    Installation manual do cu ment : m- 180.2- am6000- eng is sue : 10/1999 rev. : b.2 am-6000 analog fire alarm con trol panel no ti fier ita lia a di vi sion of pitt way corporation.

  • Page 2: Index

    Index » this new re vi sion, b.2, in clu des an ap pen dix on page 27 about “am- 6000 power sup ply”. Am-6000 exploded view 1 cabinet 2 mounting the system boards to the “ica-6” chassis 3 front panel indication & keypad 4 “be-600a” main board layout 5 connector cna on “be-600 a” board 6 connector cn...

  • Page 3

    Am-6000 exploded view page 1 installation manual am-6000-60002.Vp notifier italia rev. B.1 doc. M-180.2-am6000-eng attenzione 230 v attenzione 230 v 1 26 1 1 12 12 1 26 1 26 1 26 avps 6 board for “3 a” aux. Power supply complete of transformer be 600 a main board including support and transformer cv...

  • Page 4

    Cabinet am-6000-60001.Vp installation manual page 2 doc. M-180.2-am6000-eng rev. B.1 notifier italia 65 mm 405 mm 535 mm 65 mm 75 mm 55 mm 46.5 mm 30.5 mm 35 mm 30 mm 30 mm 35 mm 35 mm 75 mm 75 mm 35 mm 35 mm 35 mm 35 mm 35 mm 35 mm 105 mm 105 mm 45 mm 45 mm 365 mm 440 mm 200 mm 30 mm . . 4 mounting...

  • Page 5

    Mounting the system boards to the “ica-6" chassis installing the ica-6 chassis 1 - screw the two spacers 4 x 45 mf (a) to the plate. 2 - secure the metal plaquette (b) with the two screws 4 x 8 tc (c). 3 - insert the chassis on the proper hinges (d). Then push the chassis inward toward the bottom of...

  • Page 6

    Front panel indication & keypad dimensions • front panel including the hinge = 482 x 266 mm (19" - 6 units). • mounting holes wheel-base : horizontal = 465 mm. - vertical = 190 mm. Am-6000-60001.Vp installation manual page 4 doc. M-180.2-am6000-eng rev. B.1 notifier italia no tifier division of pitt...

  • Page 7

    “be-600 a” main board layout page 5 installation manual am-6000-60001.Vp notifier italia rev. B.1 doc. M-180.2-am6000-eng 1 26 1 1 12 12 led indicating trouble condition (line 1-4) cpu-reset push-button led indicating alarm condition (line 1-4) connector for sib 600 serial board interconnection crt/...

  • Page 8

    Connector cna on “be-600 a” board connector cn0 on “be-600 a” board note: ( * ) these two outputs cannot operate simultaneously. The operator must select the type of connection to employ, from the control panel main programming menu (refer to am-6000 programming manual). Serial printer connections a...

  • Page 9

    Connector cn1 on “be-600 a” board » note : 1) if a line is programmed as style 6 (loop line), terminals a are the outwards and terminals b are the return. 2) for each line connect the shield to appropriate sc terminal. 3) alarm and trouble controls : free voltage contacts. Use to drive loads in dc o...

  • Page 10

    “bps-600" board for 230 v mains wiring am-6000-60001.Vp installation manual page 8 doc. M-180.2-am6000-eng rev. B.1 notifier italia attenzione 230 v attenzione 230 v led indicating battery-charger operating led indicating auxiliary power supply operating led indicating control panel powered battery ...

  • Page 11

    Wiring the “be-600 a” main board external devices page 9 installation manual am-6000-60001.Vp notifier italia rev. B.1 doc. M-180.2-am6000-eng 1 26 1 1 12 12 rs 232 rx rs 232 rx d.3a/200v d.1n 4004 r.1k5 1/2w r.1k5 1/2w rs 232 tx rs 232 tx gnd is general trouble signal serial line: rs 232 crt/pc or ...

  • Page 12

    Detector and module wiring typical loop line (style 6) am-6000-60001.Vp installation manual page 10 doc. M-180.2-am6000-eng rev. B.1 notifier italia b501 detector base to employ with intelligent detectors separated branches to other loop device - connector cn1 > be 600 a board > lib 600 board shield.

  • Page 13

    “lib-600" expansion board layout page 11 installation manual am-6000-60001.Vp notifier italia rev. B.1 doc. M-180.2-am6000-eng 1 26 detection line connector led indicating trouble on expansion lines led indicating alarm on expansion lines status leds concerning the detector lines serial communicatio...

  • Page 14

    Connector cn1 on “lib-600" expansion board » note : 1) if a line is programmed as style 6 (loop line), terminals a are the outwards and terminals b are the return. 2) for each line connect the shield to appropriate sc terminal. 3) alarm and trouble controls : free voltage contacts. Use to drive load...

  • Page 15

    “avps-6" aux. Power supply board page 13 installation manual am-6000-60001.Vp notifier italia rev. B.1 doc. M-180.2-am6000-eng product identification connector for earth link > to the be 600 a main board fuse 3,15 a auxiliary power supply output led indicating the aux. Power supply operating interfa...

