Notifier UDACT Instruction Manual

Manual is about: Universal Digital Alarm Communicator / Transmitter

Summary of UDACT

  • Page 1

    Universal digital alarm communicator/transmitter udact instruction manual h pn 50050: h ecn 02-266 document 50050 09/16/2002 rev: technical manuals online! - http://www.Tech-man.Com.

  • Page 2

    2 udact instruction manual pn 50050:h 09/16/2002 fire alarm system limitations while a fire alarm system may lower insurance rates, it is not a substitute for fire insurance an automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning dev...

  • Page 3: Installation Precautions

    Udact instruction manual pn 50050:h 09/16/2002 3 installation precautions adherence to the following will aid in problem-free installation with long-term reliability: warning - several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before...

  • Page 4

    4 udact instruction manual pn 50050:h 09/16/2002 technical manuals online! - http://www.Tech-man.Com.

  • Page 5: Table of Contents

    Udact instruction manual pn 50050:h 09/16/2002 5 table of contents overview introduction ................................................................................................................. 9 description ......................................................................................

  • Page 6

    6 udact instruction manual pn 50050:h 09/16/2002 secondary number communication format (42) ................................................ 32 secondary number account code (43-46) .......................................................... 32 secondary number 24-hour test time (47-50) ................

  • Page 7

    Udact instruction manual pn 50050:h 09/16/2002 7 internal ................................................................................................................. 67 remote ................................................................................................................. 67 w...

  • Page 8

    8 udact instruction manual pn 50050:h 09/16/2002 for zone identification: ....................................................................................... 95 for point identification: ....................................................................................... 95 event code/report ...

  • Page 9: Overview

    Introduction udact instruction manual pn 50050:h 09/16/2002 9 overview introduction this document contains information for installing, programming and operating the udact, universal digital alarm communicator/transmitter. The table below contains a list of document sources for supplemental informati...

  • Page 10: Description

    Description 10 udact instruction manual pn 50050:h 09/16/2002 description the universal digital alarm communicator/transmitter (udact) may be used with a variety of notifier control panels. The udact transmits system status to ul listed central station receivers via the public switched telephone net...

  • Page 11: Controls and Indicators

    Controls and indicators udact instruction manual pn 50050:h 09/16/2002 11 controls and indicators the following membrane type switches are provided on the front panel of the udact: displays are as shown below: figure 1 controls and indicators compatible panels the udact has been designed to be compa...

  • Page 12: Digital Communicator

    Digital communicator 12 udact instruction manual pn 50050:h 09/16/2002 digital communicator two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled ph1 and ph2 for the primary and secondary phone lines. Telephone line 'primary and secondary active' red leds are pr...

  • Page 13: Specifications

    Specifications udact instruction manual pn 50050:h 09/16/2002 13 specifications dc power 24vdc (nominal) filtered, non-resettable and power-limited. Voltage range is 21.2 to 28.2 volts. Dc power at terminal block tb1 (+, –) is 40 ma in standby, 75 ma maximum while communicating and 100 ma with the o...

  • Page 14

    Telephone requirements and warnings 14 udact instruction manual pn 50050:h 09/16/2002 telephone company rights and warnings the telephone company under certain circumstances may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect...

  • Page 15: Modes and Special Functions

    Modes and special functions udact instruction manual pn 50050:h 09/16/2002 15 modes and special functions normal mode normal mode is the standard mode of operation. In this mode, the udact monitors host facp status as well as monitoring telephone line voltage. The udact reports system status informa...

  • Page 16

    Modes and special functions 16 udact instruction manual pn 50050:h 09/16/2002 clear function when the clear function is activated, it causes the udact to immediately stop transmissions, hang-up from the telephone network and clear out any messages that were waiting for transmission and reset. Manual...

  • Page 17

    Udact instruction manual pn 50050:h 09/16/2002 17 notes technical manuals online! - http://www.Tech-man.Com.

  • Page 18

    Modes and special functions 18 udact instruction manual pn 50050:h 09/16/2002 technical manuals online! - http://www.Tech-man.Com.

  • Page 19: Installation and Wiring

    Installation udact instruction manual pn 50050:h 09/16/2002 19 installation and wiring installation options the udact is either installed internally in the facp cabinet or in a remote cabinet. The following table contains information specific to each facp that is compatible with the udact. See "inte...

  • Page 20

    Installation 20 udact instruction manual pn 50050:h 09/16/2002 internal installation caution: remove all power from the control panel by disconnecting ac and batteries before installation or making any connections to prevent personal and/or circuit damage. Chs-4/chs-4mb chassis mounting the udact is...

