National Instruments SCXI-1163 User Manual - About This Manual

Manual is about: 32-Channel Isolated Digital Output Module

Summary of SCXI-1163

  • Page 1

    © copyright 1993, 1994 national instruments corporation. All rights reserved. Scxi-1163 user manual 32-channel isolated digital output module september 1994 edition part number 320576-01.

  • Page 2

    National instruments corporate headquarters 6504 bridge point parkway austin, tx 78730-5039 (512) 794-0100 technical support fax: (800) 328-2203 (512) 794-5678 branch offices: australia (03) 879 9422, austria (0662) 435986, belgium 02/757.00.20, canada (ontario) (519) 622-9310, canada (québec) (514)...

  • Page 3

    Limited warranty the scxi-1163 is warranted against defects in materials and workmanship for a period of one year from the date of shipment, as evidenced by receipts or other documentation. National instruments will, at its option, repair or replace equipment that proves to be defective during the w...

  • Page 4: Contents

    © national instruments corporation v scxi-1163 user manual contents about this manual ............................................................................................................. Xi organization of this manual ............................................................................

  • Page 5

    Contents scxi-1163 user manual vi © national instruments corporation chapter 4 register descriptions ......................................................................................................... 4-1 register description........................................................................

  • Page 6

    Contents © national instruments corporation vii scxi-1163 user manual appendix e scxi-1163 cabling ............................................................................................................. E-1 scxi-1340 cable assembly .................................................................

  • Page 7

    Contents scxi-1163 user manual viii © national instruments corporation figures figure 1-1. Scxi-1163 digital output module.................................................................... 1-1 figure 2-1. Scxi-1163 parts locator diagram ................................................................

  • Page 8: About This Manual

    © national instruments corporation ix scxi-1163 user manual about this manual this manual describes the electrical and mechanical aspects of the scxi-1163 and contains information concerning its operation and programming. The scxi-1163 is a member of the national instruments signal conditioning exte...

  • Page 9

    About this manual scxi-1163 user manual x © national instruments corporation • the glossary contains an alphabetical list and description of terms used in this manual, including abbreviations, acronyms, metric prefixes, mnemonics, and symbols. • the index contains an alphabetical list of key terms a...

  • Page 10: Related Documentation

    About this manual © national instruments corporation xi scxi-1163 user manual abbreviations, acronyms, metric prefixes, mnemonics, symbols, and terms are listed in the glossary. Related documentation the following documents contain information that you may find helpful as you read this manual: • at-...

  • Page 11: Customer Communication

    About this manual scxi-1163 user manual xii © national instruments corporation customer communication national instruments wants to receive your comments on our products and manuals. We are interested in the applications you develop with our products, and we want to help if you have problems with th...

  • Page 12: Chapter 1

    © national instruments corporation 1-1 scxi-1163 user manual chapter 1 introduction this chapter describes the scxi-1163; lists the contents of your scxi-1163 kit; describes the optional software, optional equipment, and custom cables; and explains how to unpack the scxi-1163 kit. Figure 1-1 shows t...

  • Page 13: What You Need to Get Started

    Introduction chapter 1 scxi-1163 user manual 1-2 © national instruments corporation with the scxi-1163, you can use the scxi chassis as a controller in laboratory testing, production testing, and industrial-process monitoring. What you need to get started scxi-1163 module scxi-1163 user manual scxi ...

  • Page 14: Optional Equipment

    Chapter 1 introduction © national instruments corporation 1-3 scxi-1163 user manual you can also use the scxi-1163, combined with the nb series data acquisition boards, with ni-daq software for macintosh. Ni-daq software for macintosh, which is shipped with all national instruments macintosh data ac...

  • Page 15: Unpacking

    Introduction chapter 1 scxi-1163 user manual 1-4 © national instruments corporation • erni components, inc. (part number 033-273) the mating connector for the scxi-1163 front connector is a special 48-pin reversed din c female connector. National instruments uses a polarized and keyed connector to p...

  • Page 16: Chapter 2

    © national instruments corporation 2-1 scxi-1163 user manual chapter 2 configuration and installation this chapter describes the scxi-1163 jumper configurations, installation of the scxi-1163 into the scxi chassis, signal connections to the scxi-1163, and cable wiring. Module configuration the scxi-...

