National Instruments Network Adapter NI PXIe-1075 User Manual - Connecting to Power Source
Chapter 2
Installation and Configuration
2-6
ni.com
If your power outlet does not have an appropriate ground connection, you
must connect the premise safety ground to the chassis grounding screw
located on the rear panel. Refer to Figure 1-2,
, to locate the chassis grounding screw. To connect
the safety ground, complete the following steps:
1.
Connect a 16 AWG (1.3 mm) wire to the chassis grounding screw
using a grounding lug. The wire must have green insulation with a
yellow stripe or must be noninsulated (bare).
2.
Attach the opposite end of the wire to permanent earth ground using
toothed washers or a toothed lug.
Connecting to Power Source
Caution
Do
not
install modules prior to performing the following power-on test.
To completely remove power, you
must
disconnect the AC power cable.
Attach input power through the rear AC inlet using the appropriate
AC power cable supplied. Refer to Figure 1-2,
, to locate the AC inlet.
The Inhibit Mode switch allows you to power on the chassis or place it in
standby mode. Set the Inhibit Mode switch on the back of the chassis to the
Manual
position. Observe that all fans become operational and the power
switch LED is a steady green. Switching the Inhibit Mode switch to the
Default
position allows the system controller to control the power supply.
Installing a PXI Express System Controller
This section contains general installation instructions for installing a
PXI Express system controller in a NI PXIe-1075 chassis. Refer to your
PXI Express system controller user manual for specific instructions and
warnings. To install a system controller, complete the following steps:
1.
Inspect the slot 1 pins on the chassis backplane for any bending or
damage prior to installation.
2.
Connect the AC power source to the PXI Express chassis before
installing the system controller. The AC power cord grounds the
chassis and protects it from electrical damage while you install the
system controller.
Summary of Network Adapter NI PXIe-1075
Page 1
Pxi express ni pxie-1075 user manual ni pxie-1075 user manual july 2008 372537a-01.
Page 2
Support worldwide technical support and product information ni.Com national instruments corporate headquarters 11500 north mopac expressway austin, texas 78759-3504 usa tel: 512 683 0100 worldwide offices australia 1800 300 800, austria 43 662 457990-0, belgium 32 (0) 2 757 0020, brazil 55 11 3262 3...
Page 3: Important Information
Important information warranty the ni pxie-1075 is warranted against defects in materials and workmanship for a period of one year from the date of shipment, as evidenced by receipts or other documentation. National instruments will, at its option, repair or replace equipment that proves to be defec...
Page 4: Contents
© national instruments corporation v ni pxie-1075 user manual contents about this manual conventions ...................................................................................................................Vii related documentation..............................................................
Page 5
Contents ni pxie-1075 user manual vi ni.Com installing peripheral modules........................................................................................ 2-9 power inhibit switch led indicator ............................................................................. 2-10 remote voltage m...
Page 6: About This Manual
© national instruments corporation vii ni pxie-1075 user manual about this manual the ni pxie-1075 user manual describes the features of the ni pxie-1075 chassis and contains information about configuring the chassis, installing the modules, and operating the chassis. Conventions the following conve...
Page 7: Related Documentation
About this manual ni pxie-1075 user manual viii ni.Com related documentation the following documents contain information that you might find helpful as you read this manual: • ieee 1101.1-1991, ieee standard for mechanical core specifications for microcomputers using iec 603-2 connectors • ieee 1101...
Page 8: Getting Started
© national instruments corporation 1-1 ni pxie-1075 user manual 1 getting started this chapter describes the key features of the ni pxie-1075 chassis and lists the kit contents and optional equipment you can order from national instruments. Unpacking carefully inspect the shipping container and the ...
Page 9: Key Features
Chapter 1 getting started ni pxie-1075 user manual 1-2 ni.Com for 100–120 vac installation, use the ni cable part numbers listed in table 1-2, which are rated for 125 v/15 a. Note ni pxi-1075 chassis ordered in north america or japan ship with the proper cables by default. If you are missing any of ...
Page 10
Chapter 1 getting started © national instruments corporation 1-3 ni pxie-1075 user manual the key features of the ni pxie-1075 chassis include the following: high performance for instrumentation requirements • up to 1 gb/s (single direction) per pxi express slot dedicated bandwidth (x4 pcie) • 38 w ...
