Notifier IFS-2600 Operation, Installation, And Maintenance Manual

Summary of IFS-2600

  • Page 1

    Ifs-2600 fire indicator panel o peration , i nstallation & p rogramming m anual doc-01-009 ecn11-0012 19/04/2011 rev: 1.02.

  • Page 2: Documentation Feedback

    Documentation feedback your feedback helps us keep our documentation up to date and accurate. If you have any comments or suggestions about our printed manuals you can email us. Please include the following information: product name and version number (if applicable) manual part number and revision ...

  • Page 3: Installation Precautions

    Installation precautions adherence to the following will aid in problem-free installation with long-term reliability: warning - several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment...

  • Page 4: Table Of Contents

    Ifs-2600 fire indicator panel section 1 about this manual doc-01-009 table of contents section 1 - about this manual ................................................................ 1 1.1. Notes, cautions and warnings..................................................................... 1 section 2 -...

  • Page 5

    Ifs-2600 fire indicator panel section 1 about this manual doc-01-009 5.4. Global options & programming...................................................................46 5.5. Print programming data..............................................................................48 section 6 appendix ....

  • Page 6

    Ifs-2600 fire indicator panel section 1 about this manual doc-01-009 1 section 1 - about this manual 1.1. Notes, cautions and warnings this manual contains notes, cautions and warnings to alert the reader as follows: note: supplement information for a topic such as tips and references. Caution: info...

  • Page 7

    Ifs-2600 fire indicator panel section 2 system overview doc-01-009 2 section 2 - system overview 2.1. Overview the overall intent of a fire protection system is to provide warning should smoke or a fire be detected. The systems can be configured to alert occupants of the building, advise fire brigad...

  • Page 8

    Ifs-2600 fire indicator panel section 2 system overview doc-01-009 3 2.3. System description the basic ifs-2600 fire indicator panel (fip) consists of quantity description 1 wall mounting cabinet with manual call point 1 main control board (located on inside of inner door) – cpu – ni-2004-01 1 main ...

  • Page 9

    Ifs-2600 fire indicator panel section 2 system overview doc-01-009 4 2.5. Lcd display in addition to the led's a 16-character x 2-line liquid crystal display is provided to indicate system status, changing events and programming information. Any keystroke or event will actuate the backlighting on th...

  • Page 10

    Ifs-2600 fire indicator panel section 2 system overview doc-01-009 5 2.6. Keypad the custom-designed 30 key membrane keypad is the users interface to accessing all zone and global functions of the ifs-2600.These 30 keys consist of; figure 2-1, ifs-2600 keypad 1. Five specialised single-stroke fire f...

  • Page 11

    Ifs-2600 fire indicator panel section 2 system overview doc-01-009 6 qty descriptor colour function buzzer 1 mains on green illuminates when there is ac supply to the panel. 1 battery fault yellow illuminates if the battery fails a battery test. Illuminates if batteries are disconnected >30 seconds....

  • Page 12: Section 3 - Operation

    Ifs-2600 fire indicator panel section 3 operation doc-01-009 7 section 3 - operation 3.1. Suggested alarm procedure the following is a suggested alarm procedure for use by building fire officers or duty wardens. The fire indicator panel is designed for use by qualified fire fighters and it is strong...

  • Page 13

    Ifs-2600 fire indicator panel section 3 operation doc-01-009 8 isolate isolate the isolate function prevents the transmission of alarms or faults from the zones to the master alarm facility. The isolate key only operates on zones with acknowledged alarms. Bell isolate ext bell isol pressing the "ext...

  • Page 14

    Ifs-2600 fire indicator panel section 3 operation doc-01-009 9 for ifs-2005 & ifs-2006 boards: this function tests the performance of the batteries fitted to the system. Pressing this button will initiate a battery test as specified in as4428. The test will temporarily disconnect the batteries from ...

  • Page 15

    Ifs-2600 fire indicator panel section 3 operation doc-01-009 10 for the duration of walk test mode, all zones are changed to output configuration #2 (indicate and ring bells only) and all zones are set to type #1 (standard latching, 2 second). If the bells are not required to ring during walk test, ...