  • Page 18

    Chapter 2 configuration and installation © national instruments corporation 2-3 scxi-1163 user manual the scxi-1163 can accept data in two forms–serial and parallel. Serial data is transferred across the scxibus using the serial peripheral interface (spi) protocol. Using serial communication, one da...

  • Page 19

    Configuration and installation chapter 2 scxi-1163 user manual 2-4 © national instruments corporation do not operate damaged equipment. The safety protection features built into this module can become impaired if the module becomes damaged in any way. If it is damaged, turn the module off and do not...

  • Page 20

    Chapter 2 configuration and installation © national instruments corporation 2-5 scxi-1163 user manual - jumper w5 carries the scxibus miso line, after buffering, to the serdatout signal on the rear signal connector. - jumper w6 selects the primary operating mode, either serial or parallel, and confi...

  • Page 21

    Configuration and installation chapter 2 scxi-1163 user manual 2-6 © national instruments corporation position par disconnects serdatout from the scxibus miso line. Use this position when you will connect the module in parallel to a data acquisition board. Using jumpers w4 and w5 if a module is not ...

  • Page 22

    Chapter 2 configuration and installation © national instruments corporation 2-7 scxi-1163 user manual table 2-1. Configuration of jumpers w2, w3, and w5 for dio-type and mio-type boards jumper description configuration for dio-type board configuration for mio-type board w2 w3 w5 w5 configures rear c...

  • Page 23: Hardware Installation

    Configuration and installation chapter 2 scxi-1163 user manual 2-8 © national instruments corporation hardware installation you can install the scxi-1163 in any available scxi chassis. After you have made any necessary changes and have verified and recorded the jumper settings on the form in appendi...

  • Page 24

    Chapter 2 configuration and installation © national instruments corporation 2-9 scxi-1163 user manual front connector figure 2-2 shows the pin assignments for the scxi-1163 front connector. Pin number signal name column a b c signal name 30 29 26 25 22 21 18 17 14 13 10 9 6 5 2 1 out 0 out 1 out 2 o...

  • Page 25

    Configuration and installation chapter 2 scxi-1163 user manual 2-10 © national instruments corporation front connector signal descriptions pin signal name description b30, a30, out port 0 outputs b29, a29 c30 vcc port 0 power c29 gnd port 0 ground b26, a26, out port 1 outputs b25, a25 c26 vcc port 1...

  • Page 26

    Chapter 2 configuration and installation © national instruments corporation 2-11 scxi-1163 user manual pin signal name description (continued) a1, b1, a2, out port 7 outputs b2 c2 gnd port 7 ground c1 vcc port 7 power the scxi-1163 consists of eight ports of four optically isolated digital outputs. ...

  • Page 27

    Configuration and installation chapter 2 scxi-1163 user manual 2-12 © national instruments corporation when using the terminal block with high common-mode voltages, you must insulate your signal wires appropriately. National instruments is not liable for any damages or injuries resulting from inadeq...

  • Page 29

    Configuration and installation chapter 2 scxi-1163 user manual 2-14 © national instruments corporation scxi-1326 installation to connect the terminal block to the scxi-1163 front connector, follow these steps: 1. Connect the scxi-1163 front connector to its mating connector on the terminal block. 2....

  • Page 30

    Chapter 2 configuration and installation © national instruments corporation 2-15 scxi-1163 user manual 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 serdatin daqd*/a slot0sel* (mio) serclk dig gnd (mio) se...

  • Page 31

    Configuration and installation chapter 2 scxi-1163 user manual 2-16 © national instruments corporation rear signal connector signal descriptions, serial configuration pin signal name description 24 or 50 dig gnd digital ground – supplies the reference for data acquisition board digital signals and i...

  • Page 32

    Chapter 2 configuration and installation © national instruments corporation 2-17 scxi-1163 user manual all other pins are not connected. The signals on the rear signal connector are digital i/o signals. Signal connection guidelines for each of these groups are given in the following section. Serial ...

  • Page 33

    Configuration and installation chapter 2 scxi-1163 user manual 2-18 © national instruments corporation when you configure the scxi-1163 for an mio-type board, the digital i/o signals of the scxi-1163 match the digital i/o lines of the mio board. When you use the scxi-1163 with an scxi-1341, scxi-134...

  • Page 34

    Chapter 2 configuration and installation © national instruments corporation 2-19 scxi-1163 user manual timing requirements and communication protocol communication signals this section describes the methods for communicating on the serial peripheral interface (spi) bus and their timing requirements....