  • Page 21

    Installation udact instruction manual pn 50050:h 09/16/2002 21 chs-m2 chassis mounting the udact is installed on a chs-m2 chassis within the control panel backbox as described and shown below: figure 3 chs-m2 installation step action 1 disconnect ac power and disconnect batteries. 2 insert the tab a...

  • Page 22

    Installation 22 udact instruction manual pn 50050:h 09/16/2002 remote installation for remote installation the udact uses either an abs-8r/rb or ubs-1 enclosure. The unit must be placed within 6000 feet (1828.8 meters) of the fire alarm control panel. Installation for either enclosure is detailed be...

  • Page 23: Power Connection - 24 Vdc

    Power connection - 24 vdc udact instruction manual pn 50050:h 09/16/2002 23 power connection - 24 vdc 24 vdc filtered, non-resettable power is connected between the main power supply of the facp and the udact using twisted pair wire. For complete information on wiring the udact to a specific facp se...

  • Page 24: Telephone Connections

    Telephone connections 24 udact instruction manual pn 50050:h 09/16/2002 telephone connections provision to connect to two independent telephone lines is available via two telephone jacks labeled ph1 (primary) and ph2 (secondary). Telephone line control/command is possible via double line seizure as ...

  • Page 25

    Udact instruction manual pn 50050:h 09/16/2002 25 relay driver (auxiliary output) connections the udact's open collector output on tb3 (comm fail), is provided for communicator failure and udact trouble. It can be used to drive ul listed relay mr-101/c or mr-201/c. The output is rated for 40 ma. The...

  • Page 26

    Relay driver (auxiliary output) connections 26 udact instruction manual pn 50050:h 09/16/2002 figure 9 monitoring for udact trouble 8 9 8 8 9 9 10 11 12 13 14 15 0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 0 1 2 3 4 7 6 5 tens ones address loop 0 no on mr-101/c* nc c 18/24 115 230 +24 vdc comm failure earth tb3...

  • Page 27

    Ul power-limited wiring requirements udact instruction manual pn 50050:h 09/16/2002 27 ul power-limited wiring requirements power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25" away from any nonpower-limit...

  • Page 28

    Ul power-limited wiring requirements 28 udact instruction manual pn 50050:h 09/16/2002 technical manuals online! - http://www.Tech-man.Com.

  • Page 29: Programming Instructions

    General udact instruction manual pn 50050:h 09/16/2002 29 programming instructions general programming of the udact is possible at any time including while it is communicating with a central station. Note: during communication, addresses 16 and 42 are not programmable. The udact has been designed fo...

  • Page 30: Switch Functions

    Switch functions 30 udact instruction manual pn 50050:h 09/16/2002 switch functions the function of each switch in program mode is shown below : figure 11 udact keypad programming options primary phone number (00-15) the first sixteen addresses, 00-15, are factory set to 'f' (from 00_f to 15_f). Pro...

  • Page 31

    Programming options udact instruction manual pn 50050:h 09/16/2002 31 primary number communication format (16) one location is needed to select the communication format to the primary phone number. Address 16 is used for this purpose. The default (factory setting) for this address is contact id, whi...

  • Page 32

    Programming options 32 udact instruction manual pn 50050:h 09/16/2002 primary number 24/12 hour test time interval (25) the test report sent to the primary phone number may be sent every 12 or 24 hours. If the message is to be sent every 24 hours, leave the factory default entry of zero. If 12 hour ...

  • Page 33

    Udact instruction manual pn 50050:h 09/16/2002 33 secondary number 24-hour test time (47-50) this number is programmed in addresses 47-50 in the same manner as the primary number 24-hour test time. Default is 00:00 (12:00 midnight). Secondary number 24/12 hour test time (51) the test report sent to ...

  • Page 34

    Programming options 34 udact instruction manual pn 50050:h 09/16/2002 udact communication selection (56) leaving address 56 at '0' disables communications to the central station(s). Enter '1' for zone reporting, receive only, '2' for zone reporting, receive/transmit, '3' for point reporting, receive...

  • Page 35

    Programming options udact instruction manual pn 50050:h 09/16/2002 35 loop number (64 - 65) for contact id format only. Factory default is '00'. Maximum value is '97'. Refer to section 5.0 for additional information. Device/zone number (66 - 68) for contact id format only. These entries apply to the...

  • Page 36

    Programming options 36 udact instruction manual pn 50050:h 09/16/2002 programming event codes (69-208) the type of reports and 'event codes' that are sent to the central station are in table 4 through table 9. The selections made for the primary central station number communication format (address 1...

