Narada ACMEG AG12V100A Operation Manual

Manual is about: front access design

Summary of ACMEG AG12V100A

  • Page 1

    Polymer gel standby battery (front access design) operation manual version 3.2 narada power source co., ltd website: www.Naradapower.Com.

  • Page 2: Contents

    Operation manual v3.2 for acmeg series - 2 - contents important safety instructions ....................................................................................................... - 3 - chapter one product introduction ............................................................................

  • Page 3

    Operation manual v3.2 for acmeg series - 3 - important safety instructions please read this operation manual carefully. It offers very important safety instructions, installation and operation guide, and ensure your equipment with best performance and prolong the service life of your equipment. · fo...

  • Page 4: Chapter One

    Operation manual v3.2 for acmeg series - 4 - chapter one product introduction 1. Features 1.1 long life  using the polymer gel electrolyte  4bs paste technology  special paste technology  special patent grid alloy 1.2 wide operational temperature range  excellent charging and discharging abilit...

  • Page 5

    Operation manual v3.2 for acmeg series - 5 - ag12v100f 12 100 390 105 287 33.0 ag12v100a 12 100 390 105 287 33.0 ag12v100s 12 100 395 108 287 31.0 ag12v125f 12 125 558 125 270 46.0 ag12v150s 12 150 550 125 283 48.0 ag12v155f 12 155 558 125 270 52.5 ag12v170s 12 170 550 125 283 51.5 ag12v180 12 180 5...

  • Page 6

    Operation manual v3.2 for acmeg series - 6 - ag12v180, ag12v190, ag12v200 ag12v100s ag12v150s, ag12v170s ag12v190s 558 [21.99] 3 1 6 [ 1 2 .4 5 ] 125 [4.93].

  • Page 7: Chapter Two

    Operation manual v3.2 for acmeg series - 7 - 5. Terminals sketch map chapter two technical characteristics 1. Charge performance curve fig 2-1 battery voltage vs discharge time curves at different current at 25º c. 2. Internal resistance and short circuit current the internal resistance of the batte...

  • Page 8

    Operation manual v3.2 for acmeg series - 8 - table 2-1. Internal resistance and short circuit current (25º c) type internal resistance (mΩ) short circuit current (a) ag12v50f 8.94 1500 ag12v85f 6.52 1897 ag12v100f 6.36 1989 ag12v100s 5.52 2318 ag12v100a 6.59 1909 ag12v125f 5.76 2226 ag12v150s 5.19 2...

  • Page 9

    3. Discharge data with constant current & constant power tab.2-1 discharge data with constant current (a, 25℃) ag12v50f 5min 15min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 12h 20h 24h 1.60v/cell 187.0 100.5 61.1 44.2 35.7 20.5 14.9 11.7 9.86 8.46 6.49 5.30 4.53 2.84 2.37 1.67v/cell 175.6 96.9 60.1 43.8 ...

  • Page 10

    Operation manual v 3.2 for acmeg series - 10 - 1.70v/ cell 334.7 183.3 113.5 83.7 67.8 38.9 27.9 22.2 18.6 16.0 12.4 10.19 8.61 5.40 4.51 1.75v/ cell 307.8 177.3 112.5 83.1 66.8 37.9 27.6 21.9 18.5 15.9 12.3 10.09 8.61 5.39 4.51 1.80v/ cell 275.9 165.3 107.6 79.7 65.1 37.6 27.4 21.8 18.1 15.6 12.2 1...

  • Page 11

    Operation manual v 3.2 for acmeg series - 11 - ag12v180 5min 15min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 12h 20h 24h 1.60v/ cell 506.5 317.6 209.0 153.8 125.6 72.8 51.6 40.7 34.6 29.2 23.1 18.6 16.0 9.90 8.30 1.67v/ cell 474.4 312.6 206.0 153.8 124.6 72.1 51.4 40.7 34.4 28.9 22.9 18.5 15.9 9.80 8.23 ...