  • Page 35

    Configuration and installation chapter 2 scxi-1163 user manual 2-20 © national instruments corporation to write the 16-bit slot-select number to slot 0, follow these steps: 1. Initial conditions: serdatin = don't care. Daqd*/a = 1. Slot0sel* = 1. Serclk = 1. 2. Clear slot0sel* to 0. This deasserts a...

  • Page 36

    Chapter 2 configuration and installation © national instruments corporation 2-21 scxi-1163 user manual to write to the address handler, follow these steps: 1. Initial conditions: ss* asserted low. Serdatin = don't care. Daqd*/a = 1 (indicates data will be written to the address handler). Slot0sel* =...

  • Page 37

    Configuration and installation chapter 2 scxi-1163 user manual 2-22 © national instruments corporation to write to the data register, follow these steps: 1. Initial conditions: ss* asserted low. Serdatin = don't care. Daqd*/a = 0 (indicates data will be written to a register). Slot0sel* = 1. Serclk ...

  • Page 38

    Chapter 2 configuration and installation © national instruments corporation 2-23 scxi-1163 user manual to read from the module id register, follow these steps: 1. Initial conditions: ss* asserted low. Serdatin = don't care. Daqd*/a = 0. = 1. Serclk = 1 (and has not changed since daqd*/a went low). 2...

  • Page 39

    Configuration and installation chapter 2 scxi-1163 user manual 2-24 © national instruments corporation to read from a status register, follow these steps: 1. Initial conditions: ss* asserted low. Serdatin = don't care. Daqd*/a = 0. = 1. Serclk = don't care. 2. The status registers are 1-bit read-onl...

  • Page 40: Chapter 3

    © national instruments corporation 3-1 scxi-1163 user manual chapter 3 theory of operation this chapter contains a functional overview of the scxi-1163 module and explains the operation of each functional unit making up the scxi-1163. Functional overview the block diagram in figure 3-1 shows the key...

  • Page 41

    Theory of operation chapter 3 scxi-1163 user manual 3-2 © national instruments corporation intr* d*/a chsgnd chsgnd v+ v+ +5 v mosi a1 b1 a2 b2 a3 b3 a4 b4 a5 b5 a6 b6 a7 b7 a8 b8 a9 b9 a10 b10 a11 b11 a12 b12 a13 b13 a14 b14 a15 b15 a16 b16 a17 b17 a18 b18 a19 b19 a20 b20 a21 b21 a22 b22 a23 b23 a2...

  • Page 42

    Chapter 3 theory of operation © national instruments corporation 3-3 scxi-1163 user manual scxibus connector signal descriptions pin signal name description a19 reset* reset – when pulled low, reinitializes the module to its power-up state. Totem pole. Input. B19 miso master-in-slave-out – transmits...

  • Page 43

    Theory of operation chapter 3 scxi-1163 user manual 3-4 © national instruments corporation table 3-1. Scxibus equivalents for rear signal connector rear signal connector signal scxibus equivalent serdatin mosi daqd*/a d*/a slot0sel* intr* serclk spiclk serdatout miso when the primary mode of operati...

  • Page 44: Register Circuitry

    Chapter 3 theory of operation © national instruments corporation 3-5 scxi-1163 user manual this circuitry is divided into an scxi digital interface section and two signal routing sections. The scxi digital interface buffers signals from the scxibus to the module and drives signals from the module on...

  • Page 45

    Theory of operation chapter 3 scxi-1163 user manual 3-6 © national instruments corporation the register circuitry section consists of the data register, the module id register, the output mode register, and the primary mode status register. The data register is a 4-byte serial-in parallel-out shift ...

  • Page 46

    Chapter 3 theory of operation © national instruments corporation 3-7 scxi-1163 user manual output channels and the vcc and ground connections. Table 3-2 shows the channel and port assignments. These outputs are open-collector outputs with 4.7 k Ω pullups, which can sink 12 ma while maintaining an ou...

  • Page 47: Chapter 4

    © national instruments corporation 4-1 scxi-1163 user manual chapter 4 register descriptions this chapter describes in detail the scxi-1163 address handler, the module id register, the data register, the status registers, and the scxi-1000/1001 slot 0 registers. Note: if you plan to use a programmin...

  • Page 48

    Register descriptions chapter 4 scxi-1163 user manual 4-2 © national instruments corporation address handler you must write to the address handler at the beginning of each write to or read from the scxi-1163. Write the address of the register of interest to this handler, which in turn enables the re...

