Prozeda Solareg II ENERGY Operating Manual - 5  Menu Structure

Manual is about: Microcontroller-controlled temperature difference controller for solar thermal systems

Summary of Solareg II ENERGY

  • Page 1

    Microcontroller-controlled temperature difference controller for solar thermal systems operating manual solareg ii energy.

  • Page 2

    2 content 1 application area / device features 3 1.1 application area 3 1.2 device features 3 2 safety instructions 3 3 mounting the device 4 3.1 opening the device 4 3.2 wall mounting 4 3.3 connections 5 3.4 temperature sensor connection 5 4 short descriptions and device operation 5 4.1 display lay...

  • Page 3: 2  Safety Instructions

    3 1 application area / device features 1.1 application area the solareg ii energy controllers are high-performance microprocessor-con- trolled units for controlling the functions of solar thermal systems. The solareg ii energy perfectly controls solar power systems equipped with one collector and on...

  • Page 4: 3  Mounting The Device

    4 3 mounting the device 3.1 opening the device prior to opening the device, make sure to disconnect the mains voltage and ensure that it cannot be switched back on again. The upper part of the housing is locked to the lower part using two latches. Pull the side pieces (cover plates) of the upper par...

  • Page 5

    5 3.3 connections the following points must be followed for the 230v connections: ◼ in case of a fixed mains connection, there must be a switch installed outside the controller that can disconnect the device from the mains power supply. This switch is not required if the mains supply is connected us...

  • Page 6: 5  Menu Structure

    6 4.2 operating the device the solareg ii controller is convenient and easy to operate using four operating buttons. Using the operating buttons, you can: access display values ◼ perform device settings ◼ the graphic display symbols allow you to easily navigate through the operating structure. The o...

  • Page 7

    7 display e.G. Meaning can be reset 60 °c displays the current temperature collector return line nein 1234 h operating hours for charging storage tank can be reset to 0 h yes 927 kwh energy yield for storage tank can be reset to 0 kwh yes 5.2 "programming" menu the operating parameters are displayed...

  • Page 8

    8 5.4 "basic setup" menu the main functions are displayed in the basic setup menu. Settings must only be changed by a specialised technician. Settings may be adjusted only when you enter the menu within one minute after the device has been switched on. Display meaning value range factory setting cur...

  • Page 9: 6  System Diagram

    9 6 system diagram 1 collector, 1 storage tank 230v connections l mains phase n neutral conductor - mains and outputs a1 solar circuit pump (switching output 1) a2 switching output 2 sensor connections s1 collector sensor s2 lower storage tank s3 thermostat s4 collector return s5 option: flow meter.

  • Page 10: Controller Functions

    10 controller functions 7.1 general controller functions the controller compares the temperatures of the various measuring points and op- timally charges the storage tank. If the collector temperature exceeds the storage tank temperature, the solar circuit pump is switched on. Monitoring and protect...

  • Page 11

    11 7.1.4 tube collector or start function if this function is activated, the solar circuit pump is started for the entered time frame regardless of the actual collector temperature. This allows the medium to reach the measuring point to determine the collector temperature. "basic setup" menu display...

  • Page 12: 8  System Monitoring

    12 7.2.3 system protection if the collector temperature exceeds the collector protection temperature (see 7.2.2) by 10k, the solar circuit pump is switched off to protect the system compo- nents. If the collector temperature drops below the collector protection temperature, the solar circuit pump is...

  • Page 13: 9  Troubleshooting

    13 9 troubleshooting system faults are distinguished into two general categories: faults that are automatically detected by the controller and therefore can be ◼ displayed using error messages faults that the controller cannot detect ◼ 9.1 faults with error messages error indication in the display p...

  • Page 14

    14 9.2 faults without error messages faults and malfunctions that cannot be displayed as well as possible causes and their error source can be identified using the following table. If you cannot remedy the fault using the description below, contact the supplier or installer. Problem possible causes ...

  • Page 15

    15 10 solareg ii specifications housing material 100% recyclable abs housing for wall mount- ing dimensions l x w x d in mm, weight 175 x 134 x 56; approx. 360 g protection class ip20 according to din 40050, iec 529, vde 0470, en 60529 electrical specifications operating voltage ac 230 volts, 50hz, ...

  • Page 16: 12  Warranty Conditions

    16 12 warranty conditions the solareg ii controllers are carefully produced and tested on an automatic testing station. If any failures occur, first check if there are any operation / setting or system errors. Furthermore, check the pump and temperature sensor connections. Prozeda gmbh provides a 2-...