Page 11: Chassis Description
Chapter 1 getting started ni pxie-1075 user manual 1-4 ni.Com chassis description figures 1-1 and 1-2 show the key features of the ni pxie-1075 chassis front and back panels. Figure 1-1 shows the front view of the ni pxie-1075. Figure 1-2 shows the rear view of the ni pxie-1075. Figure 1-1. Front vi...
Page 12: Optional Equipment
Chapter 1 getting started © national instruments corporation 1-5 ni pxie-1075 user manual figure 1-2. Rear view of the ni pxie-1075 chassis optional equipment contact national instruments to order the following options for the ni pxie-1075 chassis. Emc filler panels optional emc filler panel kits ar...
Page 13
Chapter 1 getting started ni pxie-1075 user manual 1-6 ni.Com slot blockers optional slot blocker kits are available from national instruments for improved thermal performance when all slots are not used. Ni pxie-1075 chassis backplane overview this section provides an overview of the backplane feat...
Page 14
Chapter 1 getting started © national instruments corporation 1-7 ni pxie-1075 user manual system controller slot the system controller slot is slot 1 of the chassis and is a 4-link configuration system slot as defined by the compactpci express and pxi express specifications. It has three system cont...
Page 15
Chapter 1 getting started ni pxie-1075 user manual 1-8 ni.Com pxi express peripheral slots there are eight (8) pxi express peripheral slots: slots 6–9 and 11–14 (=8 slots). Pxi express peripheral slots can accept the following modules: • a pxi express peripheral with x4 or x1 pci express link to the...
Page 16
Chapter 1 getting started © national instruments corporation 1-9 ni pxie-1075 user manual figure 1-4. Pxie_dstar and pxi star connectivity diagram pxi local bus the pxi backplane local bus is a daisy-chained bus that connects each peripheral slot with adjacent peripheral slots to the left and right....
Page 17
Chapter 1 getting started ni pxie-1075 user manual 1-10 ni.Com the pxi trigger lines from adjacent pxi trigger bus segments can be routed in either direction across the pxi trigger bridges. Refer to figure 1-5 for the connectivity diagram. This allows you to send trigger signals to, and receive trig...
Page 18
Chapter 1 getting started © national instruments corporation 1-11 ni pxie-1075 user manual an independent buffer drives pxie_clk100 to each peripheral slot. These clocks are matched in skew to less than 100 ps. The differential pair must be terminated on the peripheral with lvpecl termination for th...
Page 19
Chapter 1 getting started ni pxie-1075 user manual 1-12 ni.Com to synchronize the system to an external clock, you can drive pxi_clk10 from an external source through the pxi_clk10_in pin on the system timing slot. Refer to table b-5, xp4 connector pinout for the system timing slot , for the pinout....
Page 20
Chapter 1 getting started © national instruments corporation 1-13 ni pxie-1075 user manual a copy of the backplane’s pxi_clk10 is exported to the 10 mhz ref out connector on the rear of the chassis. Refer to figure 1-2 for the location of this connector. This clock is driven by an independent buffer...
Page 21: Safety Information
© national instruments corporation 2-1 ni pxie-1075 user manual 2 installation and configuration this chapter describes how to prepare and operate the ni pxie-1075 chassis. Before connecting the chassis to a power source, read this chapter and the read me first: safety and radio-frequency interferen...
Page 22
Chapter 2 installation and configuration ni pxie-1075 user manual 2-2 ni.Com • part replacement —only service this equipment with parts that are exact replacements, both electrically and mechanically. Contact national instruments for replacement part information. Installation of parts with those tha...
Page 23
Chapter 2 installation and configuration © national instruments corporation 2-3 ni pxie-1075 user manual figure 2-1. Ni pxie-1075 cooling clearances 1.75 (44.45) 1.75 (44.45) 3 .00 (76.20) dimen s ion s a re in inche s (millimeter s ) ni pxie-1075.
Page 24
Chapter 2 installation and configuration ni pxie-1075 user manual 2-4 ni.Com figure 2-2. Ni pxie-1075 vents chassis ambient temperature definition the chassis fan control system uses intake air temperature as the input for controlling fan speeds when in auto fan speed mode. Because of this, the chas...
Page 25: Rack Mounting
Chapter 2 installation and configuration © national instruments corporation 2-5 ni pxie-1075 user manual responsibility to ensure that this ambient temperature does not exceed the rated ambient temperature as stated in appendix a, specifications . If the temperature exceeds the stated spec the power...