  • Page 16

    “dia-6":front panel display and keypad interface layout am-6000-60001.Vp installation manual page 14 doc. M-180.2-am6000-eng rev. B.1 notifier italia lcd display contrast adjustment product identification factory code number connector for keypad connector for be 600 a main board interconnection wd t...

  • Page 17

    Analog identification system components detector and module communication lines the am-6000 system communicates with intelligent and addressable, monitor and control devices through a 2-wire line. The lines can be wired to meet the requirements of an nfpa style 4, style 6 or style 7. The peripheral ...

  • Page 18

    Class “a” wiring circuit and line isolators functions in accordance with nfpa style 7 signaling line circuit » note: the number of addressable devices between iso-x modules must not exceed 25 devices. Operation by separating each group of slc loop devices, with a pair of iso-x trouble isolator modul...

  • Page 19

    Notes about loop wiring class “a” wiring total length of the slc loop pair (from the control panel output and back to the control panel) cannot exceed 3000 meters. The dc resistance of the slc loop pair cannot exceed 40 ohm. The measurement must be made by disconnecting channels a and b at the contr...

  • Page 20

    Class “b” wiring branch resistance short the termination point of one branch at a time and measure the dc resistance, from the beginning of the channel to the end of that particular branch. The total dc resistance from panel to branch end cannot exceed 40 ohm. Repeat the procedure for all remaining ...

  • Page 21

    Analog system lines test procedure q before powering the control panel lines, verify the following values: » note : digital voltage meter needed a) line resistance short positive and negative of one end of the system. Place tester probes on the (+) and (-) sides of the line. The resistance cannot ex...

  • Page 22

    Cable requirements type of cable: 2-conductor twisted-shielded cable. Sections concerning the line total lenght (for the line “style 6", the operator must consider the loop lenght) which cannot exceed 3000 meters and whose resistance must be lower than 40 ohm. Example: • up to 500 mt. - cable 2 x 0....

  • Page 23

    Slc loop shield wiring a) note: maintain the continuity of the shield wire throughout the loop, but do not connect to any devices. Connect the shield wire to the outside of the control panel cabinet and the cabinet to earth. B) note: in this case, do not allow the shield drain or shield foil to touc...

  • Page 24

    Connector cn2 on “sib-600” optional board » note : for wiring of maximum 15 meters use 232 serial line (terminals 4-5-6) for wiring exceeding 15 meters use 485 serial line with it-485 interface (terminals 7-11) am-6000-60001.Vp installation manual page 22 doc. M-180.2-am6000-eng rev. B.1 notifier it...

  • Page 25

    The 220 vac power supply line the am6000 control panel requires connection to a separate 220 vac 50 hz line, which must be labeled “fire alarm”. No other equipment may be powered from the circuit employed for the fire alarm system. Overcurrent protection for this circuit must comply with local norma...

  • Page 26

    Main power supply current draw calculation the main power supply must be capable of powering, all internal system devices (and all external devices) continuously during stand-by condition, which means non-fire alarm condition. Use table 2 to determine the stand-by load. Use table 3 to determine the ...

  • Page 27

    Alarm condition current load the table 3 allows the system designer to determine the current load that must be supported by the main power supply during an alarm condition. The total current drawn from the main power supply in alarm condition cannot exceed 3.0 amps. Enter the number of devices, for ...

  • Page 28

    Battery capacity calculation the table 4 allows to determine the size of the batteries needed to support both stand-by condition and five minutes of alarm operation. Table 4 : battery current load required am-6000-60003.Vp installation manual page 26 doc. M-180.2-am6000-eng rev. B.1 notifier italia ...

  • Page 29

    Ap pen dix: am- 6000 power sup ply block diagram in put and out put • mains in put in put vol ta ge 230 vac with 5a pro tec tion fuse • mains tran sfor mer n° 2 39 vac 3a au xi lia ri es the first au xi lia ry powers the rec ti fi ca tion cir cuit of the main power sup ply with a 4a pro tec tion fus...

  • Page 30

    • power sup ply troub le. Any power sup ply troub le ge ne ra te a sy stem troub le and a ge ne ral troub le si gnal; the ge ne ral troub le re lay is de- ac ti va ted and the buz zer so und. • mains troub le. It an nun cia tes that the mains vol ta ge is less than 50 vac. In case of troub le for ma...

  • Page 31

    • bat te ry char ger fai lu re or over load. It in di ca tes that the bat te ry char ger out put vol ta ge is less than 21 vdc • di scon nected bat te ry or bat te ry fuse troub le. A pe rio di cal test is exe cu ted only if the 220 mains is con nected (vol ta ge >= 170 vac) and the main vol ta ge >...

  • Page 32: B.2

    All rights re ser ved. All spe ci fi ca tions are sub ject to chan ge wit hout no ti ce. De li ve ry ti mes de pend on pro duct avai la bi li ty. No ti fier ita lia s.R.L. Via grandi, 22 - 20097 san do na to mi la ne se (mi) tel. : 02/51897.1 (isdn) fax : 02/5189730 e- mail : no ti fier- i ta lia@in...