the fcc-a rules. Operation is subject to the following conditions: (1) this device may not cause harmful interference (2) this device must accept any interference received, including interference that may cause undesired operation. Not...

  • Page 14

    5/17/2007 14 regulatory approvals: safety: ul listed per ansi/isa-12.12.01-2000 (us and canada) this apparatus is suitable for use in class i, div 2, groups a, b, c, and d ul temperature ratings: 102mc/mce - t5 104tx, 105tx, and 108tx - t4a emi: en61000-6-4, en55011 - class a fcc title 47, part 15, ...

  • Page 15

    5/17/2007 15 102mc/mce - key specifications physical height: 2.90” (max.) width: 1.50” (max.) depth including din-rail clip: 4.82” (max.) weight: 0.60 lbs. Electrical input voltage: 10-30 vdc (regulated) input current: 1 40ma max. @ 24vdc (steady state) inrush current: 8.5amp/0.7 ms max. @ 24vdc inp...

  • Page 16

    5/17/2007 16 104tx/105tx - key specifications physical height: 2.9” (max.) width: 1.50” (max.) depth: 4.25” (max.) weight: 0.60 lbs. Electrical input voltage: 10-30 vdc (regulated) input current: 215 ma max. @ 24vdc (steady state) inrush current: 7.8 amp/0.7ms max. @ 24vdc input ripple: less than 10...

  • Page 17

    5/17/2007 17 108tx - key specifications physical height: 3.5” (8.89 cm) width: 1.50” (3.81 cm) depth including din rail clip: 4.22” (10.7 cm) weight: 0.64 lbs. (0.29 kg) din rail 35 mm electrical input voltage: 10-30 vdc (regulated) input current: 250 ma max. @ 24vdc (steady state) inrush current: 8...

  • Page 18

    5/17/2007 18 n-tron limited warranty n-tron, corp. Warrants to the end user that this hardware product will be free from defects in workmanship and materials, under normal use and service, for the applicable warranty period from the date of purchase from n-tron or its authorized reseller. If a produ...