Page 26: Connecting to Power Source
Chapter 2 installation and configuration ni pxie-1075 user manual 2-6 ni.Com if your power outlet does not have an appropriate ground connection, you must connect the premise safety ground to the chassis grounding screw located on the rear panel. Refer to figure 1-2, rear view of the ni pxie-1075 ch...
Page 27
Chapter 2 installation and configuration © national instruments corporation 2-7 ni pxie-1075 user manual 3. Install the system controller into the system controller slot (slot 1, indicated by the red card guides) by first placing the system controller pcb into the front of the card guides (top and b...
Page 28
Chapter 2 installation and configuration ni pxie-1075 user manual 2-8 ni.Com figure 2-4 shows a pxi express system controller installed in the system controller slot of a ni pxie-1075 chassis. You can place compactpci, compactpci express, pxi, or pxi express modules in other slots depending on the s...
Page 29
Chapter 2 installation and configuration © national instruments corporation 2-9 ni pxie-1075 user manual installing peripheral modules caution the ni pxie-1075 chassis has been designed to accept a variety of peripheral module types in different slots. To prevent damage to the chassis, ensure that t...
Page 30
Chapter 2 installation and configuration ni pxie-1075 user manual 2-10 ni.Com figure 2-5. Installing pxi, pxi express, or compactpci peripheral modules power inhibit switch led indicator the chassis power inhibit switch has an integrated led. Refer to figure 1-1, front view of the ni pxie-1075 chass...
Page 31
Chapter 2 installation and configuration © national instruments corporation 2-11 ni pxie-1075 user manual note if two system fans or both of the power supply fans fail the chassis will shut down automatically, preventing the chassis and modules from damage due to overheating. Remote voltage monitori...
Page 32: Inhibit Mode Switch
Chapter 2 installation and configuration ni pxie-1075 user manual 2-12 ni.Com you can use a digital voltmeter to ensure all voltage levels in the ni pxie-1075 chassis are within the allowable limits. Referring to table 2-2, connect one lead of the voltmeter to a supply pin on the remote voltage moni...
Page 33: Pxi_Clk10 Rear Connectors
Chapter 2 installation and configuration © national instruments corporation 2-13 ni pxie-1075 user manual (pin 5) to a logic ground pin (pin 1 or 9). As long as this connection exists, the chassis will remain off (standby); when you remove this connection, the chassis turns on. Note for the remote i...
Page 34
Chapter 2 installation and configuration ni pxie-1075 user manual 2-14 ni.Com figure 2-6. Multichassis configuration in max pxi-1 system configuration 1. Launch max. 2. In the configuration tree, click the devices and interfaces branch to expand it. 3. If the pxi system controller has not yet been c...
Page 35
Chapter 2 installation and configuration © national instruments corporation 2-15 ni pxie-1075 user manual 4. Click the pxi system controller. The chassis (or multiple chassis, in a multichassis configuration) is listed below it. Identify each chassis by right-clicking its entry, then selecting the a...
Page 36
Chapter 2 installation and configuration ni pxie-1075 user manual 2-16 ni.Com complete the following steps to reserve these trigger lines in max. 1. In the configuration tree, click on the pxi chassis branch you want to configure. 2. Then, in the right-hand pane, toward the bottom, click on the trig...
Page 37
Chapter 2 installation and configuration © national instruments corporation 2-17 ni pxie-1075 user manual the capability documentation for the ni pxie-1075 chassis is contained in the chassis.Ini file on the software media that comes with the chassis. The information in this file is combined with in...
Page 38: Maintenance
© national instruments corporation 3-1 ni pxie-1075 user manual 3 maintenance this chapter describes basic maintenance procedures you can perform on the ni pxie-1075 chassis. Caution disconnect the power cable prior to servicing a ni pxie-1075 chassis. Service interval clean the chassis fan filters ...
Page 39
Chapter 3 maintenance ni pxie-1075 user manual 3-2 ni.Com caution always disconnect the ac power cable before cleaning or servicing the chassis. Interior cleaning use a dry, low-velocity stream of air to clean the interior of the chassis. Use a soft-bristle brush for cleaning around components. Exte...
