National Instruments NI 9474 Getting Started Manual - Caution
Caution
Substitution of components may impair
suitability for Class I, Division 2.
Caution
For Division 2 and Zone 2 applications,
install the system in an enclosure rated to at least IP54
as defined by IEC/EN 60079-15.
Caution
For Division 2 and Zone 2 applications,
install a protection device between the Vsup and COM
terminals on the NI 9474. The device must prevent the
input Vsup-to-COM voltage from exceeding 42 V if
there is a transient overvoltage condition.
Special Conditions for Hazardous Locations Use in
Europe and Internationally
The NI 9474 has been evaluated as Ex nA IIC T4 Gc equipment
under DEMKO Certificate No. 03 ATEX 0324020X and is
IECEx UL 14.0089X certified. Each NI 9474 is marked II 3G
and is suitable for use in Zone 2 hazardous locations, in ambient
temperatures of -40 °C ≤ Ta ≤ 70 °C. If you are using the NI 9474
in Gas Group IIC hazardous locations, you must use the device in
an NI chassis that has been evaluated as Ex nC IIC T4, Ex IIC
T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.
6
| ni.com | NI 9474 Getting Started Guide