    L:\product documentation\manuals\doc\mew00442.Doc operating instructions mew00442 revision - fire alarm system ebl512 v1.44.X author: jan pettersson date: 2003-09-09 rev. Date: checked by: mikael Östergren s-class: public rev. By: approved by: rutger pålsson number of pages: 111.

  • Page 2

    This page has deliberately been left blank..

  • Page 3: Table of Contents

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 1 table of contents 1 introduction________________________________ 5 2 definitions / explanations ____________________ 6 2.1 mfstech_________________________________________ 6 2.2 alarm poi...

  • Page 4

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 2 5 led indicators and push buttons _____________ 14 6 access levels_______________________________ 17 6.1 access level 1 ____________________________________ 17 6.2 access level 2 ________...

  • Page 5

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 3 17.2 control units in a tlon network ____________________ 48 17.2.1 tlon network programming (configuration) ______ 49 18 programming (ssd download) _______________ 50 18.1 single control...

  • Page 6

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 4 27.6 display current consumption in unit (h5/a5)____________ 86 27.7 display current consumption com-/bs4-loop (h5/a6) ___ 87 27.8 display statistics for com-loop (h5/a7)_______________ 8...

  • Page 7: 1 Introduction

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 5 1 introduction ebl512 operating instructions, is a document intended to be used by the end user and the fire brigade personnel as well as service / commissioning engineer. Due to continua...

  • Page 8: Definitions / Explanations

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 6 2 definitions / explanations definitions / explanations / abbreviations / etc. Frequently used or not explained elsewhere in the document. 2.1 mfstech matsushita electric works fire & sec...

  • Page 9: 2.3 Output

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 7 2.2.8 addressable a unit with a built-in address device, i.E. Each unit is individually identified, handled and indicated in the control unit. (the unit can consequently be an addressable...

  • Page 10: 2.9

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 8 2.9 control unit (c.U.) / c.I.E. Control unit = c.U. = control and indicating equipment = unit to which the alarm points are connected, e.G. Ebl512. Indicates fire alarm, fault condition,...

  • Page 11: 2.14 Led

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 9 router or repeater is the same type of unit (different configuration). All network programming (configuration) are made with the pc program "tlon manager". 2.14 led led (light emitting di...

  • Page 12: 3 Overview

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 10 3 overview 3.1 the ebl512 system ebl512 is a microprocessor controlled intelligent fire alarm system, intended for analog addressable smoke detectors, as well as conventional detectors a...

  • Page 13: 3.3 Documents

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 11 3.3 documents the following documents are available: • planning instructions (incl. Drawings) • operating instructions normally information that is found in one document is not to be fou...

  • Page 14: 4 Control

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 12 4 control unit figure 1. Ebl512 control unit (1548 / 1549). The look may vary according to configuration, country, etc. The control unit (c.I.E.) is housed in a grey metal cabinet. The d...

  • Page 15

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 13 address within the zone. On the second row is shown a user definable text message, if programmed. Required fire brigade personnel manoeuvres can be performed from the fbp. The cp is used...

  • Page 16

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 14 5 led indicators and push buttons leds and push buttons vary according to type and configuration (convention / country / language). Led indicators on the fire brigade panel (fbp) led ind...

  • Page 17

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 15 led indicators on the control panel (cp) led indicator indicating l8 fault (yellow) acknowledged fault(s) and/or acknowledged but not corrected fault(s). L9 test mode (yellow) one or mor...

  • Page 18

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 16 keypad/push buttons on the control panel (cp) key/push button operation/function 0 - 9 numeric keys for the figures 0-9. ← → ↑ ↓ left / right keys to move the cursor in a menu. Up / down...

  • Page 19: 6 Access

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 17 6 access levels the control unit has five access levels which are adapted to different kind of users. Access level 1 open door (key is needed) fire brigade personnel fire alarm handling ...