  • Page 16

    Ifs-2600 fire indicator panel section 3 operation doc-01-009 11 3.4. Zone operator function zone functions are those relating specifically to the detection zones. Following is an explanation of their operation and the keystrokes required to perform the function required. Alarm test alarm test # ent ...

  • Page 17

    Ifs-2600 fire indicator panel section 3 operation doc-01-009 12 fault test fault test # enter the fault test function momentarily disconnects the detection zone(s) under test and simulates the worst- case condition for fault. A resistor load equal to worst case fault is placed on the zone continuous...

  • Page 18

    Ifs-2600 fire indicator panel section 3 operation doc-01-009 13 if a correct entry is made, the zone is immediately isolated. If the zone is already in alarm, all of its alarm outputs are isolated and indicators remain visible. If the "all" function is performed, all zones will be isolated, regardle...

  • Page 19

    Ifs-2600 fire indicator panel section 3 operation doc-01-009 14 3.5. Standard outputs output type description standby change over relay contact normally energised relay: will de- energise if system volts fall below 21v. This usually means ac has failed and batteries are getting low. I.E. Panel is ab...

  • Page 20

    Ifs-2600 fire indicator panel section 3 operation doc-01-009 15 3.6. Relay expansion boards the maximum number of boards that can be fitted is eight (i.E.: 64 relays). Each board contains 8 change-over relay outputs. Relays can be programmed to simulate: brigade alarm relay #1 brigade alarm relay #2...

  • Page 21: Section 4 - Installation

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 16 section 4 - installation 4.1. Compatible detectors make model type model number system sensor thermal type a 5451aus system sensor thermal type a 51a51 system sensor thermal type b 4451aus system sensor thermal type b 51b51 system se...

  • Page 22

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 17 panelect thermal type d pfs-d panelect smoke ionisation pfs-i panelect smoke ionisation pfs-i , mkii panelect smoke photo optical pfs-p panelect smoke photo optical pfs-p, mkii table 4-1, compatible detectors 4.2. Specification gener...

  • Page 23

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 18 specification for ifs-2608 & ifs-2624: cabinet zinc sealed steel 1.6mm, powder coated hinged inner & outer door outside dimensions 2608 (8 zones) 394mm h x 390mm w x 180mm d* 2624 (24 zones) 750mm h x 390mm w x 180mm d* *note: the de...

  • Page 24

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 19 cab 650 mechanical dimensions: figure 4-1, cab650 dimensions cab 900 mechanical dimensions: figure 4-2, cab900 dimensions.

  • Page 25

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 20 4.3. Overview of ifs-2600 system equipment ni-2025-01 disp pcb816 mimic panel 12v battery 12v battery + + - - main processor board main termination board serial printer power supply unit 240v isol s/w mains supply 240 v ac ni-2004-01...

  • Page 26

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 21 4.4. Power supply ifs-2600 panels use two kinds of power supply with different set of boards. Power supply (brick power supply – nps-2/nps-5/nps-11): this type of power supply is used in new ifs-2600 panels in conjunction with ni-202...

  • Page 27

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 22 power supplies nps-2, nps-5, nps-11 ac operational voltage nps-2 ac 100-240v; 50/60hz; 1.3a nps-5 ac 100-240v; 50/60hz; 2.5a nps-11 ac 100-240v; 50/60hz; 5a output current @ 27.3v (max) nps-2 2.6 amp nps-5 5.6 amp nps-11 11.7 amp out...

  • Page 28

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 23 4.4.2. Power supply ratings & settings for ifs-2005 & ifs-2006 boards figure 4-5, power supply schematics (ifs-2004, ifs-2005 & ifs-2006 boards) ifs - 2005 12v battery 12v battery + + - - main processor board main termination board 2...

  • Page 29

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 24 panel power supply with batteries disconnected and no alarms present, measure voltage across the 0v and main test points on the 2006 power supply board and, if necessary, adjust the multi-turn potentiometer vr2 until voltage is 26.5v...

  • Page 30

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 25 important notes: this applies to ifs-2005/ifs-2006 boards without ecn09-034 modification!! When using external power supply, jp1 link on ifs2006e must be fitted to enable external psu monitoring. If this supply is used to power a ni-...

  • Page 31

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 26 4.5. Technical description general the ifs-2600 in its most basic form comprises of three boards, the main control board, the main termination board and the power supply board. The main control board contains the microprocessor, epro...

