Door Contact
Electric
Door Strike
Door Lock
Power Supply
RS422 to Panels
Continental
Instruments llc
Request to Exit
Motion Detector
Door Contact
Card Reader
Request
to Exit
Bu
Door Lock
A or B
G
D
G
G
G
Request
to Exit
G
H
G
NOTE: Request to Exit motion detectors will require
an additional 12VDC power cable. Exit devices are
typically mounted on the egress side of door.
CardAccess 3000
Database and
Communications
Server
CICE1940PL-1
Polling Line Converter
RS232 to RS422
Required if server is not located
within 50
RS422 Repeat Mode Communications Network
4000' max. distance between controllers.
Up to 63 controllers on a Repeat Mode Network.
perterm
Sup
p
perterm
Sup
p
RS422
x. 4000'
RS422
Max. 4000'
RS422
Max. 4000'
RS422
Max. 4000'
RS422
Max. 4000'
RS232
Max. 50'
niterm
Mii
marterm
Sm
m
C
CICP1400 Four Door Intelligent Controller
Continental Instrument’s Controllers can connect to the
CardAccess Server via hardwire (shown below), LAN/WAN
dial-up modem or fiber optics. See the CIC Configuration
Guide for additional detailed system information.
Smarterm Components
QTY.
Part No.
Description
1
CICP1400
Four (4) reader controller with stan-
dard 2,500 card capacity, 16 alarm
inputs, tamper alarm, and 9 relay
outputs. Unit ships complete in a
locking steel enclosure including
standby battery for memory and
system operation.
1
Standard
115VAC Power Supply (230VAC
optional). 10’ power line cable with
110VAC plug is included.
1
Standard
7AH Battery Backup included.
1 Optional* CICP1400MB256-1
Memory Board - 256K (up to 14,000
cardholders or for supporting
elevator control).
1 Optional* CICP1400MB2-1
Memory Board - 2MB (up to 120,000
cardholders and elevator control).
Up to 4
Optional**
CICP1400RB
Relay Expander Board - 16 output
relays, 8 alarm inputs (Unsupervised).
Up to 4
Optional**
CICP1400RB
Alarm Expander Board - 16 alarm
inputs (Supervised). UL Listed.
NOTE: * Either a 256K or 2MB Memory board may be added to the Smar-
term unit in order to increase cardholder and/or transaction memory. **A
maximum of 4 Expansion Boards in any combination may be added to the
Smarterm enclosure.
A433A