  • Page 20: 6.2

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 18 6.2 access level 2 from access level 1, the user can login to access level 2, which gives access to the following menus: h1 perform monthly test. H2 disable or re-enable. B1 disable zone...

  • Page 21: 6.3

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 19 6.3 access level 3 from access level 2 17 , the user can login to access level 3, which gives access to the following menus, normally used by service personnel: same menus as in access l...

  • Page 22: 6.4

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 20 6.4 access level 4 from access level 2 18 , the user can login to access level 4, which gives access to the following menus, normally used by a service / commissioning engineer: same men...

  • Page 23: 7 Normal

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 21 7 normal operation when the control unit / system is in normal operation, i.E. No fire alarm, no fault, no disablement, no service signal, not in test mode and no open doors, etc., only ...

  • Page 24: Push Button "silence"

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 22 8 push button "silence" in the control unit (on the fbp) there is a push button (p2) "silence" and an led (l7) "silence". In some configurations / conventions, this button could have spe...

  • Page 25

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 23 9 alarm device on / alarm device off via menu h2/b9, all outputs, programmed for sounders (type 3 = alarm devices), can be turned off (disabled). In case of a fire, the sounders will rem...

  • Page 26: Controls On / Controls Off

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 24 10 controls on / controls off via menu h2/b8, all control output types: 0 = control (general) 1 = fire ventilation 2 = extinguishing system 21 can be collective turned off (disabled). Th...

  • Page 27: Door Open (Key Switch)

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 25 11 door open (key switch) a key is used to open the control unit door to get access to the system, see chapter "access levels", page 17. Door open is indicated by led "key switch" (l16),...

  • Page 28: Number

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 26 12 technical number / presentation number 12.1 technical number for com loop units the technical number, nnnnnn, is used when programming all units connected to the com loops. Technical ...

  • Page 29: 12.2

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 27 12.2 technical number for bs4 loop units autronica interface board 1584 (four bs4 loops) is required in the control unit. The technical number, nnnnnn, is used when programming all units...

  • Page 30: 12.3 Presentation

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 28 12.3 presentation number for each fire alarm point / input, a presentation number, nnn-nn, has to be programmed. This number is shown in the fbp display(s) 23 , to identify the point / z...

  • Page 31: 13 Alarm

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 29 13 alarm types in case of a fire, sensors, conventional smoke and/or heat detectors, manual call points or programmable inputs can generate fire alarm. When somebody break into a key cab...

  • Page 32: 13.2 Fire

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 30 13.2 fire alarm a sensor generates fire alarm for an offset (level) that can normally not be changed 26 . In case of a fire alarm, the following will happen: • the buzzer in the control ...

  • Page 33: 13.3

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 31 note! Up to 120 fire alarms can be stored. In case of more alarms they will not be registered until one or more of the 120 alarms are reset. 13.2.1 alert annunciation indications, print-...

  • Page 34: 14 Key

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 32 14 key cabinet one of the programmable inputs i0-i3 35 in the control unit can be used to connect a key cabinet. The fire brigade uses a key cabinet to store a key for the building locks...

  • Page 35: 15 Alarm

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 33 15 alarm reset 15.1 pre-alarm reset pre-alarm is automatically reset (i.E. When the sensor value + offset for pre-alarm, is below the pre-alarm level). 15.2 fire alarm reset • the fire a...

  • Page 36: 15.4

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 34 15.4 key cabinet alarm reset key cabinet alarm is reset the same way as a fire alarm, see above. To inform the user that the key cabinet has been opened, a fault message is shown in the ...

  • Page 37: 16 Fault

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 35 16 fault in case of a fault condition, the following has happened / will happen in the control unit: • the buzzer in the control unit sounds (steady on). • output(s) for routing equipmen...

  • Page 38

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 36 two (or more) units, connected to a bs4 loop (1584 board), have been given the same address. Check the units. Fault: 1581 relay board x, cu xx (=1581, 8 relays expansion board) fault on ...