Page 40
Chapter 3 maintenance © national instruments corporation 3-3 ni pxie-1075 user manual resetting the ac mains circuit breaker if the ni pxie-1075 chassis is connected to an ac source and encounters an over-current condition, the circuit breaker on the rear panel will trip to prevent damage to the cha...
Page 41
Chapter 3 maintenance ni pxie-1075 user manual 3-4 ni.Com before connecting the power supply shuttle to a power source, read this section and the read me first: safety and radio-frequency interference document included with the kit. Removal the ni pxie-1075 ac power supply shuttle is a replacement p...
Page 42: Specifications
© national instruments corporation a-1 ni pxie-1075 user manual a specifications this appendix contains specifications for the ni pxie-1075 chassis. Caution specifications are subject to change without notice. Electrical ac input input voltage rating ................................ 100 to 120 vac, ...
Page 43
Appendix a specifications ni pxie-1075 user manual a-2 ni.Com power disconnect ....................................The ac power cable provides main power disconnect. The front-panel power switch causes the internal chassis power supply to provide dc power to the compactpci/pxi express backplane. You...
Page 44
Appendix a specifications © national instruments corporation a-3 ni pxie-1075 user manual backplane pin current capacity load regulation maximum ripple and noise (20 mhz bandwidth) over-current protection.......................... All outputs protected from short circuit and overload with automatic ...
Page 45: Chassis Cooling
Appendix a specifications ni pxie-1075 user manual a-4 ni.Com chassis cooling module cooling system...........................Forced air circulation (positive pressurization) through three 165 cfm fans with high/auto speed selector slot airflow direction ..............................Bottom of modul...
Page 46
Appendix a specifications © national instruments corporation a-5 ni pxie-1075 user manual operating environment ambient temperature range.................... 0 to 55 °c (tested in accordance with iec-60068-2-1 and iec-60068-2-2. Meets mil-prf-28800f class 3 low temperature limit and mil-prf-28800f c...
Page 47
Appendix a specifications ni pxie-1075 user manual a-6 ni.Com sound power auto fan (up to ~30 °c ambient) ............55.5 dba high fan ..................................................76.2 dba notes for emc compliance, operate this device with shielded cabling. In addition, all covers and filler p...
Page 48: Rohs
Appendix a specifications © national instruments corporation a-7 ni pxie-1075 user manual ce compliance this product meets the essential requirements of applicable european directives, as amended for ce marking, as follows: • 2006/95/ec; low-voltage directive (safety) • 2004/108/ec; electromagnetic ...
Page 49
Appendix a specifications ni pxie-1075 user manual a-8 ni.Com backplane size .........................................................3u-sized; one system slot (with three system expansion slots) and 17 peripheral slots. Compliant with ieee 1101.10 mechanical packaging. Pxi express specification com...
Page 50
Appendix a specifications © national instruments corporation a-9 ni pxie-1075 user manual 100 mhz system reference clock: pxie_clk100 and pxie_sync100 maximum slot-to-slot skew ................... 100 ps accuracy ................................................ ±25 ppm max. (guaranteed over the oper...
Page 51
Appendix a specifications ni pxie-1075 user manual a-10 ni.Com external clock source frequency ...............................................10 mhz ±100 ppm input amplitude rear panel bnc...............................200 mv pp to 5 v pp square-wave or sine-wave system timing slot pxi_clk10_in .......
Page 52
Appendix a specifications © national instruments corporation a-11 ni pxie-1075 user manual notes for pxie slot to pxi_dstar mapping refer to the system timing slot section of chapter 1, getting started . For other specifications, the ni pxie-1075 complies with the pxi-5 pxi express hardware specific...
Page 53
Appendix a specifications ni pxie-1075 user manual a-12 ni.Com figure a-1. Ni pxie-1075 chassis dimensions (front and side) dimen s ion s a re in inche s (millimeter s ) 0.57 (14.5) . 3 9 (9.9) 17.54 (445.6) 6.97 (177.1) 1.14 0. 3 0 (7.25) 3 .54 (90.0) 1. 8 4 (46. 8 ) 17.11 (4 3 4.6) 3 .19 ( 8 1.1) ...
Page 54
Appendix a specifications © national instruments corporation a-13 ni pxie-1075 user manual figure a-2. Ni pxie-1075 chassis dimensions (bottom) 1.017 (25.83) 2.524 (64.11) 15.504 (393.8) 12.700 (322.58) dimensions are in inches (millimeters).
