1 safety precautions 3 2 features 5 3 functions 6 3.1. Remote control 6 3.2. Indoor unit 7 4 product specifications 9 5 dimensions 10 5.1. Cassette type 10 5.2. Grille 12 6 refrigeration cycle diagram 13 7 block diagram 14 8 wiring diagram 15 9 electronic circuit diagram 16 10 operation details (fun...
13.1. Operation characteristics 40 14 exploded view & replacement parts list 45 14.1. Exploded view 45 14.2. Replacement parts list 46 2 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e operating instructions of this product can be referred at following web site. Http://phaam.Panasonic.Com.My.
1 safety precautions 3 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
4 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
· serviceability − − − − self diagnosis − − − − test run at both cooling and heating rated frequency · built-in drain pump − − − − a drain pump is built in. The pipe can rise to 200 mm above the drain outlet. 2 features · product − − − − a single outdoor unit enables air conditioning of up to four s...
3 functions 3.1. Remote control 6 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
3.2. Indoor unit 7 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
8 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
4 product specifications model cs-me7eb1e cs-me10eb1e cs-me12eb1e cs-me14eb1e item cassette type power source outdoor power (single 230v 50hz) air volume cooling m 3 /min. 9.1 9.6 9.5 heating m 3 /min. 10.1 10.9 9.8 noise level cooling (power) db(a) (db) hi:40(53) lo:32(45) hi:41(54) lo:32(45) hi:42...
5 dimensions 5.1. Cassette type 10 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
11 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
5.2. Grille 12 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
6 refrigeration cycle diagram 13 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
7 block diagram cs-me7eb1e/me10eb1e/me12eb1e/me14eb1e 14 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
8 wiring diagram 15 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
9 electronic circuit diagram 16 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e cs-me7eb1e cs-me10eb1e cs-me12eb1e cs-me14eb1e.
17 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
10 operation details (functions & protection) 10.1. Simultaneous operation control 1. Operation modes which can be selected using the remote control unit: automatic, cooling, soft dry, heating, fan operation 2. Types of operations modes which can be performed simultaneously · cooling operation and c...
10.2. Airflow direction control the following shows how louver operation changes depending on the direction set with the air swing button and other operating conditions. Cooling and dry heating · the louver stops at the close position when the power switch or breaker is on. · the louver stops at the...
10.3. Indoor fan control · the following shows how fan speed changes depending on the setting made with the fan speed button and other operating conditions. · actual fan speed may differ from that you set with remote control. 20 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
21 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
10.4. Drain pump control basic operation · the drain pump starts 50 seconds after the indoor unit starts or the thermostat comes on (i.E., 10 seconds after the fan motor starts). The drain pump stops 30 seconds after the indoor unit stops or the thermostat turns off. · the drain pump repeats a cycle...
10.5. Auto restart control · if there is a power failure, operation will automatically be restarted when the power is resumed. It will start with the previous operation mode and airflow direction. (time delay safety control is valid) 1. Control start conditions the 24-hour timer must not be set. The...
10.6. Other indoor unit operation functions 10.6.1. Auto button proceed with operation when the air conditioner is stopped. (when the auto button is pressed during operation, the air conditioner is stopped.) 1. Emergency operation press the auto button and release it within 5 seconds to perform emer...
10.6.2. Drain test when installing the unit and you want the drain pump to operate independently, press the drain test switch to operate it for about 5 minutes. 25 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
10.6.3. Self diagnosis display 10.6.3.1. Breakdown self diagnosis function (three digits alphanumeric code) · once abnormality has been detected during operation, the unit will immediately stop its operation. (timer led blinks.) · although timer led goes off when power supply is turned off, if the u...
10.6.3.2. Error co de 27 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e symbol diagnosis diagnosis method h11 indoor / outdoor abnormal communication this error occurs when indoor/outdoor unit communication fails to be established after 30 seconds or more. 1. Measure the voltage of the indoor/...
28 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e symbol diagnosis diagnosis method h30 outdoor discharge pipe temp. Sensor disconnected discharge sensor when the condensation temperature is higher than the discharge temperature + (plus) 6°c, a sensor disconnection is detected, operation stops...
29 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e symbol diagnosis diagnosis method h99 indoor operating unit freezing the restriction on the compressor frequency is started when the indoor unit heat exchanger temperature is between 8°c and 12°c. Operation stops if a temperature below 0°c cont...
30 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e symbol diagnosis diagnosis method f97 compressor high discharge temperature this error occurs and operation stops when this happens on 6 occasions (it is cleared when the operation is normal for 20 minutes). 1. Check the refrigerating cycle: ga...
Cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e 31 11 installation instructions.
Cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e 32.
Cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e 33.
Cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e 34.
Cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e 35.
12 disassembly of parts high voltages are generated in the electrical parts area by the capacitor, ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 12.1. Detaching the fan motor and cross flow fan 1)...
8) detach the air guide and unscrew the screw on the heat exchanger. 9) detach the float switch and unscrew the 3 screws and disengage the 2 catches on the fan motor holder. 10) loosen the screw fixing the shaft between the cross flow fan and the fan motor and detach the fan motor. 11) remove the cr...
3) loosen the screw on the cover and detach the cover. 4) unscrew the 2 screws on the control section cover and detach all connectors. 5) disengage the catch on the control board and remove it. 38 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
12.4. Detaching the louver motor 3) loosen the screw on the cover and detach the cover. 4) unscrew the 2 screws on the control section cover and detach the connector for the louver motor. 5) unscrew the screw and disengage the 2 catches on the air outlet grille. 6) unscrew the 2 screws on the louver...
13 technical data 13.1. Operation characteristics 40 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
41 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
42 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
43 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
44 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
14 exploded view & replacement parts list 14.1. Exploded view note: the above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts. 45 cs-me7eb1e / cs-me10eb1e / cs-me12eb1e / cs-me14eb1e.
14.2. Replacement parts list ref. No. Part name & description q´ty part no. Remarks cs-me7eb1e cs-me10eb1e cs-me12eb1e cs-me14eb1e 1 float switch 1 cwa121207 ← ← ← ← ← ← ← ← ← ← ← ← l 2 thermal fuse 1 cwa16c1020j ← ← ← ← ← ← ← ← ← ← ← ← l 3 terminal board complete 1 cwa28k1045j ← ← ← ← ← ← ← ← ← ← ←...