  • Page 39

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 37 fault: battery not connected cu xx also indicated by led "fault power supply". • batteries (2 x 12 v) are missing or not correctly connected. • fuse(es) f2, f3 on the charger board 1557 ...

  • Page 40

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 38 tlon network (tlon manager). Note! Programmed control units have to be connected / running. Fault: cu xx has wrong information control units have data stored, which is not the same in al...

  • Page 41

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 39 asf 3cu = between short circuit isolator number 3 and the control unit). Each 10 minutes an attempt is made to comm. In one direction again. Fault:cut-off loop x, det8-board x,cu xx (det...

  • Page 42

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 40 also indicated by led "fault power supply". The fault is to be found in the external power supply (blown fuses, etc.). Fault: fuse bs4-board x, cu xx (bs4=1584, autronica interface board...

  • Page 43

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 41 or zone interface 2226: no ext. Power supply. Fault: key box, control unit: xx the key cabinet has been opened without a prior fire alarm (i.E. A break into the cabinet). Or the key cabi...

  • Page 44

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 42 x=2 (s2): short circuit/break on the connected cable/ equipment x=3 (s3): short circuit/break on the connected cable/ equipment • connected equipment may be "stolen". • resistor(s) missi...

  • Page 45

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 43 fault: restart cu nn code xx yyyyyyyyyy control unit restart (reset) has occurred. Nn: control unit number (00-29) xx=00: power on reset. (power supply connected) xx=01: watchdog reset. ...

  • Page 46

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 44 circuit isolators 2370, asf, are connected on the loop). Check the specified and isolated segment on the loop (e.G. Cu asf0 = between the control unit and short circuit isolator number 0...

  • Page 47

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 45 fault: supply for external fbp cu xx also indicated by led "fault power supply". Check the fuses f2 and f4 on the connection board 1555. (monitored output s2 is also supplied via f2 and ...

  • Page 48

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 46 fault: wrong type of unit no. Xxxxxx the output unit is not the same type as programmed. Change the programming or the output unit. High current loop x, bs4-board x, cu xx (bs4=1584, aut...

  • Page 49: 16.2 Fault

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 47 16.2 fault acknowledge the leds "fault tx" and "fault" are lit. A fault message, date and time are shown in the fbp display(s). After the time may be shown more faults = more than one fa...

  • Page 50: 17.1

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 48 17 commissioning an installation before you connect the power supply to a control unit, all other cable connections should be made. Check once more that they are correct. 17.1 single con...

  • Page 51

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 49 specific data (ssd) can be downloaded, see chapter "programming (ssd download)", page 50. 17.2.1 tlon network programming (configuration) a pc is connected to the modular connector j2 in...

  • Page 52: 18 Programming

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 50 18 programming (ssd download) the pc program win512 is used for programming (download) of the site specific data (ssd). When the control units is running (power supplied) and when requir...

  • Page 53: 18.3

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 51 18.3 user definable text messages download when a fire alarm (an addressable alarm point) is activated, the presentation number (zone & address) will be shown on the first row in the con...

  • Page 54: Download

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 52 19 new system program (sw) version download sw download is normally factory made before delivery. Latest sw version is then downloaded. Due to continual development and improvement, diff...

  • Page 55: Ebl512 Settings Download

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 53 20 ebl512 settings download ebl512 settings are normally factory made before delivery. On site, it is possible to download the following: • the number of addresses (max. Loop units) 44 •...

  • Page 56: 20.1

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 54 20.1 control units in a tlon network all control units connected to a tlon network should have the same convention. The number of addresses could vary and the language if required. For d...

  • Page 57: Reset / Restart

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 55 21 reset / restart reset/restart 46 will reset/delete all activated fire alarms, faults and disablements (ffd). When required, make notes of the disablements before reset/restart, so tha...

  • Page 58

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 56 note! By reset/restart, the fault tx output(s) will be "activated". The "restart" will last for up to 2 minutes. During this 2 min. Period no fire alarm can be activated. A fault is gene...