  • Page 32

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 27 azf description the azf's on the ifs-2600 are monitored and scanned by custom thick film hybrids. These hybrid ic's significantly reduce the possibility of false alarms and improve product efficiency and reliability. The total alarm ...

  • Page 33

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 28 manual call point (mcp) for ifs-2005 boards: panel mcp connection is achieved by wiring from the zone, to the mcp, to the mcp loop then out to the field with the eol across the last detector. The mcp is the first device on the circui...

  • Page 34

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 29 ifs-2600 mimic mimic outputs: a mimic output is standard on all ifs-2600 panels. This output mimics the status of all alarm zones fitted on the panel to a remote mimic panel in the building. The four (4) wire serial mimic decoder boa...

  • Page 35

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 30 programming by computer programming of the zones, relays, global functions and time can be set with the dos based program “2600/sw” using the printer port (cannot be used with windows xp). After the cable is installed, the program ca...

  • Page 36

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 31 fault threshold comparator tp6 (for ifs-2005 & ifs-2006 boards only) with the panel in the quiescent mode, measure and take note of the internal 24v dc power supply as above. Measure the voltage between system 0v and tp6. Adjust mult...

  • Page 37

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 32 ifs804 - jp1-7 zone board addressing jumper jp1 to jp7 on zone expansion board ifs-804 selects the addressing for the zones. Place jumper in link position for the appropriate 8 zones to which the expansion board applies figure 4-9, z...

  • Page 38

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 33 4.6. Placing into operation suitably qualified technicians must install the panel. The following check procedures are recommended after every installation and prior to initial power-up. A thorough visual inspection should be made to ...

  • Page 39

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 34 power up checklist ensure batteries are disconnected turn mains switch to "on" the "mains on" led should light allow 15 seconds for the panel to perform its start up tests connect batteries pulsing heartbeat on the termination board ...

  • Page 40

    Ifs-2600 fire indicator panel section 4 installation doc-01-009 35 fault record fault correction date tests satisfactorily completed. Tested by _______________________________ signature _______________________________ date of test ____________________________ if all faults have been rectified and al...

  • Page 41: Section 5 - Programming

    Ifs-2600 fire indicator panel section 5 programming doc-01-009 36 section 5 - programming 5.1. Program mode press the following buttons in order shown to enter programming mode. Previous → next → select → exit → enter programming mode the liquid crystal display will display all messages and prompts ...

  • Page 42

    Ifs-2600 fire indicator panel section 5 programming doc-01-009 37 relays type mapping isolate relay ancillary output (acf) brigade relay #1 brigade relay #2 fault relay mains fail relay general alarm relay bell output door holder relay map - and (00)(00)(00)(00)(00) map - or (00)(00)(00)(00)(00) map...

  • Page 43

    Ifs-2600 fire indicator panel section 5 programming doc-01-009 38 exit programming mode save changes yes (no) use the "next" & "previous" keys to scroll through "yes" & "no". Once the desired option has been highlighted, pressing the "select" button will select it. Highlighting "yes" and pressing "s...

  • Page 44

    Ifs-2600 fire indicator panel section 5 programming doc-01-009 39 5.2. Zone options & programming 5.2.1. Zone options description of alarm zone types different zone types can be selected using the programming mode. Each zone can be selected as any one of the following: type description input delay 1...

  • Page 45

    Ifs-2600 fire indicator panel section 5 programming doc-01-009 40 if an alarm is received, the detector is reset again and timer#2 is also reset. This monitoring continues until the 60-second timer (timer#1) has elapsed and then the next alarm signal will trip the zone into "full alarm". This is the...

  • Page 46

    Ifs-2600 fire indicator panel section 5 programming doc-01-009 41 zone type zone # all type std latching use the "next" & "previous" keys to scroll through once the desired option has been highlighted, pressing the "select" button will select it. Making a selection or pressing "exit" will return to ...

  • Page 47

    Ifs-2600 fire indicator panel section 5 programming doc-01-009 42 5.3. Relay options & programming 5.3.1. Relay options optional relays can be programmed to simulate: isolate relay acf output brigade relay #1 brigade relay #2 fault relay mains fail relay general alarm relay bell output door holder r...

