Notifier LCD2-80 Instruction Manual

Manual is about: Liquid Crystal Display

Summary of LCD2-80

  • Page 1

    B1 p/n 53242:b1 ecn 12-0233 document 53242 10/25/2012 rev: liquid crystal display lcd2-80 instruction manual.

  • Page 2

    2 lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 fire alarm system limitations while a fire alarm system may lower insurance rates, it is not a substitute for fire insurance! An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull sta- tions, audible wa...

  • Page 3

    Lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 3 installation precautions adherence to the following will aid in problem-free installation with long-term reliability: warning - several different sources of power can be connected to the fire alarm control panel. Dis- connect all sources of powe...

  • Page 4

    4 lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 software downloads in order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and prog...

  • Page 5: Table of Contents

    Lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 5 table of contents section 1: product overview ................................................ 6 1.1: ul 864 compliance.............................................................................6 1.1.1: products subject to ahj approval ..........

  • Page 6

    6 lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 section 1: product overview the lcd2-80 alphanumeric display module is an ancillary device used by notifier fire alarm control panels including nca-2, nfs-320, nfs2-640, and nfs2-3030. The product operates in terminal mode, where it acts as a di...

  • Page 7

    Features product overview lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 7 1.1.2 programming features subject to ahj approval this product incorporates field-programmable software. The features and/or options listed below must be approved by the local ahj. 1.2 features • 80-character backlit l...

  • Page 8

    Product overview board layout 8 lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 1.3 board layout 1.4 power specifications current consumption @ 24 vdc • normal (no activity): 84 ma • lamp test: 105 ma • ac fail (piezo on): 45 ma • ac fail (piezo off): 28 ma • alarm (piezo on): 98 ma • alarm (pi...

  • Page 9

    Connections product overview lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 9 1.5 connections 1.5.1 terminal connections - tb1 and tb2 these connections provide 24 vdc operating power (tb1) and eia-485 connections (tb2) to the lcd2-80. The connections must be power-limited. Power connections a...

  • Page 10

    Product overview switches and indicators 10 lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 figure 1.3 supplying power to the lcd2-80 1.5.2 nup connection - j3 connection for standard nup cable for verifire ® tools downloads. 1.5.3 aks-1b keyswitch - j2 keyswitch connector for an optional aks-1...

  • Page 11

    Switches and indicators product overview lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 11 1.6.2 piezo the lcd2-80 sounder will be activated when any new alarm or trouble is received from the panel. It is silenced by the acknowledge switch. 1.6.3 address switches - sw1 and sw2 in acs mode, the...

  • Page 12

    12 lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 section 2: terminal mode configuration when the lcd2-80 is set for terminal mode it operates like a crt terminal without full keyboard capability, but with the advantages of 24 vdc power, wall mount, and multiple terminal location with acknowle...

  • Page 13

    Terminal mode eia-485 connections terminal mode configuration lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 13 3-6 - set off. 3-7 and 3-8 - set on. Setting the acs/term mode switch: set this switch (sw10) to t (term). 2.2 terminal mode eia-485 connections see figure 2.2 for wiring diagram; th...

  • Page 14

    Terminal mode configuration terminal mode eia-485 connections 14 lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 figure 2.2 terminal mode eia-485 connections last lcd2-80 (must set dip switch sw3-7 and sw3-8 “on” and sw3-5 “on”) all lcd2-80s except last one (set dip switch sw3-7 and sw3-8 “on” ...

  • Page 15

    Lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 15 section 3: acs mode configuration the primary application for the lcd2-80 in acs mode is to display messages with text that is a subset of the panel message text, or custom messages programmed using verifire ® tools. The power-limited eia-485 i...

  • Page 16

    Acs mode configuration acs mode eia-485 connections 16 lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 3.2 acs mode eia-485 connections refer to your control panel manual for illustrations of panel-side terminals. 3.3 programming the lcd2-80 is programmed using verifire ® tools. Downloads are p...

  • Page 17

    Programming acs mode configuration lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 17 3.3.1 general tab host panel: node id - node id of the host panel. Panel type - select the host panel type from the drop-down menu. Acs addresses: start - select the first annunciator address to be programmed....

  • Page 18

    Acs mode configuration programming 18 lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 system trouble/display option - set on to have a general alarm or trouble message display in the system if there is no annunciator point mapped to the device. Acs circuit size - 64 or 96 points. System message...

  • Page 19

    Lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 19 section 4: operating the lcd2-80 4.1 displays the display consists of four 20-space rows, 80 characters total. Following are formats for different message types. 4.1.1 terminal mode in terminal mode, the lcd2-80 directly displays event informat...

  • Page 20

    Operating the lcd2-80 displays 20 lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 40 character event messages displays when one or more events are active in the system. Rows two and three display the custom label for the first active point. If there is more than one event, press the display ste...

  • Page 21

    Buttons operating the lcd2-80 lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 21 4.2 buttons the lcd2-80 emulates from one to 32 annunciators. Acknowledge when the acknowledge button is pressed on the front panel, the lcd2- 80 sends an acknowledge command to the control panel, and silences the ...

  • Page 22: Appendix 5: Eia-485 Shield

    22 lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 appendix 5: eia-485 shield terminations the eia-485 circuit must be wired using a twisted-shielded pair cable having a characteristic impedance of 120 ohms, +/- 20%. Do not run cable adjacent to, or in the same conduit as, 120-volt ac service, ...

  • Page 23

    Lcd2-80 instruction manual — p/n 53242:b1 10/25/2012 23 manufacturer warranties and limitation of liability manufacturer warranties. Subject to the limitations set forth herein, manufacturer warrants that the products manufactured by it in its northford, connecticut facility and sold by it to its au...

  • Page 24

    World headquarters 12 clintonville road northford, ct 06472-1610 usa 203-484-7161 fax 203-484-7118 www.Notifier.Com.