  • Page 49

    Chapter 4 register descriptions © national instruments corporation 4-3 scxi-1163 user manual module id register the module id register contains the 4-byte module id code for the scxi-1163. This code number is read on the miso line whenever the module id register is accessed. The bytes appear least s...

  • Page 50

    Register descriptions chapter 4 scxi-1163 user manual 4-4 © national instruments corporation data register the data register contains 32 bits that control the state of each output of the scxi-1163. Whenever the data register is selected by the address handler, the data register shifts in the data pr...

  • Page 51

    Chapter 4 register descriptions © national instruments corporation 4-5 scxi-1163 user manual status registers the status registers are 1-bit read-only registers that indicate the primary (jumper-set) mode of operation and the mode of operation currently driving the outputs. The register at address 0...

  • Page 52

    Register descriptions chapter 4 scxi-1163 user manual 4-6 © national instruments corporation parking register this register is a dummy register that you should select after the end of a read or write operation. Selecting the parking register places the module in a state insensitive to noise and to e...

  • Page 53

    Chapter 4 register descriptions © national instruments corporation 4-7 scxi-1163 user manual slot 0 register descriptions slot 0 has three registers–the fifo register, the hardscan register, and the slot-select register. Only the slot-select register is relevant to this module. The slot-select regis...

  • Page 54

    Register descriptions chapter 4 scxi-1163 user manual 4-8 © national instruments corporation slot-select register the slot-select register contains 16 bits that determine which module in which chassis is enabled for communication when the slot0sel* line is high. An scxi-1000 chassis selects the appr...

  • Page 55: Chapter 5

    © national instruments corporation 5-1 scxi-1163 user manual chapter 5 programming this chapter contains a functional programming description of the scxi-1163 and slot 0. Note: if you plan to use a programming software package such as ni-daq, labwindows, or labview with your scxi-1163 board, you do ...

  • Page 56

    Programming chapter 5 scxi-1163 user manual 5-2 © national instruments corporation table 5-1. Scxibus to scxi-1163 rear signal connector to data acquisition board pin equivalences scxibus line scxi-1163 rear signal connector mio boards lab-nb/lab-pc/ lab-pc+/lab-lc pc-lpm-16 dio-24 dio-96 dio-32f mo...

  • Page 57

    Chapter 5 programming © national instruments corporation 5-3 scxi-1163 user manual 5. If you are writing to a data register, you must first write address 0001 (hexadecimal) or address 0006 (hexadecimal) to the address handler. See chapter 4, register descriptions , for a discussion on the uses of th...

  • Page 58: Examples

    Programming chapter 5 scxi-1163 user manual 5-4 © national instruments corporation examples this section describes how to program the scxi-1163, either alone or in conjunction with other modules. The following examples are intended to aid your understanding of module and slot 0 programming. It will ...

  • Page 59

    Chapter 5 programming © national instruments corporation 5-5 scxi-1163 user manual example 3 you have a multiple-chassis system with an scxi-1163 in slots 4 and 8 of chassis 1, and another scxi-1163 in slot 11 of chassis 2. The scxi-1163 in slot 8 of chassis 1 is configured for a primary mode of ope...

  • Page 60: Appendix A

    © national instruments corporation a-1 scxi-1163 user manual appendix a specifications this appendix lists the specifications for the scxi-1163. These are typical at 25 ° cand 50% humidity unless otherwise stated. The operating temperature range is 0 ° to 50 ° c. Digital outputs power requirements (...

  • Page 61: Operating Environment

    Specifications appendix a scxi-1163 user manual a-2 © national instruments corporation operating environment temperature 0 ° to 50 ° c relative humidity 5% to 90% at 35 ° c storage environment temperature -55 ° to 150 ° c relative humidity 5% to 90% noncondensing.

  • Page 62: Appendix B

    © national instruments corporation b-1 scxi-1163 user manual appendix b rear signal connector this appendix describes the pinout and signal names for the scxi-1163 50-pin rear signal connector, including a description of each connection. Figure b-1a shows the pin assignments for the scxi-1163 rear s...

  • Page 63

    Rear signal connector appendix b scxi-1163 user manual b-2 © national instruments corporation 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 serdatin daqd*/a slot0sel* (mio) serclk dig gnd (mio) serdatout (...

