Palm GH Installation And Operation Manual - 7 5 Routine Maintenance
Our heat pump has antifreeze function if the electricity is connected. So please keep the electricity always
connected even when you don t use the heat pumps
If you don t want to use the heat pumps for
long time in winter or if the electricity is cut off by accident for more than 30 minutes, you need to drain out
all the recycling water to protect the heat pump to be freezen.
In cold area
for the safety, you d better use brine as the fluid in the heat pump water system instead of
pure water. If the lowest air temperature come to -10°C , you need add 25% C2H602 (Ethylene glycol) to the
clean pure water. If the lowest air temperature come to -25°C, you need to add 40% C2H602 to the clean
water.
To prevent faults due to sediment in the heat exchangers, care must be taken to ensure that no impurities can
enter either the heat source system or the heating system. In the event that operating malfunctions due to
contamination occur nevertheless,the system should be checked.
1 Check and clean all the water filters every months
2 Check all the water pipe connection for any leakage every half year
3 Check the refrigerant pressure through the needle valve every year
If the pressure is too low it
need to add more refrigerant
You need to check the leakage also
'
.
'
,
'
.
.
.
.
.
.
,
.
.
7 5 Routine Maintenance
7 4 Important Notice for Antifreeze to Avoid heat pump broken
.
21
Model No Illustration:
Refrigerant type
410 R410a
22 R22
.
:
;
:
Capacity unit kw
(
:
)
P With inner circulation water pump
Omitted without water pump
:
;
:
GH P
XXAC 410
( )-
-
( )
M
M 230V 60HZ
N 115V 60HZ
S 380V 50HZ
Omitted 230V 50HZ
:
/
;
:
/
;
:
/
;
:
/
Unit type
H Heating only
C Cooling only
R Heat recovery
AC Heating Cooling
HC Multifunctional Heating Cooling DHW
.
:
;
:
;
:
:
&
;
:
(
,
&
)
R series
Always with Heating Cooling
Domestic hot water functions together with additional Heat Recovery function
S
only shown to identify 3 phase and 1 phase
S means 3 phase 380V 50HZ
But if there are only 3 phase available for the
model
it can also be omitted
:
,
,
.
:
.
/
.
,
.
GH
Close loop type
OH Special type for open loop
:
:
M O S T I M P O R T A N T
!
1 Make sure
2 Select a big enough water pump for the air conditioning water circuit
3 Always keep the electricity connection with heat pump to enable the antifreeze function
.
.
.
.
.
and water circuit is recycling smoothly
water pumps C2 and C4
for water source side and usage side
are both working properly
before turn on the
heat pump to avoid freezing the plate heat exchangers
(
)
.