  • Page 37

    3+1, 4+1 express and 4+1 standard formats udact instruction manual pn 50050:h 09/16/2002 37 3+1, 4+1 express and 4+1 standard formats primary number if '0, 2, 4, 6 or 8' are entered for address 16, the following data is automatically programmed for the primary phone number event codes. Enter a '0' f...

  • Page 38

    3+1, 4+1 express and 4+1 standard formats 38 udact instruction manual pn 50050:h 09/16/2002 secondary number if '0, 2, 4, 6 or 8' are entered for address 42, the following data is automatically programmed for the secondary phone number event codes. Enter a '0' for the data setting to disable the rep...

  • Page 39

    4+2 standard and 4+2 express formats udact instruction manual pn 50050:h 09/16/2002 39 4+2 standard and 4+2 express formats primary number if '1, a or c' are entered for address 16, the following data is automatically programmed for the primary phone number event codes. Enter a '0' for the data sett...

  • Page 40

    4+2 standard and 4+2 express formats 40 udact instruction manual pn 50050:h 09/16/2002 secondary number if '1, a or c' are entered for address 42, the following data is automatically programmed for the secondary phone number event codes. Enter a '0' for the data setting to disable the report. These ...

  • Page 41: Ademco Contact Id Format

    Ademco contact id format udact instruction manual pn 50050:h 09/16/2002 41 ademco contact id format primary number if 'e' is entered for address 16, the following data is automatically programmed for the primary phone number event codes. Enter a '000' for the data setting to disable the report. Tabl...

  • Page 42

    Ademco contact id format 42 udact instruction manual pn 50050:h 09/16/2002 secondary number if 'e' is entered for address 42, the following data is automatically programmed for the secondary phone number event codes. Enter a '000' for the data setting to disable the report. Table 9 ademco contact id...

  • Page 43: Programming Reference Sheets

    Programming reference sheets udact instruction manual pn 50050:h 09/16/2002 43 programming reference sheets options to enter programming, press mode , then 7764, then enter / store . 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 primary phone number: enter 'f' to represent the end of the number. 1...

  • Page 44

    Programming reference sheets 44 udact instruction manual pn 50050:h 09/16/2002 59 make/break ratio: if rotary dialing is selected in address 58; enter '0' for a 67/73 make/ break ratio; '1' for a 62/38 make/break ratio. 60 leave default of 0. 61 leave default of 0. 62 ac loss reporting delay: enter ...

  • Page 45

    Programming reference sheets udact instruction manual pn 50050:h 09/16/2002 45 event codes 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 ...

  • Page 46: Factory Default Settings

    Factory default settings 46 udact instruction manual pn 50050:h 09/16/2002 factory default settings continued on the next page... Primary communication format: primary 24-hour test time: 16 e 21 22 23 24 0 0 0 0 primary account code: primary number test time interval: 17 18 19 20 0 0 0 0 25 0 primar...

  • Page 47

    Factory default settings udact instruction manual pn 50050:h 09/16/2002 47 69 70 71 72 73 74 75 76 77 78 79 80 81 82 1 1 0 0 8 1 0 0 f 1 f 6 0 0 83 84 85 86 87 88 89 90 91 92 93 94 95 96 f 8 f a f b f c f d f e f e 97 98 99 100 101 102 103 104 105 106 107 108 109 110 f f f f e 1 0 0 e 2 0 0 e 3 111 ...

  • Page 48

    Factory default settings 48 udact instruction manual pn 50050:h 09/16/2002 notes technical manuals online! - http://www.Tech-man.Com.

  • Page 49: Operating Instructions

    Normal mode udact instruction manual pn 50050:h 09/16/2002 49 operating instructions the udact has five modes of operation; normal, program, lamp test, troubleshoot and type mode. This chapter will cover all but the ‘program mode’, which was discussed in the programming instructions chapter. Normal ...

  • Page 50

    Normal mode 50 udact instruction manual pn 50050:h 09/16/2002 mode pressing the mode key followed by a valid 4-digit numerical code and enter / store selects one of the four modes of operation. ☛ to enter normal mode from any other mode press mode , then 6676, then enter / store . 6676 spells norm o...

  • Page 51

    Normal mode udact instruction manual pn 50050:h 09/16/2002 51 displays and leds four, seven-segment red led characters (see below) provide visual annunciation of udact trouble conditions. A list of messages that may appear on the display in normal mode is shown below: table 10 normal mode messages s...

  • Page 52

    Normal mode 52 udact instruction manual pn 50050:h 09/16/2002 normal mode operation normal mode is the standard mode of operation. In this mode, the udact monitors the following: • host facp status, power input and eia-485 communications. • udact telephone line voltage. The four character 7-segment ...