  • Page 64

    Appendix b rear signal connector © national instruments corporation b-3 scxi-1163 user manual rear signal connector signal descriptions, serial configuration pin signal name description 24 or 50 dig gnd digital ground – supplies the reference for data acquisition board digital signals and is tied to...

  • Page 65

    Rear signal connector appendix b scxi-1163 user manual b-4 © national instruments corporation all other pins are not connected. See the timing requirements and communication protocol section in chapter 2, configuration and installation , for more detailed information on timing..

  • Page 66: Appendix C

    © national instruments corporation c-1 scxi-1163 user manual appendix c scxibus connector this appendix describes the pinout and signal names for the scxi-1163 scxibus connector, including a description of each connection. Figure c-1 shows the pin assignments for the scxi-1163 scxibus connector..

  • Page 67

    Scxibus connector appendix c scxi-1163 user manual c-2 © national instruments corporation intr* d*/a chsgnd chsgnd v+ v+ +5 v mosi a1 b1 a2 b2 a3 b3 a4 b4 a5 b5 a6 b6 a7 b7 a8 b8 a9 b9 a10 b10 a11 b11 a12 b12 a13 b13 a14 b14 a15 b15 a16 b16 a17 b17 a18 b18 a19 b19 a20 b20 a21 b21 a22 b22 a23 b23 a24...

  • Page 68

    Appendix c scxibus connector © national instruments corporation c-3 scxi-1163 user manual scxibus connector signal descriptions pin signal name description a19 reset* reset – when pulled low, reinitializes the module to its power-up state. Totem pole. Input. B19 miso master-in-slave-out – transmits ...

  • Page 69: Appendix D

    © national instruments corporation d-1 scxi-1163 user manual appendix d scxi-1163 front connector this appendix describes the pinout and signal names for the scxi-1163 front connector, including a description of each connection. Figure d-1 shows the pin assignments for the scxi-1163 front connector..

  • Page 70

    Scxi-1163 front connector appendix d scxi-1163 user manual d-2 © national instruments corporation pin number signal name column a b c signal name 30 29 26 25 22 21 18 17 14 13 10 9 6 5 2 1 out 0 out 1 out 2 out 3 out 4 out 5 out 6 out 7 out 8 out 9 out 10 out 11 out 12 out 13 out 14 out 15 out 19 ou...

  • Page 71

    Appendix d scxi-1163 front connector © national instruments corporation d-3 scxi-1163 user manual front connector signal descriptions pin signal name description b30, a30, out port 0 outputs b29, a29 c30 vcc port 0 power c29 gnd port 0 ground b26, a26, out port 1 outputs b25, a25 c26 vcc port 1 powe...

  • Page 72

    Scxi-1163 front connector appendix d scxi-1163 user manual d-4 © national instruments corporation pin signal name description (continued) a1, b1, a2, out port 7 outputs b2 c2 gnd port 7 ground c1 vcc port 7 power further information is given in chapter 2, configuration and installation ..

  • Page 73: Appendix E

    © national instruments corporation e-1 scxi-1163 user manual appendix e scxi-1163 cabling this appendix describes how to use and install the hardware accessories for the scxi-1163: • scxi-1340 cable assembly • scxi-1341 lab-nb, lab-pc, and lab-pc+ cable assembly • scxi-1344 lab-lc cable assembly • s...

  • Page 74

    Scxi-1163 cabling appendix e scxi-1163 user manual e-2 © national instruments corporation • the scxi-1340 has an extra male breakout connector for use with the scxi-1180 feedthrough panel or additional modules or breadboards that need a direct connection to the mio-16 or dio-24 board. • the scxi-134...

  • Page 75

    Appendix e scxi-1163 cabling © national instruments corporation e-3 scxi-1163 user manual scxi-1340 installation follow these steps to install the scxi-1340: 1. Make sure that the computer and the scxi chassis are turned off. 2. Install the scxi module in the chassis. 3. Plug the mounting bracket co...

  • Page 76: Lab-Lc Cable Assembly

    Scxi-1163 cabling appendix e scxi-1163 user manual e-4 © national instruments corporation scxi-1341 lab-nb, lab-pc, or lab-pc+ and scxi-1344 lab-lc cable assembly the scxi-1341 lab-nb, lab-pc, or lab-pc+ cable assembly connects a lab-nb, lab-pc, or lab-pc+ board to an scxi-1163 module. The scxi-1344...