Page 55
Appendix a specifications ni pxie-1075 user manual a-14 ni.Com figure a-3 shows the chassis rack mount kit components. Figure a-3. Ni chassis rack mount kit components notes the chassis shown in figure a-3 is representative of the ni pxi-1044/1045 and ni pxie-1075 product line. For more information ...
Page 56: Pinouts
© national instruments corporation b-1 ni pxie-1075 user manual b pinouts this appendix describes the connector pinouts for the ni pxie-1075 chassis backplane. Figure b-1 illustrates the types of pxie connectors by providing a layout of the pxi express system controller slot (slot 1). Table b-1 show...
Page 57
Appendix b pinouts ni pxie-1075 user manual b-2 ni.Com system controller slot pinouts figure b-1. Pxi express system controller slot layout 1 xp4 connector 2 xp3 connector 3 xp2 connector 4 xp1 connector table b-1. Xp4 connector pinout for the system controller slot pin z a b c d e f 1 gnd ga4 ga3 g...
Page 58
Appendix b pinouts © national instruments corporation b-3 ni pxie-1075 user manual table b-2. Xp3 connector pinout for the system controller slot pin a b ab c d cd e f ef 1 rsv rsv gnd rsv rsv gnd rsv rsv gnd 2 rsv rsv gnd pwr_ok ps_on# gnd linkcap pwrbtn# gnd 3 smbdat smbclk gnd 4refclk+ 4refclk– g...
Page 59: System Timing Slot Pinouts
Appendix b pinouts ni pxie-1075 user manual b-4 ni.Com system timing slot pinouts figure b-2. Pxi express system timing slot layout table b-4. Xp1 connector pinout for the system controller slot pins signals a gnd b 12v c 12v d gnd e 5v f 3.3v g gnd 1 xp4 connector 2 xp3 connector 3 tp2 connector 4 ...
Page 60
Appendix b pinouts © national instruments corporation b-5 ni pxie-1075 user manual table b-5. Xp4 connector pinout for the system timing slot pin z a b c d e f 1 gnd ga4 ga3 ga2 ga1 ga0 gnd 2 gnd 5v aux gnd sysen# wake# alert# gnd 3 gnd 12v 12v gnd gnd gnd gnd 4 gnd gnd gnd 3.3v 3.3v 3.3v gnd 5 gnd ...
Page 61
Appendix b pinouts ni pxie-1075 user manual b-6 ni.Com table b-7. Tp2 connector pinout for the system timing slot pin a b ab c d cd e f ef 1 pxie_ dstarc0+ pxie_ dstarc0– gnd pxie_ dstarc8+ pxie_ dstarc8– gnd pxie_ dstarb8+ pxie_ dstarb8– gnd 2 pxie_ dstara0+ pxie_ dstara0– gnd pxie_ dstarc9+ pxie_ ...
Page 62
Appendix b pinouts © national instruments corporation b-7 ni pxie-1075 user manual table b-8. Tp1 connector pinout for the system timing slot pin a b ab c d cd e f ef 1 pxie_ dstara3+ pxie_ dstara3– gnd pxie_ dstarc7+ pxie_ dstarc7– gnd pxie_ dstarc12+ pxie_ dstarc12– gnd 2 pxie_ dstarc4+ pxie_ dsta...
Page 63: Hybrid Slot Pinouts
Appendix b pinouts ni pxie-1075 user manual b-8 ni.Com hybrid slot pinouts figure b-3. Pxi express system hybrid slot layout 1 xp4 connector 2 xp3 connector 3 p1 connector table b-9. Xp4 connector pinout for the hybrid slot pin z a b c d e f 1 gnd ga4 ga3 ga2 ga1 ga0 gnd 2 gnd 5vaux gnd sysen# wake#...
Page 64
Appendix b pinouts © national instruments corporation b-9 ni pxie-1075 user manual table b-10. Xp3 connector pinout for the hybrid slot pin a b ab c d cd e f ef 1 pxie_ clk100+ pxie_ clk100– gnd pxie_ sync100+ pxie_ sync100– gnd pxie_ dstarc+ pxie_ dstarc– gnd 2 prsnt# pwren# gnd pxie_ dstarb+ pxie_...