  • Page 53

    Udact instruction manual pn 50050:h 09/16/2002 53 since higher priority events take precedence over lower priority events, the udact will transmit higher priority events before sending the lower priority events. Priorities are as follows: table 11 event activations and restorals note: where #n repre...

  • Page 54

    Normal mode 54 udact instruction manual pn 50050:h 09/16/2002 key report descriptions udact off normal report removing the udact from normal mode and placing it into program, type or troubleshoot mode causes a transmission of an 'udact off normal' fault message. Returning the udact to normal mode ca...

  • Page 55: Type Mode

    Type mode udact instruction manual pn 50050:h 09/16/2002 55 type mode caution: the udact fire protection and reporting capabilities are inactive while in type mode. Type mode may be used to disable reports by zone or point and to identify the specific functionality of each zone or point in the syste...

  • Page 56

    Type mode 56 udact instruction manual pn 50050:h 09/16/2002 use the up , down and 1 st event keys to move through the list of zones/points (refer to appendices), similar to the method described in the programming section of this manual. To define all zones or points as fire alarm (return to original...

  • Page 57: Troubleshoot Mode

    Troubleshoot mode udact instruction manual pn 50050:h 09/16/2002 57 troubleshoot mode ☛ to access troubleshoot mode, press mode , then 8768, then enter / store . 8768 spells trou on a touch-tone® phone. Once in this mode, the udact will: • transmit the 'udact off normal' message to the central stati...

  • Page 58

    Lamp test mode 58 udact instruction manual pn 50050:h 09/16/2002 notes technical manuals online! - http://www.Tech-man.Com.

  • Page 59: Reporting Formats

    Data reporting structure udact instruction manual pn 50050:h 09/16/2002 59 reporting formats data reporting structure the table below shows the data reporting structure for each of the pulsed formats as well as the ademco express formats. • ademco express formats allow a typical data message to be t...

  • Page 60

    Data reporting structure 60 udact instruction manual pn 50050:h 09/16/2002 letter codes for table 12 on page 59: table 13 letter code definitions sss or ssss = subscriber id a = alarm (1st digit) a2 = alarm (2nd digit) ra = alarm restore (1st digit) ra2 = alarm restore (2nd digit) tz =zone trouble (...

  • Page 61

    Data reporting structure udact instruction manual pn 50050:h 09/16/2002 61 ademco contact id the reporting structure for the ademco contact id format is as follows: ssss 18 qxyz gg ccc table 14 ademco contact id reporting structure note: for general reports (alarm, trouble and supervisory), the gg a...

  • Page 62

    Data reporting structure 62 udact instruction manual pn 50050:h 09/16/2002 by using the type mode feature, identification of zone/point types is possible. Limits for the maximum number of zones/points reported for each panel are as follows: afp-100 = 198 points or 56 zones afp-200 = 99 zones afp-300...

  • Page 63

    Udact instruction manual pn 50050:h 09/16/2002 63 table 16 type mode maximum address facp maximum address system 500 56 afp-100 198 afp-200 99 system 5000 120 system 5000 with aim-200 248 afp-300 256 afp-400 448 afc-600 568 nfs-640 568 am2020/afp1010/ina 568 nca 568 nfs-3030 568 technical manuals on...

  • Page 64

    Data reporting structure 64 udact instruction manual pn 50050:h 09/16/2002 technical manuals online! - http://www.Tech-man.Com.

  • Page 65: Compatible Receivers

    Ul listed receivers udact instruction manual pn 50050:h 09/16/2002 65 compatible receivers ul listed receivers the chart below shows ul listed receivers compatible with the udact: notes: (1) with 685-8 line card with rev 4.4d software. (2) with 9002 line card rev 9035 software or 9032 line card with...

  • Page 66

    Ul listed receivers 66 udact instruction manual pn 50050:h 09/16/2002 notes technical manuals online! - http://www.Tech-man.Com.

  • Page 67: Appendix A: Afp-100

    Udact instruction manual pn 50050:h 09/16/2002 67 appendix a: afp-100 general the udact is capable of reporting a maximum of 56 zones or 198 points when used with the afp-100. For more information on the afp-100 see the afp-100 instruction manual. Mounting internal the udact can be mounted in the af...

  • Page 68: Wiring

    Wiring 68 udact instruction manual pn 50050:h 09/16/2002 wiring caution: remove all power from the control panel by disconnecting ac and batteries before making any connections to prevent personal and/or circuit damage. Connections with internal installation the eia-485 circuit and 24vdc are provide...

  • Page 69: Zone Assignments

    Udact instruction manual pn 50050:h 09/16/2002 69 zone assignments use chart to carefully identify function of each zone in the system. Take special precaution with any supervisory zones in the system. Use type mode (refer to "type mode" on page 55) to match the function of remaining zones in the sy...