  • Page 59: 22 Access

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 57 22 access to be able to use the key pad in the control unit (to get access to the menu tree), it is necessary to login with an access code for level 2 ,3 or 4. See also chapter "access l...

  • Page 60: Perform Monthly Test (H1)

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 58 23 perform monthly test (h1) the control unit and the installation should be tested on a regular basis. If one twelfth of the alarm points are tested each month, the whole installation w...

  • Page 61

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 59 perform the tests as quickly as possible, since the output for routing equipment (fire brigade tx) is disabled (also the parts of the zones in test mode, not visible for the test personn...

  • Page 62: Disable Or Re-Enable (H2)

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 60 24 disable or re-enable (h2) a whole zone, one or more alarm points within a zone and/or control outputs can be disabled via menus h2/b1-b3. This possibility can be used when a temporary...

  • Page 63: 24.1 Disable

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 61 24.1 disable zone (h2/b1) when a whole zone is disabled, all alarm points within the zone are disabled (excl. Addressable manual call points). Disabled zones are listed in menu h4/u1. Fr...

  • Page 64: 24.2

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 62 24.2 disable zone / address (h2/b2) every addressable alarm point connected to the com loop can be individually disabled. Disabled alarm points, zone / addresses, are listed in menu h4/u...

  • Page 65: 24.3

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 63 24.3 disable control output (h2/b3) every control output can be individually disabled. Disabled outputs are listed in menu h4/u1. From this menu, it's also possible to get a print-out. A...

  • Page 66: 24.4

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 64 24.4 re-enable zone (h2/b4) disabled zones are listed in menu h4/u1. From this menu, it's also possible to get a print-out. Re-enabling via this menu, has higher priority than automatic ...

  • Page 67: 24.5

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 65 24.5 re-enable zone / address (h2/b5) disabled alarm points, zone / addresses, are listed in menu h4/u1. From this menu, it's also possible to get a print-out. Re-enabling via this menu,...

  • Page 68: 24.6

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 66 24.6 re-enable control output (h2/b6) disabled outputs are listed in menu h4/u1. From this menu, it's also possible to get a print-out. When all control outputs have been re-enabled, the...

  • Page 69: 24.7

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 67 24.7 re-enable non-reset zone / address (h2/b7) this function is normally only used in the swedish configuration (convention = rus in win512). One or more alarm points have been reset wh...

  • Page 70: 24.8

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 68 24.8 control on / control off (h2/b8) outputs programmed as type 0 = control (general), type 1 = fire ventilation and/or type 2 = extinguishing system 50 can be disabled all at the same ...

  • Page 71: 24.9

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 69 24.9 alarm device on / alarm device off (h2/b9) outputs programmed as type 3 = alarm device (sounder) can be disabled all at the same time. Alarm device off means that even if the contro...

  • Page 72: Set Calendar and Clock (H3)

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 70 25 set calendar and clock (h3) the rtc component has a built-in battery. Normally, date, day of the week and time don't have to be set, except when the control unit is powered for the fi...

  • Page 73: And Printer (H4)

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 71 26 present system status on display and printer (h4) printer is factory mounted in control unit 1549. Printer 1558 is an option for control unit 1548. 26.1 disablement (h4/u1) a list of ...

  • Page 74: 26.2

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 72 26.2 disablement by time channel (h4/u2) a list of all disablements by time channel(s) in the system. From this menu, it's also possible to get a print-out. Action text in display commen...

  • Page 75: 26.3

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 73 26.3 show open doors (h4/u3) the led "key switch" (l16) is lit, to indicate that one or more doors are open. See chapter "door open (key switch)", page 25. Menu h4/u3 is a list of all op...

  • Page 76: 26.4

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 74 26.4 activated 2-zone/address dependent (h4/u4) 2-zone dependency (win512, dialog box "system"): when only one zone is in alarm status, the leds "fire" (l1) are flashing but there is no ...

