National Instruments NI 9403E Operating Instructions Manual

Manual is about: National Instruments Digital Input/Output Module Operating Instructions and Specifications

Summary of NI 9403E

  • Page 1

    Operating instructions and specifications ni 9403e 32-channel, ttl digital input/output module.

  • Page 2

    Ni 9403e operating instructions and specifications 2 ni.Com this document describes how to use the national instruments 9403e and includes dimensions, pin assignments, and specifications for the ni 9403e. Visit ni.Com/info and enter rdsoftwareversion to determine which software you need for the modu...

  • Page 3

    © national instruments corp. 3 ni 9403e operating instructions and specifications ni 9403e dimensions the following figure shows the dimensions of the ni 9403e. Figure 1. Ni 9403e dimensions in millimeters (inches) 73.4 (2.89) 0.0 (0.00) 26.7 (1.05) 58.4 (2.30) 66.0 (2.60) 0.0 (0.00).

  • Page 4

    Ni 9403e operating instructions and specifications 4 ni.Com connecting the ni 9403e the ni 9403e has a 37-pin dsub connector that provides connections for the 32 digital input/output channels. Figure 2. Ni 9403e pin assignments dio16 dio17 dio18 dio19 dio20 dio21 dio22 dio23 com com dio24 dio25 dio2...

  • Page 5

    © national instruments corp. 5 ni 9403e operating instructions and specifications each channel has a dio pin to which you can connect a digital input or output device. The 32 dio channels are internally referenced to com, so you can use any of the four com lines as a reference for the external signa...

  • Page 6

    Ni 9403e operating instructions and specifications 6 ni.Com refer to figure 3 for an illustration of several types of digital devices connected to the ni 9403e. Figure 3. Connecting digital devices to the ni 9403e ttl signal +5 v +5 v led dio0 as input dio1 as input com dio2 as output ni 9403e dev 3...

  • Page 7

    © national instruments corp. 7 ni 9403e operating instructions and specifications overcurrent/short-circuit protection the overcurrent protection allows only a specified amount of current through the output channels to protect the ni 9403e from short circuits. If the ni 9403e goes into an overcurren...

  • Page 8

    Ni 9403e operating instructions and specifications 8 ni.Com ni.Com/info and enter cseriesdoc for information about c series documentation. Typically, when a system is in sleep mode, you cannot communicate with the modules. In sleep mode, the system consumes minimal power and may dissipate less heat ...

  • Page 9

    © national instruments corp. 9 ni 9403e operating instructions and specifications digital logic levels input voltage ................................. –0.25 to 5.25 v high, v ih .............................. 2.2 v min low, v il ............................... 0.8 v max hysteresis, v h ................

  • Page 10

    Ni 9403e operating instructions and specifications 10 ni.Com timing input setup time 1 ........................... 10 ns min hold time 2 ............................ 60 ns min output propagation delay 3 ............... 330 ns max channel-to-channel skew 4 ... 265 ns max 1 setup time is the amount of...

  • Page 11

    © national instruments corp. 11 ni 9403e operating instructions and specifications update/transfer time 1 crio-9151 r series expansion chassis ................ 8 μ s max all other chassis................... 7 μ s max direction change time 1 ............... 18 μ s max overvoltage protection channel-t...

  • Page 12

    Ni 9403e operating instructions and specifications 12 ni.Com mtbf ............................................... 763,325 hours at 25 °c; bellcore issue 2, method 1, case 3, limited part stress method note contact ni for bellcore mtbf specifications at other temperatures or for mil-hdbk-217f specifi...

  • Page 13

    © national instruments corp. 13 ni 9403e operating instructions and specifications physical characteristics if you need to clean the module, wipe it with a dry towel. Weight............................................... 47 g (1.7 oz) safety safety voltages connect only voltages that are within the ...

  • Page 14

    Ni 9403e operating instructions and specifications 14 ni.Com measurement category i is for measurements performed on circuits not directly connected to the electrical distribution system referred to as mains voltage. Mains is a hazardous live electrical supply system that powers equipment. This cate...

  • Page 15

    © national instruments corp. 15 ni 9403e operating instructions and specifications online product certification refer to the product declaration of conformity (doc) for additional regulatory compliance information. To obtain product certifications and the doc for this product, visit ni.Com/ certific...

  • Page 16

    Ni 9403e operating instructions and specifications 16 ni.Com maximum altitude............................. 2,000 m pollution degree (iec 60664) .......... 2 environmental management ni is committed to designing and manufacturing products in an environmentally responsible manner. Ni recognizes that e...

  • Page 17

    © national instruments corp. 17 ni 9403e operating instructions and specifications waste electrical and electronic equipment (weee) eu customers at the end of the life cycle, all products must be sent to a weee recycling center. For more information about weee recycling centers and national instrume...

  • Page 18

    Ni 9403e operating instructions and specifications 18 ni.Com where to go for support the national instruments web site is your complete resource for technical support. At ni.Com/support you have access to everything from troubleshooting and application development self-help resources to email and ph...

  • Page 19

    © 2008 national instruments corp. All rights reserved. 372617a-01 jul08 national instruments, ni, ni.Com, and labview are trademarks of national instruments corporation. Refer to the terms of use section on ni.Com/legal for more information about national instruments trademarks. Other product and co...