  • Page 48

    Ifs-2600 fire indicator panel section 5 programming doc-01-009 43 and mapping and mapping allows the relay output to be programmed for a combination of up to 5 zones, and only after they ‘all’ go into alarm, will the relay operate. And mapping is useful for applications which have special shutdowns,...

  • Page 49

    Ifs-2600 fire indicator panel section 5 programming doc-01-009 44 5.3.2. Relay programming select relay # select relay# (all) use the "next" & "previous" keys to scroll through "all" "1" "2" "3” up to 64 and then wrap around. Once the desired relay number has been selected, pressing the "select" but...

  • Page 50

    Ifs-2600 fire indicator panel section 5 programming doc-01-009 45 relay mapping relay #1 map (00) 00 00 00 00 ** relay mapping can only be selected if the relay is set as a map type. These 5 entry fields represent the zone numbers that the relay is to be mapped to and will be activated from. Use the...

  • Page 51

    Ifs-2600 fire indicator panel section 5 programming doc-01-009 46 5.4. Global options & programming there are four global options that can be programmed: (acf) avf relay time use the "next","previous" & "select" keys to select. Pressing "exit" will return to "main menu". Ancillary control facility (...

  • Page 52

    Ifs-2600 fire indicator panel section 5 programming doc-01-009 47 alarm verification facility (avf) alarm verification (avf) is a facility used to minimise false alarms. Avf only applies to the zones programmed for the avf function. Global programmable options: alarm verification 1 disabled 2 2 minu...

  • Page 53

    Ifs-2600 fire indicator panel section 5 programming doc-01-009 48 use the "next" & "previous" keys to change the first relay to start from, together with the matching zone. Use the “enter” key to toggle between the two and press “select” once finalised. “exit” will abort unity map. This function wil...

  • Page 54: Section 6 Appendix

    Ifs-2600 fire indicator panel section 6 appendix doc-01-009 49 section 6 appendix 6.1. Appendix a glossary of terms as-4428.1 australian standard for; - automatic fire detection and alarm systems control and indicating equipment. As-4428.5 australian standard for; - automatic fire detection and alar...

  • Page 55

    Ifs-2600 fire indicator panel section 6 appendix doc-01-009 50 6.2. Appendix b summary of terminations & cautions mcp loop used for the looping of the manual call point to a particular zone chosen for indication. This is achieved by wiring from the zone, to the mcp, to the mcp loop then out to the f...

  • Page 56

    Ifs-2600 fire indicator panel section 6 appendix doc-01-009 51 mimic data & clock these outputs together with the mimic power terminals are used to serially communicate with the mimic panels when fitted. Eol resistor is not required on these lines. (refer to section 4.5 for more details.) ac input (...

  • Page 57

    Ifs-2600 fire indicator panel section 6 appendix doc-01-009 52 6.3. Appendix c ifs-2600 programmed options global system parameters date: / / latch nd non-latch nd latch ne non-latch ne acf output disabled 2 min 3 min 4 min 5 min alarm verification (avf) notes: programmed by place an "x" in the appr...

  • Page 58

    Ifs-2600 fire indicator panel section 6 appendix doc-01-009 53 zone type programming date: / / 1 2 3 4 5 6 7 8 9 10 azf no. Std std n/l n/l t/d t/d t/d t/d t/d t/d 2s avf 2s 20s 10s 20s 30s 40s 50s 60s 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 place an "x...

  • Page 59

    Ifs-2600 fire indicator panel section 6 appendix doc-01-009 54 1 2 3 4 5 6 7 8 9 10 azf no. Std std n/l n/l t/d t/d t/d t/d t/d t/d 2s avf 2s 20s 10s 20s 30s 40s 50s 60s 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 place an "x" in the appropriate bo...

  • Page 60

    Ifs-2600 fire indicator panel section 6 appendix doc-01-009 55 zone output programming date: / / azf no. Indicate i-bell ib- general ibg- acf ibga- br1 ibga- br2 ibga- br1&br2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 place an "x" in the appropriate box =...

  • Page 61

    Ifs-2600 fire indicator panel section 6 appendix doc-01-009 56 azf no. Indicate i-bell ib- general ibg-acf ibga- br1 ibga- br2 ibga- br1&br2 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 place an "x" in the appropriate box = default.