  • Page 77: 26.5

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 75 26.5 show sensors week average values (h4/u5) each sensor's week average sensor value can be listed. 53 it is not possible to get a print-out. 26.5.1 reset of a sensor week average value...

  • Page 78: 26.6

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 76 26.6 show sensors momentary values (h4/u6) each sensor's actual sensor value can be listed: via display: see alternative "a" below. Via a print-out: see alternative "1" below. Action tex...

  • Page 79: 26.7

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 77 26.7 sensors activating service signal (h4/u7) a sensor's week average value is below or over the service level resp. For this type of sensor. Service signal is indicated by led "service...

  • Page 80: 26.8

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 78 26.8 show event log (h4/u8) this is a list of events. Types 54 , number of events in the list, etc. Can be programmed. From this menu, it's also possible to get a print-out. Each event c...

  • Page 81: 26.9

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 79 26.9 show configuration (h4/u9) in menu h4/u9, the ebl512 settings (made in win512)are shown: - number of addresses that can be used (128, 256 or 512) - convention (i.E. Different functi...

  • Page 82: 27 Programming

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 80 27 programming (h5) when commissioning an installation (power on and programming a control unit / a system), menu h5 is used to get certain information and help. Only authorised personne...

  • Page 83: 27.1

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 81 27.1 access code for programming (h5) when commissioning an installation you have to be authorised (access code to level 4). If login to level 2 was made with code for level 4, no code i...

  • Page 84: 27.2

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 82 27.2 calibration of monitored outputs (h5/a1) the voltage outputs (s0-s3) in each control unit are monitored (supervised), as well as the outputs (0-3) in each output unit type 2262 and ...

  • Page 85: 27.3

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 83 27.3 sensitive fault detection mode (h5/a2) to increase the possibilities to detect faults during the commissioning, it is possible to use the "sensitive fault detection mode. (the time ...

  • Page 86: 27.4

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 84 27.4 direction for communication on com-loop (h5/a3) to make trouble shooting easier (e.G. During the commissioning) it is possible to lock the communication on a com or bs4 loop in one ...

  • Page 87: 27.5

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 85 27.5 show information about site specific data (h5/a4) the site specific data (ssd) is downloaded via a pc and win512. Action text in display comments "access" according to chapter "acce...

  • Page 88: 27.6

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 86 27.6 display current consumption in unit (h5/a5) system shows the total current consumption (including the charging current on the 24v side) for the whole control unit. Charging shows th...

  • Page 89: 27.7 Display

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 87 27.7 display current consumption com-/bs4- loop (h5/a6) the current consumption (an average value) for each com loop and bs4 loop 58 can be displayed. Note! No or very small current cons...

  • Page 90: 27.8

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 88 27.8 display statistics for com-loop (h5/a7) pollings are the number of pollings ("questions") sent out to the units on the com-loop, by the control unit. Parity are received parity faul...

  • Page 91: 27.9

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 89 27.9 select unit on com-loop to use for triggering (h5/a8) this function is used by service engineer and by r&d for troubleshooting. On the pin respectively you will get a pulse to trig ...

  • Page 92: 27.10

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 90 27.10 change access code for pc- communication (h5/a9) as a protection against unauthorised personnel programming the system, an access code (level 5) for pc-connection (win512) is requi...

  • Page 93: 27.11

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 91 27.11 change access code for programming (h5/a10) for security reasons, the default code should be changed. Action text in display comments "access" according to chapter "access code for...

  • Page 94: Acknowledge Faults (H6)

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 92 28 acknowledge faults (h6) leds "fault tx" (l19) and "fault" (l8) are lit and resp. Outputs are activated. There is a fault message shown in the fbp display(s). More than one fault is in...

  • Page 95: (H7)

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 93 29 perform zone test (test mode) (h7) normally, zones are tested during the monthly test (menu h1). Via this menu it's possible to perform the zone test only. In test mode, only the alar...