  • Page 12

    Operation manual v 3.2 for acmeg series - 12 - tab 2-3 discharge data with constant power (watts/cell, 25℃) ag12v50f 5min 15min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 12h 20h 24h 1.60v/cell 313.5 177.0 110.5 83.0 67.5 38.6 28.2 22.3 18.8 16.2 12.6 10.3 8.69 5.58 4.66 1.67v/cell 301.5 173.9 109.5 82.5 ...

  • Page 13

    Operation manual v 3.2 for acmeg series - 13 - 1.80v/ cell 494.0 310.4 204.6 154.7 125.9 73.4 53.0 42.8 35.3 30.6 23.7 19.58 16.58 10.69 8.97 1.83v/ cell 472.1 284.4 202.6 149.7 120.9 72.5 51.7 41.2 34.5 29.7 23.5 19.08 16.08 10.69 8.91 1.85v/ cell 441.1 277.4 187.6 143.7 116.9 70.1 50.3 40.7 33.7 2...

  • Page 14

    Operation manual v 3.2 for acmeg series - 14 - 1.67v 835.2 570.8 372.9 299.5 255.3 151.8 107.5 83.6 70.4 59.9 46.0 39.5 34.2 20.8 17.4 1.70v 805.0 559.8 370.8 298.5 254.3 150.8 106.5 83.4 70.0 59.8 45.9 39.5 34.1 20.7 17.4 1.75v 743.7 538.7 363.8 294.5 250.2 149.7 106.5 82.9 69.6 59.5 45.6 39.4 34.0...

  • Page 15: Chapter Three

    Chapter three operation and maintenance 1. Operation conditions ambient temperature: acmeg series optimum temperature is 15℃~25℃, the higher and lower temperatures will impact battery performance operation temperature range operate status temperature range optimum temperature discharge -40℃~50℃ 15℃~...

  • Page 16

    Operation manual v 3.2 for acmeg series - 16 - in time. This will shorten the life of the battery. Table 3-1 discharge end voltage at different current discharge current (a) discharge end voltage (v/block) i<0.2c 10.8 0.2c≤i<0.5c 10.2 0.5c≤i<1.0c 9.30 i≥1.0c 7.80 3. Ambient temperature, capacity and...

  • Page 17

    Operation manual v 3.2 for acmeg series - 17 - the capacity of the battery will increase when the temperature rises. For example, the capacity will increase by 6% when the temperature increases by 10º c. However the high temperature will accelerate the corrosion of the grid and cause water loss in t...

  • Page 18

    Operation manual v 3.2 for acmeg series - 18 - 3.3 equalization charge vrla battery needs equalization charge regularly to ensure the battery operating under 25º c working condition. The equalization voltage of narada acmeg series battery is 14.4v/block. The temperature compensation is at -30mv/º c/...

  • Page 19

    Operation manual v 3.2 for acmeg series - 19 - 4. Charging request 4.1 equalization charging equalization charging should be carried out in the following situation: a. There are more than two batteries which voltage is under 13.0v in one group. B. More than three months after floating operation. Equ...

  • Page 20

    Operation manual v 3.2 for acmeg series - 20 - following during storage period: 5.1 the self-discharge rate is related to the ambient temperature. The degree of self-discharge is smaller when the ambient temperature is lower, otherwise it will be larger. The required temperature for narada batteries...

  • Page 21: Chapter Four

    Operation manual v 3.2 for acmeg series - 21 - chapter four maintenance 1. Regulated maintenance 1.1 instruments and tools: 1.1.1 digital voltage meter. 1.1.2 insulated wrench. 1.1.3 internal resistance, conductive and instant loading experiment instruments. 1.2 monthly maintenance — keep the batter...

  • Page 22

    Operation manual v 3.2 for acmeg series - 22 - if the floating voltage is not set correctly i.E. Too low or not amend according to the temperature, the battery system will have an insufficient charge state for a long period of time. When the electricity is cut, the battery may not be able to work be...

  • Page 23

    Operation manual v 3.2 for acmeg series - 23 - annex 1 vrla battery regular maintenance record type place status number of battery total voltage(v) current (a) temperature no. Voltage(v) no. Voltage(v) 1 13 2 14 3 15 4 16 5 17 6 18 7 19 8 20 9 21 10 22 11 23 12 24 check by sight result: tester: date...

  • Page 24