    Power supply unit hls ps series hlsps25-xp and hlsps50-xp user manual information in this document is subject to change without notice 8 april 2010 mn-dt-1305i_b.

  • Page 2

    Hls ps25 & hls ps50 user manual mn-dt-1305i_b 2.

  • Page 3: Contents

    Hls ps25 & hls ps50 user manual mn-dt-1305i_b 3 contents 1 hls ps series installation 4 1.1 checking the hls ps for damage 4 1.2 pre-installation check list 5 1.3 transient protection 5 1.4 cleaning 5 1.5 back box hls ps fixing 6 2 functions and indicators 7 2.1 hls ps25 and hls ps50 characteristics...

  • Page 4: Installation

    Hls ps25 & hls ps50 user manual mn-dt-1305i_b 4 1. Power supplies hls ps series installation the hls ps series is easy to install providing the recommended procedures described in this manual are followed. Follow all installation instructions described in this manual. Theses instructions must be und...

  • Page 5

    Hls ps25 & hls ps50 user manual mn-dt-1305i_b 5 1.2 pre-installation check list before selecting the location for the hls ps series, do make sure that: a) the ambient temperature is in the range: -5 ºc to 40 ºc b) the relative humidity is bellow: 93% (non-condensing) c) do not locate the equipment w...

  • Page 6

    Hls ps25 & hls ps50 user manual mn-dt-1305i_b 6 1.5 back box hls ps series fixing when a suitable location has been found for installing the hls ps series, proceed as follows: 1. Hold the back box assembly in the required position against the wall and mark the position of the fixing holes, while ens...

  • Page 7

    Hls ps25 & hls ps50 user manual mn-dt-1305i_b 7 2. Hls ps functions and indicators front panel: 1 2 fus bat fault low bat no bat bat test bat ch bat dis in alarm 321087 cpu max. Legend: => on => fault => main supply fault => battery fault => battery charger fault => output 1 fault => output 2 fault ...

  • Page 8

    Hls ps25 & hls ps50 user manual mn-dt-1305i_b 8 2.1 hls ps25 / hls ps50 characteristics these power supplies units are designed to comply with the requirements of en54-4 in order to provide fire control systems with backup supply. The hls ps series operates at 115/230 vac and 50/60 hz. Both power su...

  • Page 9

    Hls ps25 & hls ps50 user manual mn-dt-1305i_b 9 2.2 battery dip sw2 allows selecting the maximum current of battery load, depending on the batteries inside the power supply unit box. With dip sw2 in on position (up), 7amp/h batteries can be charged at 300ma. When dip sw2 is in off position (down), 2...

  • Page 10

    Hls ps25 & hls ps50 user manual mn-dt-1305i_b 10 2.4 control unit connections: the following 4 connectors are placed at the top of the control unit: fault (c) fault relay common fault (nc) normally closed contact fault (no) normally open contact the fault relay may be linked to an analogue input mod...

  • Page 11

    Hls ps25 & hls ps50 user manual mn-dt-1305i_b 11 the following is placed at the bottom of the control unit: in bat batteries (+) in bat batteries (-) test the test button allows performing a led test and makes a real test of batteries forcing them to supply current of 1a approx. For a minute. In cas...

  • Page 12

    Hls ps25 & hls ps50 user manual mn-dt-1305i_b 12 2.5 indicator leds: on led this led is on when the control unit is powered. Fault led yellow led that is on in case of a power supply fault. When this indication is activated, the c and nc contacts of the fault relay will be closed. Mains supply fault...

  • Page 13

    Hls ps25 & hls ps50 user manual mn-dt-1305i_b 13 output 1 fault led indicates that the output 1 is not powered. Output 2 fault led indicates that the output 2 is not powered. Earth fault led indicates an earth fault if one of the wirings (+) or (-) is linked to earth. If j3 is not connected, there w...

  • Page 14: Specification

    Hls ps25 & hls ps50 user manual mn-dt-1305i_b 14 3. Specification dimensions: 377 mm (w) x 408 mm (h) x 92 mm (d). Power supply wattage: 130 w (hlsps50) y 65 w (hlsps25). The hlsps50 power supply has a total of 5amp and 300ma to 600ma of them are dedicated to charge batteries. Input voltage: 115 - 2...

  • Page 15

    Hls ps25 & hls ps50 user manual mn-dt-1305i_b 15.

  • Page 16

    Hls ps25 & hls ps50 user manual mn-dt-1305i_b 16 honeywell life safety iberia c/pau vila 15-19 e-08911 badalona (barcelona) spain tel.: +34 93 4973960 fax: +34 93 4658635 www.Honeywelllifesafety.Es honeywell life safety: charles avenue, burgess hill, rh15 9uf west sussex tel.: +44 (0) 1444 230 300 e...