  • Page 96

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 94 note! If the control unit door is left open, the output(s) for routing equipment (fire brigade tx) may be disabled (if programmed so in win512). A sensor in test mode will not be able to...

  • Page 97: 30 Maintenance

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 95 30 maintenance (h8) 30.1 access code for maintenance access code for access level 3 is required for menu h8. Note! If login to level 2 was made with code for level 3 or 4, no code to acc...

  • Page 98: 30.2 Disable

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 96 30.2 disable or re-enable outputs for routing equipment (h8/s1) outputs for routing equipment (fire brigade tx / fault tx) can be disabled via this menu. They stay disabled, until re-ena...

  • Page 99: 30.3

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 97 30.3 disconnect com-loop (h8/s2) before physical connection / disconnection of loop units, etc. To a loop or zone line, the "loop" should be disconnected (disabled), i.E. No voltage on t...

  • Page 100: 30.4

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 98 30.4 re-connect loop (h8/s3) disconnected (disabled) loops / zone lines are indicated by led "disabled" and listed in menu h4/u1. Bs4 loop require an autronica interface board 1584 in th...

  • Page 101: 30.5

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 99 30.5 acknowledge service signal (h8/s4) see chapter "sensors activating service signal (h4/u7)", page 77. When service signal from a sensor is acknowledged, the sensor is given a default...

  • Page 102: 30.6

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 100 30.6 safe shut down of control unit (h8/s5) it's not recommended, to power off a control unit, without doing a safe shut down. This is because data can get lost. Safe shut down also put...

  • Page 103: 30.7

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 101 30.7 activate address in alarm mode (h8/s6) one or more alarm points (addresses), can be set in alarm status. (fictitious zone-addresses can not be used and address "00" can only be use...

  • Page 104: 30.8

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 102 30.8 synchronize the control units (h8/s7) the control units have to be synchronized when: • the following fault message is shown: fault: cu xx has wrong information 60 • after "status ...

  • Page 105: 30.9

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 103 30.9 change access code for maintenance (h8/s8) for security reasons, the default code should be changed. Action text in display comments "access" according to chapter "access code for ...

  • Page 106: Change Access Code For Daily

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 104 31 change access code for daily duties (h9) for security reasons, the default code should be changed. Action text in display comments "access" according to chapter "access", see page 57...

  • Page 107: 32 Annual

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 105 32 annual control the building occupier is highly recommended, once a year, to do some tests, beside the monthly tests. To avoid the fault tx output(s) to be activated, they can be disa...

  • Page 108

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 106 33 changing paper in the printer when the paper roll is almost empty, a red line appears on one edge of the paper. Change the paper roll before it's completely empty! Always have a spar...

  • Page 109: 34 Battery

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 107 34 battery maintenance the batteries (2 x 12 v, 24 ah) are normally placed in the control unit. The control unit supervises the batteries and a fault will be activated if something goes...

  • Page 110: How to Avoid Unnecessary

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 108 35 how to avoid unnecessary (nuisance) fire alarms we all realise, when life, buildings, production facilities, etc. Shall be saved, it is of utmost importance that an initial fire is d...

  • Page 111

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 109 exhausts exhausts from cars / trucks, lift trucks, lawn mowers, etc. Influences smoke detectors (sensors). If windows and doors are open, exhausts can "slip in" that way. Lack of mainte...

  • Page 112: Radiation Source

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 110 36 information regarding radioactive radiation source the installation might contain smoke sensors / detectors of the ionization type. They contain a small radioactive radiation source,...

  • Page 113: 37 Revision

    Matsushita electric works fire & security technology ab mew00442 rev: - operating instructions ebl512, v1.44.X 111 37 revision history revision -.

  • Page 114

    This page has deliberately been left blank..

  • Page 115

    This page has deliberately been left blank..

  • Page 116