  • Page 70: Point Assignments

    Point assignments 70 udact instruction manual pn 50050:h 09/16/2002 point assignments use chart to carefully identify all points in the system. Take special precaution with any supervisory points and remote switches in the system. Use type mode (refer to "type mode" on page 55) to match the function...

  • Page 71: Appendix B: Afp-200

    General udact instruction manual pn 50050:h 09/16/2002 71 appendix b: afp-200 general the udact is capable of reporting a maximum of 99 zones when used with the afp-200. For more information on the afp-200 see the afp-200 instruction manual. Mounting since the afp-200 cannot accommodate the udact in...

  • Page 72

    Wiring 72 udact instruction manual pn 50050:h 09/16/2002 below is a remote installation of a udact with an afp-200: figure 17 udact and afp-200 earth comm failure +24v +24v gnd rs+ rs– shield rs+ rs– acs/term term uda ct -0 9.Cdr solid earth ground connection to phone lines (supervised) do not use a...

  • Page 73: Zone Assignments

    Udact instruction manual pn 50050:h 09/16/2002 73 zone assignments use chart to carefully identify function of each zone in the system. Take special precaution with any supervisory zones in the system. Use type mode (refer to "type mode" on page 55) to match the function of remaining zones in the sy...

  • Page 74

    Zone assignments 74 udact instruction manual pn 50050:h 09/16/2002 notes technical manuals online! - http://www.Tech-man.Com.

  • Page 75: Appendix C: System 500

    General udact instruction manual pn 50050:h 09/16/2002 75 appendix c: system 500 general the udact is capable of reporting a maximum of 56 zones when used with the system 500. It reports alarms and troubles on inputs and reports only troubles on outputs. Beware of 'gaps' in the reporting of input ci...

  • Page 76

    Wiring 76 udact instruction manual pn 50050:h 09/16/2002 below is a remote installation of a udact with a system 500: figure 18 udact and system 500 earth comm failure +24v +24v gnd rs+ rs– shield rs+ rs– acs/term term common common +24v power +24v reset batt+ batt – solid earth ground connection to...

  • Page 77: Zone Assignments

    Udact instruction manual pn 50050:h 09/16/2002 77 zone assignments use chart to carefully identify function of each zone in the system. Take special precaution with any supervisory zones in the system. Use type mode (refer to "type mode" on page 55) to match the function of remaining zones in the sy...

  • Page 78

    Zone assignments 78 udact instruction manual pn 50050:h 09/16/2002 notes technical manuals online! - http://www.Tech-man.Com.

  • Page 79: Appendix D: System 5000

    General udact instruction manual pn 50050:h 09/16/2002 79 appendix d: system 5000 general the udact is capable of reporting a maximum of 120 zones when used with the system 5000. It reports alarms and troubles on inputs and reports only troubles on outputs. Beware of 'gaps' in the reporting of input...

  • Page 80: Mounting

    Mounting 80 udact instruction manual pn 50050:h 09/16/2002 mounting the udact may be mounted in the system 5000 control panel enclosure or be mounted remotely using an abs-8r or ubs-1 enclosure placed within 6000 feet (1828.8 meters) of the control panel. Refer to "remote installation" on page 22 or...

  • Page 81

    Udact instruction manual pn 50050:h 09/16/2002 81 below is a remote installation of a udact with a system 5000 using an mps-24b power supply: figure 19 udact and system 5000 with mps-24b below is an internal installation of a udact with a system 5000 using an mps-24a power supply: figure 20 udact an...

  • Page 82

    Zone assignments with aim-200 82 udact instruction manual pn 50050:h 09/16/2002 zone assignments with aim-200 use chart to carefully identify function of each zone in the system. Take special precaution with any supervisory zones in the system. Use type mode (refer to "type mode" on page 55) to matc...

  • Page 83

    Zone assignments without aim-200 udact instruction manual pn 50050:h 09/16/2002 83 zone assignments with aim-200 (cont.) table 30 zone assignments - system 5000 with aim-200 zone assignments without aim-200 use chart to carefully identify function of each zone in the system. Take special precaution ...

  • Page 84

    Zone assignments without aim-200 84 udact instruction manual pn 50050:h 09/16/2002 function of remaining zones in the system for proper reporting. Table 32 zone assignments - system 5000 without aim-200 zone zone function zone zone function zone zone function 1 41 81 2 42 82 3 43 83 4 44 84 5 45 85 ...

  • Page 85: General

    General udact instruction manual pn 50050:h 09/16/2002 85 appendix e: afp-300 & afp-400 general afp-300 the udact is capable of reporting a maximum of 99 zones or 256 points when used with the afp-300. Afp-400 the udact is capable of reporting a maximum of 99 zones or 448 points when used with the a...

