7-3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE
NOTES
1. Allowable length of transmission wiring between indoor/outdoor units and between the indoor unit and the
remote controller is as follows.
(1) Outdoor unit – Indoor unit:
Max. 1000 m (Max. wiring length: 2000 m)
(2) Indoor unit – Remote controller:
Max. 500 m
2. Insulated thickness:1 mm or more
• Power supply wining connections
See “INDOOR UNIT INSTALLATION” and detach the right side panel. Next, remove screw (A) and slide
front cover to the right (B) and detach. When detached, you can see terminal boards. Feed wires through
the clamp and connect to the terminal board.
• Transmission wiring connections
Feed wires through the clamp and connect to the terminal board for transmission wiring.
Depending on the number of field supplied wires, remove the clamp band and use the provided fixed
parts and clamps.
Model
Power supply wiring
Transmission wiring
Field fuses
Wire
Size
Wire
Size
CS-20KM1HPK
15A
H05VV-U3G
Wire size must com-
ply with local codes.
Vinyl cord with sheath
or cable
(2 wire) (NOTE 2)
0.75 - 1.25 mm
2
CS-25KM1HPK
CS-32KM1HPK
CS-40KM1HPK
CS-50KM1HPK
CS-63KM1HPK