National Instruments NI 9265 Getting Started Manual - Compactrio

Manual is about: National Instruments Analog Current Output Module Operating Instructions and Specifications

Summary of NI 9265

  • Page 1

    Getting started guide ni 9265 4-channel, 0 ma to 20 ma, 16-bit analog output module this document explains how to connect to the ni 9265..

  • Page 2: Note

    Note before you begin, complete the software and hardware installation procedures in your chassis documentation. Note the guidelines in this document are specific to the ni 9265. The other components in the system might not meet the same safety ratings. Refer to the documentation for each component ...

  • Page 3

    Safety voltages connect only voltages that are within the following limits. Channel-to-com or vsup-to-com ±40 v maximum 1 isolation voltages channel-to-channel none channel-to-earth ground, vsup-to-earth ground, or com-to-earth ground continuous up to 2,000 m altitude 250 vrms, measurement category ...

  • Page 4

    Withstand up to 2,000 m altitude 2,300 vrms, verified by a 5 s dielectric withstand test up to 5,000 m altitude 1,000 vrms, verified by a 5 s dielectric withstand test measurement category i is for measurements performed on circuits not directly connected to the electrical distribution system referr...

  • Page 5: Note

    Note do not connect the ni 9265 to signals or use for measurements within measurement categories iii or iv. Safety guidelines for hazardous voltages if hazardous voltages are connected to the device, take the following precautions. A hazardous voltage is a voltage greater than 42.4 vpk voltage or 60...

  • Page 6: Caution

    Safety guidelines for hazardous locations the ni 9265 is suitable for use in class i, division 2, groups a, b, c, d, t4 hazardous locations; class i, zone 2, aex na iic t4 and ex na iic t4 hazardous locations; and nonhazardous locations only. Follow these guidelines if you are installing the ni 9265...

  • Page 7: Caution

    Caution for division 2 and zone 2 applications, connected signals must be within the following limits. Capacitance 80 nf max max inductance 0.2 h max max special conditions for hazardous locations use in europe and internationally the ni 9265 has been evaluated as ex na iic t4 gc equipment under dem...

  • Page 8: Caution

    Caution the system shall be mounted in an atex/iecex-certified enclosure with a minimum ingress protection rating of at least ip54 as defined in iec/en 60079-15. Caution the enclosure must have a door or cover accessible only by the use of a tool. Electromagnetic compatibility guidelines this produc...

  • Page 9: Caution

    Furthermore, any changes or modifications to the product not expressly approved by national instruments could void your authority to operate it under your local regulatory rules. Special conditions for marine applications some products are lloyd’s register (lr) type approved for marine (shipboard) a...

  • Page 10: Note

    Preparing the environment ensure that the environment in which you are using the ni 9265 meets the following specifications. Operating temperature (iec 60068-2-1, iec 60068-2-2) -40 °c to 70 °c operating humidity (iec 60068-2-78) 10% rh to 90% rh, noncondensing pollution degree 2 maximum altitude 2,...

  • Page 12

    Ni 9265 signals the ni 9265 has four analog output channels, ao. Each channel has a common terminal, com, that is internally connected to the isolated ground reference of the module. The ni 9265 also has a terminal for an external power supply, vsup, and an external power supply common terminal, pow...

  • Page 13

    Figure 2. Connecting a load to the ni 9265 ao com ni 9265 isolated dac + _ vsup power supply com load protection dc/dc external power supply connecting an external power supply you must connect an external power supply to the ni 9265. This power supply provides the current for the devices you connec...

  • Page 14

    When the module powers on, the channels output the startup current. High-vibration application connections if your application is subject to high vibration, ni recommends that you follow these guidelines to protect connections to the ni 9265: • use ferrules to terminate wires to the detachable conne...

  • Page 15: Compactrio

    Where to go next located atni.Com/manuals installs with the software compactrio ni compactdaq related information ni 9265 datasheet ni-rio help labview fpga help ni 9265 datasheet ni-daqmx help labview help c series documentation & resources ni.Com/info cseriesdoc services ni.Com/services ni 9265 ge...

  • Page 16

    Worldwide support and services the national instruments website is your complete resource for technical support. At ni.Com/support , you have access to everything from troubleshooting and application development self-help resources to email and phone assistance from ni application engineers. Visit n...

  • Page 17

    National instruments corporate headquarters is located at 11500 north mopac expressway, austin, texas, 78759-3504. National instruments also has offices located around the world. For telephone support in the united states, create your service request at ni.Com/support or dial 1 866 ask myni (275 696...

  • Page 18

    Refer to the ni trademarks and logo guidelines at ni.Com/trademarks for information on national instruments trademarks. Other product and company names mentioned herein are trademarks or trade names of their respective companies. For patents covering national instruments products/technology, refer t...