  • Page 77

    Appendix e scxi-1163 cabling © national instruments corporation e-5 scxi-1163 user manual scxi-1341 and scxi-1344 installation follow these steps to install the scxi-1341 or scxi-1344: 1. Make sure that the computer and the scxi chassis are turned off. 2. Install the scxi module in the chassis. 3. C...

  • Page 78

    Scxi-1163 cabling appendix e scxi-1163 user manual e-6 © national instruments corporation table e-3. Scxi-1342 pin translations pc-lpm-16 pin pc-lpm-16 signal rear signal connector pin scxi-1163 use 1-2 aignd 1-2 no connect 3 ach0 3 no connect 4 ach8 4 no connect 5 ach1 5 no connect 6 ach9 6 no conn...

  • Page 79: Connection

    Appendix e scxi-1163 cabling © national instruments corporation e-7 scxi-1163 user manual dio-96, at-mio-16d, and at-mio-64f-5 board connection to use your scxi-1163 with a dio-96, at-mio-16d, or at-mio-64f-5 board, you need an nb5 cable. The nb5 cable is a ribbon cable with a 100-pin connector that...

  • Page 80

    Scxi-1163 cabling appendix e scxi-1163 user manual e-8 © national instruments corporation table e-4. Scxi-1163 and dio-96, at-mio-16d, and at-mio-64f-5 board pinout equivalences pin scxi-1163 rear signal connector dio-96 board equivalent at-mio-16d board equivalent at-mio-64f-5 board equivalent seri...

  • Page 81

    Appendix e scxi-1163 cabling © national instruments corporation e-9 scxi-1163 user manual table e-4. Scxi-1163 and dio-96, at-mio-16d, and at-mio-64f-5 board pinout equivalences (continued) pin scxi-1163 rear signal connector dio-96 board equivalent at-mio-16d board equivalent at-mio-64f-5 board equ...

  • Page 82

    Scxi-1163 cabling appendix e scxi-1163 user manual e-10 © national instruments corporation after step 1, the order of these steps is not critical; however, it is easier to locate the correct position for the mounting bracket with a module installed in the chassis. If you are attaching a cable to the...

  • Page 83

    Appendix e scxi-1163 cabling © national instruments corporation e-11 scxi-1163 user manual table e-5. Scxi-1348 pin translations dio-32f pin dio-32f signal rear signal connector pin scxi-1163 use 1 diod1 46 in (25) 2 diod4 40 in (28) 3 diod3 42 in (27) 4 diod0 48 in (24) 5 diod6 36 in (30) 6 diod7 3...

  • Page 84: Scxi-1180 Feedthrough Panel

    Scxi-1163 cabling appendix e scxi-1163 user manual e-12 © national instruments corporation scxi-1348 installation follow these steps to install the scxi-1348: 1. Make sure that the computer and the scxi chassis are turned off. 2. Install the scxi module to which the scxi-1348 will connect. 3. Connec...

  • Page 85

    Appendix e scxi-1163 cabling © national instruments corporation e-13 scxi-1163 user manual step 3 scxi-1180 breakout connector ribbon cable to front panel rear connector breakout connector from scxi-1340 threaded strip in rear of chassis step 4 rear panel figure e-3. Scxi-1180 rear connections note:...

  • Page 86

    Scxi-1163 cabling appendix e scxi-1163 user manual e-14 © national instruments corporation front panel connector front panel front threaded strip ribbon cable to rear and breakout connectors step 5 figure e-4. Scxi-1180 front panel installation scxi-1302 50-pin terminal block the scxi-1302 terminal ...

  • Page 87

    Appendix e scxi-1163 cabling © national instruments corporation e-15 scxi-1163 user manual 50-pin connector grounding screw thumbscrew cutout step 1 step 2 insert screwdriver in groove and rotate to pry open figure e-5. Cover removal scxi-1302 installation follow these steps to install the scxi-1302...

  • Page 88

    Scxi-1163 cabling appendix e scxi-1163 user manual e-16 © national instruments corporation scxi-1351 installation follow these steps to install the scxi-1351: 1. Make sure that the computer and the scxi chassis are turned off. 2. Install the scxi module in the chassis. 3. Connect the rear connector ...

  • Page 89

    Appendix e scxi-1163 cabling © national instruments corporation e-17 scxi-1163 user manual 4. Connect another ribbon cable to the chassis extender connector in the middle of the scxi-1350. 5. Plug the scxi-1350 into the back of the scxi module in the first chassis so that the module rear connector m...

