Ocean Aire CAC1211 Installation And Service Manual

Manual is about: Oceanaire CAC1211 is a portable air-cooled spot cooler

Summary of CAC1211

  • Page 1

    Oceanaire, inc. 6228 oakton street morton grove, il 60053 phone: (847) 583-0311 fax: (847) 583-0312 www.Oceanaire-inc.Com useful information model: serial number: date purchased: installed by: date installed: for technical support, or to locate a distributor for ser- vice parts, contact oceanaire at...

  • Page 2

    Table of conents page general description …................................. 1 product data and specifications ............ 2 unit description standard features.................................. 3 applications / operation.......................... 4 electrical...........................................

  • Page 3

    24 air-cooled spot cooler model cac1211 115 v / single-phase power module condensate tank full switch nc no com optional condensate pump 2dpc-1 (115v) install safety switch in low-voltage loop replacing tank full switch o a cean ire wiring diagram when field wiring—-use copper conductors only nomenc...

  • Page 4

    2 technical specifications model: cac1211 cooling capacity 12,000 btuh voltage 115 v cooling amps 11.2 a max fuse size 15 a cooling watts 1180 w in rush amps 63 a eer 10.0 compressor type rotary compressor motor 1 hp compressor rla 9.5 a compressor lra 50 a evaporator blower centrifugal evap cfm - h...

  • Page 5

    22 preventive maintenance arcticaire spot coolers are designed to last a long time and to give maximum performance and reliability with minimum maintenance. To prolong the life of the unit, regular maintenance must be performed as specified below: blower motors the motors on all units have permanent...

  • Page 6

    4 applications spot cooler the cac1211 can be used in an open environment to cool specific objects or "spots". Spot cooling is a convenient and economical way to provide air conditioning where cooling the entire space is impractical. Cool air is discharged from the unit and is directed where it is n...

  • Page 7

    20 troubleshooting guide the following steps and procedures are recommended for correcting the problems indicated. In the event that the problem can not be corrected, service may be required. Problem: unit does not power up cause: power interruption remedy: check external power supply making sure th...

  • Page 8

    6 condensate reservoir tank the cac1211, has a 2-gallon polyethylene tank for collecting condensate. The tank is located in the lower, front section of the unit. A high water level cut-out switch is used to stop the compressor and condenser fan automatically when the tank's pre-set water level has b...

  • Page 9

    Controller programming menu 1) make sure the unit has power. 2) pushing the power button, turn the unit “off”. 3) press the following buttons in sequence “s-u-d-s”: 4) the display will begin flashing p1 and a number. If there is no display, repeat the sequence, making sure the unit has power, but is...

  • Page 10

    8 uni-strut installation use (4) 5/16-18 x 1” bolts and washers to secure unit to unit-strut use (4) 5/16-18 x 1” bolts and washers to secure unit to unit-strut caution - when hanging or permanently connecting the cac1211, all applicable local/state/federal building codes must be followed. The struc...

  • Page 11

    16 evaporator return air plenum, cep-6 an evaporator return air plenum is available for installa- tions where it is required to duct air to the inlet of the evaporator. The evaporator return air plenums allow the user to connect round duct (flexible or rigid) to the return air intake to reduce air n...

  • Page 12

    10 installation—stacking kit, sk-1 two or three coolcube units are required when redundancy is critical, cooling large ar- eas, or high heat loads. The cac1211 can be stacked on top of each other to produce a capacity of 24,000 or 36,000 btuh, while maintaining the same foot print. To facilitate the...

  • Page 13

    Accessories ceiling panel conversion kit, cvk-8 the ck-8 can be converted to a dual ducted ceiling panel by use of the cvk-8 conver- sion kit. The kit contains the parts necessary to install a second 8-inch duct flange and a condenser discharge baffle onto the ck-8 ceiling panel. This allows for duc...

  • Page 14

    Accessories 12 condenser return panel ccp-8 8-inch discharge adapter cda-8 nozzle kit cnk-1 evaporator return panel cep-6 condenser discharge condenser return condensate pump kit cpc-1 condenser discharge baffle condenser discharge ring accessories condensate pump kit , cpc-1 the condensate pump pro...