  • Page 86

    Wiring 86 udact instruction manual pn 50050:h 09/16/2002 below is a remote installation of a udact with an afp-300/afp-400: figure 21 udact and afp-300/afp-400 in cab-aa below is an internal installation of a udact with an afp-300/afp-400: figure 22 udact and afp-300/afp-400 in cab-3/4 earth comm fa...

  • Page 87: Type Mode Programming

    Udact instruction manual pn 50050:h 09/16/2002 87 type mode programming to disable or identify a zone or point in type mode (refer to "type mode" on page 55), the following entries/addresses are used: for zone identification: zones 1 - 99 are programmed by entries/addresses 01 - 99. The factory defa...

  • Page 88

    Event code/report transmission 88 udact instruction manual pn 50050:h 09/16/2002 event code/report transmission via ademco contact id format only for zone reporting: zones 1 - 99 report as zone numbers 01 - 99 for point reporting: loop 1, modules 101 - 196 report as device numbers 01 - 96 (report de...

  • Page 89: Zone Assignments

    Zone assignments udact instruction manual pn 50050:h 09/16/2002 89 zone assignments use chart to carefully identify function of each zone in the system. Take special precaution with any supervisory zones in the system. Use type mode (refer to "type mode" on page 55) to match the function of remainin...

  • Page 90: Point Assignments

    Point assignments 90 udact instruction manual pn 50050:h 09/16/2002 point assignments use chart to carefully identify all points in the system. Take special precaution with any supervisory points and remote switches in the system. Use type mode (refer to "type mode" on page 55) to match the function...

  • Page 91

    Point assignments udact instruction manual pn 50050:h 09/16/2002 91 continued on the next page... Point assignments continued: note: addressable detectors on loops 1 and 2 may be disabled using type mode. The event code cannot be altered. Continued on the next page... Point no type of device: detect...

  • Page 92

    Point assignments 92 udact instruction manual pn 50050:h 09/16/2002 point assignments continued: note: system 5000 modules may only be disabled using type mode. Event code cannot be altered. Physical location is critical to the point number reported. Refer to appendix c. Table 38 point assignments -...

  • Page 93: Appendix F: Afc-600

    General udact instruction manual pn 50050:h 09/16/2002 93 appendix f: afc-600 general the udact is capable of reporting a maximum of 99 zones or 700 points when used with the afc-600. Mounting if the afc-600 is contained in a cab-600aa cabinet, then the udact must be mounted remotely in an abs-8r or...

  • Page 94

    Wiring 94 udact instruction manual pn 50050:h 09/16/2002 below is a remote installation of a udact with an afc-600: figure 23 udact and afc-600 in a cab-aa below is an internal installation of a udact with an afc-600: figure 24 udact and afc-600 in cab-3/4 earth comm failure +24v +24v gnd rs+ rs– sh...

  • Page 95: Type Mode Programming

    Udact instruction manual pn 50050:h 09/16/2002 95 type mode programming to disable or identify a zone or point in type mode (refer to "type mode" on page 55), the following entries/addresses are used: for zone identification: zones 1 - 99 are programmed by entries/addresses 01 - 99. The factory defa...

  • Page 96: Zone Assignments

    Zone assignments 96 udact instruction manual pn 50050:h 09/16/2002 zone assignments use chart to carefully identify function of each zone in the system. Take special precaution with any supervisory zones in the system. Use type mode (refer to "type mode" on page 55) to match the function of remainin...

  • Page 97: Point Assignments

    Point assignments udact instruction manual pn 50050:h 09/16/2002 97 point assignments use chart to carefully identify all points in the system. Take special precaution with any supervisory points and remote switches in the system. Use type mode (refer to"type mode" on page 55) to match the function ...

  • Page 98

    Point assignments 98 udact instruction manual pn 50050:h 09/16/2002 point assignments continued: continued on the next page... Point no type of device: module loop 1 point no type of device: module loop 1 point no type of device: module loop 2 point no type of device: module loop 2 129 161 193 225 1...

  • Page 99

    Point assignments udact instruction manual pn 50050:h 09/16/2002 99 point assignments continued: note: addressable detectors on loops 1 and 2 may be disabled using type mode. The event code cannot be altered. Continued on the next page... Point no type of device: module loop 1 point no type of devic...

  • Page 100

    Point assignments 100 udact instruction manual pn 50050:h 09/16/2002 point assignments continued: note: addressable detectors on loops 1 and 2 may be disabled using type mode. The event code cannot be altered. Continued on the next page... Point no type of device: detector loop 2 point no type of de...