  • Page 90

    Scxi-1163 cabling appendix e scxi-1163 user manual e-18 © national instruments corporation table e-6. Scxi-1343 pin connections (continued) rear signal connector pin scxi-1163 use connection serial parallel 20 no connect solder pad 21 no connect in (13) solder pad 22 no connect solder pad 23 no conn...

  • Page 91: Appendix F

    © national instruments corporation f-1 scxi-1163 user manual appendix f customer communication for your convenience, this appendix contains forms to help you gather the information necessary to help us solve technical problems you might have as well as a form you can use to comment on the product do...

  • Page 92: Technical Support Form

    Technical support form ___________________________________________________ photocopy this form and update it each time you make changes to your software or hardware, and use the completed copy of this form as a reference for your current configuration. Completing this form accurately before contacti...

  • Page 93

    Scxi-1163 hardware configuration form record the settings and revisions of your hardware and software on the line to the right of each item. Complete a new copy of this form each time you revise your software or hardware configuration, and use this form as a reference for your current configuration....

  • Page 94: Documentation Comment Form

    Documentation comment form national instruments encourages you to comment on the documentation supplied with our products. This information helps us provide quality products to meet your needs. Title: scxi-1163 user manual edition date: september 1994 part number: 320576-01 please comment on the com...

  • Page 95: Glossary

    © national instruments corporation glossary-1 scxi-1163 user manual glossary ___________________________________________________ prefix meaning value p- pico- 10- 12 n- nano- 10- 9 µ - micro- 10- 6 m- milli- 10- 3 k- kilo- 10 3 m- mega- 10 6 ˚ degrees Ω ohms +5 v (signal) +5 vdc source a amperes ac ...

  • Page 96

    Glossary scxi-1163 user manual glossary-2 © national instruments corporation msb most significant bit ram random-access memory reset* reset rms root mean square rtsi real-time system integration scxi signal conditioning extensions for instrumentation (bus) sdk software developer's kit sec seconds se...

  • Page 97: Index

    © national instruments corporation index-1 scxi-1163 user manual index numbers +5 v signal, 3-3, c-3 a address handler description, 4-2 register addresses, 4-2 selecting data register, 3-6 timing diagram, 2-21 writing to address handler, 2-21, 5-3 analog backplane protection, 3-7 at-mio board connec...

  • Page 98

    Index scxi-1163 user manual index-2 © national instruments corporation d d*/a signal scxibus connector, 3-3, c-3 writing to data register, 3-6 daqd*/a signal digital i/o signal connections, 2-17 reading from registers data register, 5-2 module id register, 2-23 status register, 2-24 rear signal conn...

  • Page 99

    Index © national instruments corporation index-3 scxi-1163 user manual scxi-1351 one-slot cable extender, e-16 unpacking the scxi-1163 module, 1-4 interface and routing circuitry, 3-4 to 3-5 intr* signal, scxibus connector, 3-3, cha3 j jumper configuration. See also module configuration; signal conn...

  • Page 100

    Index scxi-1163 user manual index-4 © national instruments corporation parts locator diagram jumper configuration, 2-2 scxi-1326 terminal block, 2-13 pc-lpm-16 cable assembly. See scxi-1342 pc-lpm-16 cable assembly. Physical specifications, a-1 pin assignments front connector, 2-9, d-2 rear signal c...

  • Page 101

    Index © national instruments corporation index-5 scxi-1163 user manual register selection and write procedure, 5-2 to 5-3 register writes, 5-1 to 5-3 scxibus to scxi-1163 rear signal connector pin equivalents, 5-2 scxi-1163 registers, 4-1 to 4-6 slot-select register, 4-8 status register description,...

  • Page 102

    Index scxi-1163 user manual index-6 © national instruments corporation selecting serial mode with jumper w6, 2-6 serial data timing diagram, 2-20 serial i/o signal connections, rear signal connector, 2-17 to 2-18, b-3 serial peripheral interface (spi) bus communications. See communication signals. S...

  • Page 103

    Index © national instruments corporation index-7 scxi-1163 user manual equivalents for rear signal connector, 3-4 pin assignments, 3-2 signal descriptions, 3-3 to 3-4 timing requirements and communication protocol. See communication signals. U unpacking the scxi-1163 module, 1-4 v v+ signal, 3-3, c-...