  • Page 62

    Ifs-2600 fire indicator panel section 6 appendix doc-01-009 57 relay output mapping date: / / mapping rly iso acf br1 br2 flt mains fail gen bell d/h and or flt iso iso/ flt do- or re- set 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 place an "x" in the appr...

  • Page 63

    Ifs-2600 fire indicator panel section 6 appendix doc-01-009 58 mapping rly iso acf br1 br2 flt mains fail gen bell d/h and or flt iso iso/ flt do- or re- set 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64.

  • Page 64

    Ifs-2600 fire indicator panel technical drawings doc-01-009 59 6.4. Technical drawings 6.4.1. System sensor conventional detector connection diagram 1 1 2 2 3 3 4 4 d d c c b b a a rev size drg. No. Title sheet: drawn/ traced engineer design approved this drawing must not be used for construction un...

  • Page 65

    Ifs-2600 fire indicator panel technical drawings doc-01-009 60 6.4.2. Hochiki conventional detector connection diagram 1 1 2 2 3 3 4 4 d d c c b b a a rev size drg. No. Title sheet: drawn/ traced engineer design approved this drawing must not be used for construction unless signed as approved 7 colu...

  • Page 66

    Ifs-2600 fire indicator panel technical drawings doc-01-009 61 6.4.3. Ancillary connection diagram ifs - 2600 typical ancillary connection.

  • Page 67

    Ifs-2600 fire indicator panel technical drawings doc-01-009 62 6.4.4. Ase connection diagram 1 1 2 2 3 3 4 4 d d c c b b a a rev size drg. No. Title sheet: drawn/ traced engineer design approved this drawing must not be used for construction unless signed as approved 7 columbia court, norwest busine...

  • Page 68

    Ifs-2600 fire indicator panel technical drawings doc-01-009 63 6.4.5. Mimic connection diagram 1 1 2 2 3 3 4 4 d d c c b b a a rev size drg. No. Title sheet: drawn/ traced engineer design approved this drawing must not be used for construction unless signed as approved 7 columbia court, norwest busi...

  • Page 69

    Ifs-2600 fire indicator panel technical drawings doc-01-009 64 6.4.6. Dual fan connection diagram 1 1 2 2 3 3 4 4 d d c c b b a a rev size drg. No. Title sheet: drawn/ traced engineer design approved this drawing must not be used for construction unless signed as approved 7 columbia court, norwest b...

  • Page 70

    Ifs-2600 fire indicator panel technical drawings doc-01-009 65 6.4.7. Exhaust fan connection diagram 1 1 2 2 3 3 4 4 d d c c b b a a rev size drg. No. Title sheet: drawn/ traced engineer design approved this drawing must not be used for construction unless signed as approved 7 columbia court, norwes...

  • Page 71

    Ifs-2600 fire indicator panel technical drawings doc-01-009 66 6.4.8. Supply fan connection diagram 1 1 2 2 3 3 4 4 d d c c b b a a rev size drg. No. Title sheet: drawn/ traced engineer design approved this drawing must not be used for construction unless signed as approved 7 columbia court, norwest...

  • Page 72

    Ifs-2600 fire indicator panel technical drawings doc-01-009 67 6.4.9. Smoke spill fan connection diagram 1 1 2 2 3 3 4 4 d d c c b b a a rev size drg. No. Title sheet: drawn/ traced engineer design approved this drawing must not be used for construction unless signed as approved 7 columbia court, no...

  • Page 73

    Ifs-2600 fire indicator panel technical drawings doc-01-009 68 6.4.10. 10w evac connection diagram 1 1 2 2 3 3 4 4 d d c c b b a a rev size drg. No. Title sheet: drawn/ traced engineer design approved this drawing must not be used for construction unless signed as approved 7 columbia court, norwest ...

  • Page 74

    Notes.

  • Page 75

    Notes.

  • Page 76

    New south wales (head office) 9 columbia way baulkham hills nsw 2153 ph +61 (02 9899-4155 fax +61 (0)2 9899-4156 queensland 24 potts street east brisbane, qld 4169 ph +61 (0)7 3391 5777 fax +61 (0)7 3391 5800 victoria 32 lambert street richmond, vic 3121 ph +61 (0)3 9421 5552 fax +61 (0)3 9421 5553 ...