National Instruments CompactRIO cRIO-9263 Operating Instructions Manual

Manual is about: 4-Channel, ±10 V, 16-Bit Analog Voltage Output Module

Summary of CompactRIO cRIO-9263

  • Page 1

    Operating instructions compactrio crio-9263 4-channel, ± 10 v, 16-bit analog voltage output module ™.

  • Page 2

    Crio-9263 operating instructions 2 ni.Com these operating instructions describe how to use the national instruments crio-9263 module. For information about installing, configuring, and programming the compactrio system, refer to the compactrio bookshelf at start»program files»national instruments»co...

  • Page 3

    © national instruments corp. 3 crio-9263 operating instructions caution do not disconnect i/o-side wires or connectors unless power has been switched off or the area is known to be nonhazardous. Caution do not remove modules unless power has been switched off or the area is known to be nonhazardous....

  • Page 4

    Crio-9263 operating instructions 4 ni.Com safety guidelines for hazardous voltages if hazardous voltages are connected to the module, take the following precautions. A hazardous voltage is a voltage greater than 42.4 v peak or 60 vdc to earth ground. Caution ensure that hazardous voltage wiring is p...

  • Page 5

    © national instruments corp. 5 crio-9263 operating instructions wiring the crio-9263 the crio-9263 has a 10-terminal, detachable screw-terminal connector that provides connections for four analog output channels. Each channel has a terminal to which you can connect the positive lead of a voltage sig...

  • Page 6

    Crio-9263 operating instructions 6 ni.Com table 1. Terminal assignments module terminal signal 0 ao0 1 common (com) 2 ao1 3 common (com) 4 ao2 5 common (com) 6 ao3 7 common (com) 8 no connection 9 common (com) 0 1 2 3 4 5 6 7 8 9.

  • Page 7

    © national instruments corp. 7 crio-9263 operating instructions connecting a load to the crio-9263 you can connect loads to the crio-9263. Connect the positive lead of the load to the ao terminal. Connect the ground of the load to a com terminal. Figure 1. Connecting a load to the crio-9263 crio-926...

  • Page 8

    Crio-9263 operating instructions 8 ni.Com each channel also has overvoltage and short-circuit protection. For more information about the overvoltage and short-circuit protection, refer to the specifications section. Figure 2. Output circuitry for one channel when the module powers on, the output cha...

  • Page 9

    © national instruments corp. 9 crio-9263 operating instructions sleep mode you can enable sleep mode for the compactrio system in software. Typically, when a system is in sleep mode, you cannot communicate with the modules. In sleep mode, the system minimizes power consumption. The system thermal di...

  • Page 10

    Crio-9263 operating instructions 10 ni.Com operating voltage nominal ......................................± 10.7 v minimum ....................................± 10.3 v maximum ...................................± 11 v current drive .....................................± 1 ma per channel min output ...

  • Page 11

    © national instruments corp. 11 crio-9263 operating instructions protection overvoltage ................................± 30 v short-circuit................................ Indefinitely power-on voltage .............................. 0 v update time reconfigurable embedded chassis one channel .........

  • Page 12

    Crio-9263 operating instructions 12 ni.Com noise ................................................. 260 µ v rms slew rate ........................................... 4 v/ µ s crosstalk ........................................... 76 db settling time (100 pf load, to 1 lsb) fs step .......................

  • Page 13

    © national instruments corp. 13 crio-9263 operating instructions mtbf ............................................... 1,732,619 hours at 25 °c; bellcore issue 6, method 1, case 3, limited part stress method note contact ni for bellcore mtbf specifications at other temperatures or for mil-hdbk-217f s...

  • Page 14

    Crio-9263 operating instructions 14 ni.Com physical characteristics if you need to clean the module, wipe it with a dry towel. Screw-terminal wiring ...................... 12 to 24 awg copper conductor wire with 10 mm (0.39 in.) of insulation stripped from the end torque for screw terminals ...........

  • Page 15

    © national instruments corp. 15 crio-9263 operating instructions limited-energy parts of equipment, circuits powered by regulated low-voltage sources, and electronics. Isolation channel-to-channel .................... No isolation between channels channel-to-earth ground withstand .....................

  • Page 16

    Crio-9263 operating instructions 16 ni.Com safety standards the crio-9263 is designed to meet the requirements of the following standards of safety for electrical equipment for measurement, control, and laboratory use: • en 61010-1, iec 61010-1 • ul 3111-1, ul 61010b-1 • can/csa c22.2 no. 1010.1 not...

  • Page 17

    © national instruments corp. 17 crio-9263 operating instructions hazardous locations u.S. (ul) .......................................... Class i, division 2, groups a, b, c, d, t4; class i, zone 2, aex nc iic t4 canada (c-ul) ................................. Class i, division 2, groups a, b, c, d,...

  • Page 18

    Crio-9263 operating instructions 18 ni.Com storage humidity .............................. 5 to 95% rh, noncondensing maximum altitude ............................ 2,000 m pollution degree (iec 60664) .......... 2 shock and vibration to meet these specifications, you must panel mount the compactrio ...

  • Page 19

    © national instruments corp. 19 crio-9263 operating instructions electromagnetic compatibility emissions.......................................... En 55011 class a at 10 m fcc part 15a above 1 ghz immunity........................................... Industrial levels per en 61326-1:1997 + a2:2001, ta...

  • Page 20

    Crio-9263 operating instructions 20 ni.Com ce compliance this product meets the essential requirements of applicable european directives, as amended for ce marking, as follows: low-voltage directive (safety)......... 73/23/eec electromagnetic compatibility directive (emc) ..............................

  • Page 21

    © national instruments corp. 21 crio-9263 operating instructions national instruments contact information national instruments corporate headquarters is located at 11500 north mopac expressway, austin, texas, 78759-3504. National instruments also has offices located around the world to help address ...

  • Page 22

    Crio-9263 operating instructions 22 ni.Com poland 48 22 3390150, portugal 351 210 311 210, russia 7 095 783 68 51, singapore 65 6226 5886, slovenia 386 3 425 4200, south africa 27 0 11 805 8197, spain 34 91 640 0085, sweden 46 0 8 587 895 00, switzerland 41 56 200 51 51, taiwan 886 2 2528 7227, thai...

  • Page 23

    © 2004 national instruments corp. All rights reserved. 373781a-01 apr04 *373781a-01* compactrio™, national instruments™, ni™, and ni.Com™ are trademarks of national instruments corporation. Product and company names mentioned herein are trademarks or trade names of their respective companies. For pa...