Ocean Aire Polaris Series Engineering, Installation And Service Manual

Summary of Polaris Series

  • Page 1

    ... R r polarismancover.

  • Page 2

    General description polaris series air conditioners are designed for applications where outside air is not available and spot cooling or air conditioning is needed. The cord connected polaris models range from 10500 btu/hr to 60100 btu/hr floor mount configuration to satisfy any space requirements. ...

  • Page 3: P  Wc  24  1  2

    Nomenclature p wc 24 1 2 portable voltage water-cooled single phase capacity selection capacity selection number code 10..........10500 btu/hr 12..........13780 btu/hr 18..........18840 btu/hr 24..........23950 btu/hr 36..........36100 btu/hr 60……..60100 btu/hr 2 polarismanpg2.

  • Page 4

    3 2 cfm with free discharge. 3 sound pressure, db at 5 feet, commercial configuration. 1 nominal capacity is total btu/hr at 80°db/67°wb return air or 85° ewt to 95° lwt(3gpm/ton) high fan speed. C a 1 f size 3/8 valve used on models 10, 12, 18, 24 (with 3/8 m flare fitting) 3/4 valve used on model ...

  • Page 5

    Standard features serviceability all polaris series units are designed with removable panels to provide full service accessibility. Turn to page 11 “part replacement procedure” for removal of the correct panel when replacing a part. Automatic water valve all units are equipped with a direct-acting, ...

  • Page 6

    State-of-the-art controls the electronic thermostat displays room temperature if the cooling system is on. Select the temperature you want by pressing the ▲ or ▼ buttons. (the word cool and the temperature setting is displayed for 5 seconds). The fan button controls the evaporator fan motor. In the ...

  • Page 7

    Unit/model plug configuration receptacle 115 volt pwc1011, pwc1211, pwc1811 pac1011 , pac1211, owc1211, owc1811, oac1211, oach1211 nema-5-15r 115 volt pac18 , oac18, oach18 nema 5-20r 208/230 volt single phase pac1012,1212,1812,2412 oac1212,1812,2412 oach1212,1812,2412 pwc1012,1212,1812,2412,3612 ow...

  • Page 8

    Optional features hose kit 10, 25, and 40 foot hose kits with flare connectors to match fittings on units, banded 3-in-one design for easy and convenient installation, are available. When using these hoses in applications with water pres- sures exceeding 50 psig, a water pressure reducing valve must...

  • Page 9

    Unit construction 8 polarismanpg8 evaporator blower evaporator blower motor thermostat evaporator coil fan motor capacitor evaporator drain pan drain hose condensate pump compressor dry base pan casters water valve high pressure switch condenser water outlet condenser condenser water inlet condensat...

  • Page 10

    Installation instructions electrical requirements adhere to the data plate on the back of the unit and make certain that the proper power is used. Refer to the "specifications" section for voltage and fuse requirements. Make sure that proper wall outlets and re- ceptacles are used as described in "s...

  • Page 11

    Practical installation proper installation can be achieved by following these simple steps: 1. Turn off cold water supply. 2. Install “t” between faucet of cold water line and supply valve. 3. Connect shut-off valve to “t” branch. 4. Insert a 3/8 pipe nipple in discharge end of water shut-off valve....

  • Page 12

    Evaporator plenum at- taches to unit in place of standard evaporator grille. Polarismanpg11 accessories model evaporator plenum round duct size fits pwc 10 fits pwc 12 fits pwc 18 fits pwc 24 fits pwc 36 fits pwc 60 ep-10 10 inch yes yes no no no no ep-12 12 inch no no yes yes no no ep-16 16 inch no...

  • Page 13

    Plug unit in and push fan button once. This turns the evaporator fan blower on. To turn the blower off, push the fan button once again. This turns the fan blower off. To change fan speeds, push the fan speed rocker switch up for high speed or down for low speed. Fan only mode fan outdoor day/night r...

  • Page 14

    Replacement procedure for parts a. Fan motor 1. Remove cabinet's left-hand (when looking at the front of the unit) side panel. 2. Disconnect motor wires from evaporator contactor and fan speed rocker switch. 3. Remove screws securing motor and o-ring to blower housing. All screws are external and vi...

  • Page 15

    4. Disconnect valve from "water in" line. 5. Install new valve, reversing the procedure. F. High pressure control 1. Follow the first two steps in "e". 2. Remove two screws that retain switch to right side panel. 3. Disconnect wire leads from compressor contactor and condensate pump safety switch. 4...

  • Page 16

    2. (cause) thermostat (remedy) examine the control unit for loose wires. Tighten any loose connections. Wait 4-minutes before re-start. 3. (reason) high pressure control cutting turning unit off (fixing) check for loose wire connections, broken or burned contacts. If switch is defective, replace. No...

  • Page 17

    Problem: insufficient cooling 1. (cause) insufficient air flow through evaporator coil due to: a. Dirty air filter in unit b. Dirty evaporator coil c. Ice on evaporator coil d. Obstructed air intake (remedy) correct as noted: a. Clean filter (see "preventive maintenance" section of this manual) b. C...

  • Page 18

    Problem: water leaking from pan 1. (cause) leaky drain pan (remedy) locate leak and repair pan. 2. (cause) loose evaporator, drain or condensate pump hose (remedy) tighten connections. 3. (cause) defective condensate pump or excessive lift on pump (remedy) examine to see if elevation exceeds 20 ft. ...

  • Page 19

    2. Filter a clogged filter will cause the unit to operate at greatly reduced efficiencies. We recommend that the filter be inspected on a regular bases every six weeks or more often depending on the environment. The foam filter is located behind the return air grille and can be easily removed by pul...

  • Page 20

    19 piping schematic water cooled air-conditioner polarismanpg19.

  • Page 21

    High pressure switch l2 for 208/230 l1 g oceanaire, inc. Polaris, (water cooled) models models pwc10, 12, 18, 24, 36, 60 120/1/60 208/230/1/60 may 1, 2002 high run cap nc no com r s c compressor safety switch run cap l1 l2 t1 t2 01pwcwiredia g y w rh b o rc c y g r terminal block thermostat cooling ...

  • Page 22

    G y w rh b o rc c y g r oceanaire, inc. Polaris (water cooled) model pwc6034 460 volt 3 phase may 1, 2002 t1 t2 t3 compressor cooling thermostat terminal block t1 t2 t3 l1 l2 l3 compressor contactor 24 volt coil evap fan motor 230 volt l1 l2 t1 t2 evap motor contactor 24 volt coil condensate pump 23...

  • Page 23

    High pressure switch l2 l1 g oceanaire, inc. Polaris, (water cooled) models model pwc6032 and pwc3632 208/230/3/60 may 1, 2002 high run cap nc no com compressor safety switch l1 l2 t1 t2 g y w rh b o rc c y g r terminal block thermostat cooling only evaporator fan motor high-lo evaporator fan switch...

  • Page 24

    The manufacturer (oceanaire, inc.) warrants to the original owner that the product will be free from defects in material or workmanship for a period not to exceed one (1) year from date of installation. If upon examination by the manufacturer the product is shown to have a defect in material or work...