  • Page 101

    Point assignments udact instruction manual pn 50050:h 09/16/2002 101 point assignments continued: note: addressable detectors on loops 1 and 2 may be disabled using type mode. The event code cannot be altered. Continued on the next page... Point no type of device: detector loop 2 point no type of de...

  • Page 102

    Point assignments 102 udact instruction manual pn 50050:h 09/16/2002 point assignments continued: table 47 point assignments point no type of device: output module point no type of device: output module 641 673 642 674 643 675 644 676 645 677 646 678 647 679 648 680 649 681 650 682 651 683 652 684 6...

  • Page 103: Appendix G: Nfs-640

    General udact instruction manual pn 50050:h 09/16/2002 103 appendix g: nfs-640 general the udact is capable of reporting a maximum of 99 zones or 700 points when used with the nfs-640. Mounting if the udact is not mounted within the cabinet that contains the nfs-640, then it must be mounted remotely...

  • Page 104

    Wiring 104 udact instruction manual pn 50050:h 09/16/2002 below is a remote installation of a udact with an nfs-640: figure 25 udact and nfs-640 in separate cabinets below is an internal installation of a udact with an nfs-640: figure 26 udact and nfs-640 in the same cabinet earth comm failure +24v ...

  • Page 105: Type Mode Programming

    Udact instruction manual pn 50050:h 09/16/2002 105 type mode programming to disable or identify a zone or point in type mode (refer to "type mode" on page 55), the following entries/addresses are used: for zone identification: zones 1 - 99 are programmed by entries/addresses 01 - 99. The factory def...

  • Page 106

    Event code/report transmission 106 udact instruction manual pn 50050:h 09/16/2002 technical manuals online! - http://www.Tech-man.Com.

  • Page 107: Appendix H: Nca

    General udact instruction manual pn 50050:h 09/16/2002 107 appendix h: nca general the udact is capable of reporting a maximum of 99 zones or 2040 points when used with the nca. Mounting if the udact is not mounted in the same cabinet that contains the nca, it must be mounted remotely in an abs-8r/r...

  • Page 108

    Wiring 108 udact instruction manual pn 50050:h 09/16/2002 below is a remote installation of a udact with an nca: figure 27 udact and nca in separate cabinets below is an internal installation of a udact with an nca: figure 28 udact and nca in the same cabinet note: use table 51 and in appendix i: am...

  • Page 109: Appendix I: Am2020/afp1010

    General udact instruction manual pn 50050:h 09/16/2002 109 appendix i: am2020/afp1010 general the udact is capable of reporting up to 2,040 points when used with the am2020/afp1010 (1,980 addressable devices plus 60 zones or 1,800 addressable devices plus 240 zones) the first 568 points can be progr...

  • Page 110

    Wiring 110 udact instruction manual pn 50050:h 09/16/2002 below is a remote installation of a udact with an am2020/afp1010 using an mps-24a main power supply: figure 29 udact and am2020/afp1010 with mps-24a below is an internal installation of a udact with an am2020/afp1010 using an mps-24b main pow...

  • Page 111: Point Assignments

    Udact instruction manual pn 50050:h 09/16/2002 111 point assignments use the following charts to carefully identify the function of each point in the system. Take special precaution with any supervisory points in the system. For the udact to report a supervisory point to the central station, both th...

  • Page 112

    Point assignments 112 udact instruction manual pn 50050:h 09/16/2002 continued on the next page... Point assignments continued: continued on the next page... Point no point function point no point function point no point function point no point function 201 251 301 351 202 252 302 352 203 253 303 35...

  • Page 113

    Udact instruction manual pn 50050:h 09/16/2002 113 point assignments continued: table 51 point assignments - am2020/afp1010 point no point function point no point function point no point function point no point function 401 451 501 551 402 452 502 552 403 453 503 553 404 454 504 554 405 455 505 555 ...

  • Page 114

    Point assignments 114 udact instruction manual pn 50050:h 09/16/2002 technical manuals online! - http://www.Tech-man.Com.

  • Page 115: Appendix J: Nfs-3030

    General udact instruction manual pn 50050:h 09/16/2002 115 appendix j: nfs-3030 general the udact is capable of reporting up to 2,040 points when used with the nfs-3030 (1,980 addressable devices plus 60 zones or 1,800 addressable devices plus 240 zones) the first 568 points can be programmed using ...

  • Page 116

    Wiring 116 udact instruction manual pn 50050:h 09/16/2002 below is a remote installation of a udact with an nfs-3030 using power supplied by the control panel: figure 31 udact and nfs-3030 below is a remote installation of a udact with an nfs-3030 using an amps-24/e main power supply: figure 32 udac...