Page 65
Appendix b pinouts ni pxie-1075 user manual b-10 ni.Com table b-11. P1 connector pinout for the hybrid slot pin z a b c d e f 25 gnd 5v req64# enum# 3.3v 5v gnd 24 gnd ad[1] 5v v(i/o) ad[0] ack64# gnd 23 gnd 3.3v ad[4] ad[3] 5v ad[2] gnd 22 gnd ad[7] gnd 3.3v ad[6] ad[5] gnd 21 gnd 3.3v ad[9] ad[8] ...
Page 66: Technical Support and
© national instruments corporation c-1 ni pxie-1075 user manual c technical support and professional services visit the following sections of the award-winning national instruments web site at ni.Com for technical support and professional services: • support —technical support resources at ni.Com/su...
Page 67
Appendix c technical support and professional services ni pxie-1075 user manual c-2 ni.Com • declaration of conformity (doc) —a doc is our claim of compliance with the council of the european communities using the manufacturer’s declaration of conformity. This system affords the user protection for ...
Page 68: Glossary
© national instruments corporation g-1 ni pxie-1075 user manual glossary symbol prefix value p pico 10 –12 n nano 10 –9 μ micro 10 – 6 m milli 10 –3 k kilo 10 3 m mega 10 6 g giga 10 9 t tera 10 12 symbols ° degrees. ≥ equal or greater than. ≤ equal or less than. % percent. A a amperes. Ac alternati...
Page 69
Glossary ni pxie-1075 user manual g-2 ni.Com b backplane an assembly, typically a printed circuit board, with connectors and signal paths that bus the connector pins. Bnc bayonet neill concelman connector; a commonly used coaxial connector. C c celsius. Cfm cubic feet per minute. Cfr code of federal...
Page 70
Glossary © national instruments corporation g-3 ni pxie-1075 user manual e efficiency ratio of output power to input power, expressed as a percentage. Eia electronic industries association. Emc electromagnetic compatibility. Emi electromagnetic interference. F fcc federal communications commission. ...
Page 71
Glossary ni pxie-1075 user manual g-4 ni.Com in. Inches. Inhibit to turn off. J jitter a measure of the small, rapid variations in clock transition times from their nominal regular intervals. Units: seconds rms. K kg kilograms. Km kilometers. L lb pounds. Led light emitting diode. Line regulation th...
Page 72
Glossary © national instruments corporation g-5 ni pxie-1075 user manual n nema national electrical manufacturers association. Ni national instruments. P power supply shuttle a removable module that contains the chassis power supply. Pxi pci extensions for instrumentation. Pxi_clk10 10 mhz pxi syste...
Page 73
Glossary ni pxie-1075 user manual g-6 ni.Com system reference clock a 10 mhz clock, also called pxi_clk10, that is distributed to all peripheral slots in the chassis, as well as a bnc connector on the rear of chassis labeled 10 mhz ref out . The system reference clock can be used for synchronization...
Page 74: Index
© national instruments corporation i-1 ni pxie-1075 user manual index a ac power cables part numbers (table), 1-2 ac power cables (table), 1-2 architecture, backplane, 1-6 b backplane architecture, 1-6 hybrid peripheral slots, 1-7 interoperability with compactpci, 1-6 overview, 1-6 pxi express perip...
Page 75
Index ni pxie-1075 user manual i-2 ni.Com f fan, setting speed, 2-5 filler panel installation, 2-5 g ground, connecting, 2-5 h help, technical support, c-1 hybrid peripheral slots, description, 1-7 hybrid slot pinouts p1 connector (table), b-10 xp3 connector (table), b-9 xp4 connector (table), b-8 i...
Page 76
Index © national instruments corporation i-3 ni pxie-1075 user manual hybrid peripheral slots, 1-7 installation. See installation, configuration, and operation interoperability with compactpci, 1-6 key features, 1-2 maintenance. See maintenance of ni pxie-1075 chassis optional equipment, 1-5 pxi exp...
Page 77
Index ni pxie-1075 user manual i-4 ni.Com s safety, specifications, a-6 safety and caution notices, 2-1 safety ground, connecting, 2-5 service interval, 3-1 setting fan speed, 2-5 slot blocker installation, 2-5 kit, 1-6 software (ni resources), c-1 specifications acoustic emissions sound power, a-6 ...
Page 78
Index © national instruments corporation i-5 ni pxie-1075 user manual v voltage monitoring connector. See db-9 connector voltages at voltage monitoring connector (db-9) (table), 2-12 w web resources, c-1.