  • Page 117: Point Assignments

    Point assignments udact instruction manual pn 50050:h 09/16/2002 117 point assignments use the following charts to carefully identify the function of each point in the system. Take special precaution with any supervisory points in the system. For the udact to report a supervisory point to the centra...

  • Page 118

    Point assignments 118 udact instruction manual pn 50050:h 09/16/2002 continued on the next page... Point assignments continued: continued on the next page... Point no point function point no point function point no point function point no point function 201 251 301 351 202 252 302 352 203 253 303 35...

  • Page 119

    Point assignments udact instruction manual pn 50050:h 09/16/2002 119 point assignments continued: table 55 point assignments - am2020/afp1010 point no point function point no point function point no point function point no point function 401 451 501 551 402 452 502 552 403 453 503 553 404 454 504 55...

  • Page 120

    Point assignments 120 udact instruction manual pn 50050:h 09/16/2002 technical manuals online! - http://www.Tech-man.Com.

  • Page 121: Appendix K: Ina

    General udact instruction manual pn 50050:h 09/16/2002 121 appendix k: ina general the udact is capable of reporting up to 2,040 points when used with the intelligent network annunciator (ina). The first 568 points can be programmed using the type mode feature (refer to "type mode" on page 55). All ...

  • Page 122

    Wiring 122 udact instruction manual pn 50050:h 09/16/2002 below is a remote installation of a udact with an ina with an mps-24a main power supply: figure 33 udact and ina with mps-24a below is an internal installation of a udact with an ina and mps-24b main power supply: figure 34 udact and ina with...

  • Page 123: Appendix L: Annunciators

    General udact instruction manual pn 50050:h 09/16/2002 123 appendix l: annunciators general the udact is connected to the eia-485 communication bus. Afm series and ldm series annunciators may also occupy the same bus. Use of a udact along with one of the above mentioned annunciators on the same cont...

  • Page 124

    General 124 udact instruction manual pn 50050:h 09/16/2002 am2020/afp1010/ina notes: 1. Use of a udact with the afp-200, system 500 or system 5000 will not alter the assignment of the first eight red leds on the annunciator. The first red led annunciates alarms while the next seven red leds are not ...

  • Page 125

    Udact instruction manual pn 50050:h 09/16/2002 125 numerics 24 vdc 23 6.6 11 73609 11 73610 11 73611 11 a abs-8r 67, 71, 75, 80, 85, 93, 109, 115, 121 abs-8r/8r 107 abs-8r/rb 103 remote installation of 22 ademco 65 contact id 12, 31–32, 36, 49, 53, 55, 88, 95, 105 contact id format 61 express 12, 32...

  • Page 126

    126 udact instruction manual pn 50050:h 09/16/2002 communications 12–13 disabled 29 failure 10 communicator failure 25 compatibility document 9 compatible facps 11 receivers 65 connections 10, 12 24 vdc 23 ground 14 relay driver 25 telephone 24 telephone line 52 d dc power 13, 23 delay 52 dial tone ...

  • Page 127

    Udact instruction manual pn 50050:h 09/16/2002 127 m m2.7 11 m2.8 11 main power supply 23 manual test 37–40 manual test function 16 manual test message 41–42 manual test message 51 maximum address 63 memory read-only 29 memory address 29 messages 16, 43, 51, 61 military time 31, 36 mode aim 79 lamp ...

  • Page 128

    128 udact instruction manual pn 50050:h 09/16/2002 nca 108 nfs-3030 116 nfs-3030/amps-24 116 nfs-640 104 system 500 76 system 5000 81 reporting codes 62 reporting structure 61 resistance 12 restoral 54 restorals 53 restore code 37–38 ringer equivalence number (ren) 13 rj31x 13–15, 24 rotary dialing ...

  • Page 129

    Udact instruction manual pn 50050:h 09/16/2002 129 w wiring entering 27 exiting 27 nonpower-limited 27 power limited 27 relay driver 25 z zone 33, 59, 62 zone number 55 zone reporting 33–34 zone trouble 25 technical manuals online! - http://www.Tech-man.Com.

  • Page 130

    130 udact instruction manual pn 50050:h 09/16/2002 technical manuals online! - http://www.Tech-man.Com.

  • Page 131: Limited Warranty

    Udact instruction manual pn 50050:h 09/16/2002 131 limited warranty notifier® warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and...

  • Page 132

    World headquarters 12 clintonville road northford, ct 06472-1653 usa 203-484-7161 fax 203-484-7118 www.Notifier.Com notifier is an operation of technical manuals online! - http://www.Tech-man.Com.