11
Quadra-Fire • QV36DB • 2017-900 Rev. C • 5/05
Framing should be
constructed of 2 X 4
lumber or heavier.
A. ............. 42”*
B. ......... 38 1/2”
C. ............... 22”
D. ........ 42-3/4”
E. ......... 27 7/8”
Figure 3.
Framing Dimensions
Step 2. Framing the Fireplace
Fireplace framing can be built before or after the fireplace is
set in place. Framing should be positioned to accommo-
date wall coverings and fireplace facing material. The dia-
gram below shows framing reference dimensions.
CAUTION: MEASURE FIREPLACE DIMENSIONS AND
VERIFY FRAMING METHODS AND WALL COVERING
DETAILS BEFORE FRAMING.
1/2” CLEARANCE FROM BACK OF FIREPLACE TO COMBUSTIBLE
0” CLEARANCE TO
FRAMING MEMBER
0” CLEARANCE
1/2” CLEARANCE
FROM BOTH SIDES
OF FIREPLACE
TO COMBUSTIBLE
FRAMING
MEMBER
Shows center of
10” x 12” vent framing
holes for top and rear vent-
ing. The center of the hole is one
(1) inch (25.4mm) above the center
of the horizontal vent pipe.
D
E
A
B
C
WALL
STUD
3 1/2”
3
”
Noncombustible zone is defined
by 3” above the elbow for the
entire width and depth (behind
the front header) of the firebox.
Summary of QV36DB
Page 1
1 quadra-fire • qv36db • 2017-900 rev. C • 5/05 - do not store or use gasoline or other flam- mable vapors and liquids in the vicinity of this or any other appliance. - what to do if you smell gas • do not try to light any appliance. • do not touch any electrical switch. • do not use any phone in yo...
Page 2
2 quadra-fire • qv36db • 2017-900 rev. C • 5/05 these units must use one of the vent systems described in the installing the fireplace section of the installers guide. No other vent systems or components may be used. This gas fireplace and vent assembly must be vented directly to the outside and mus...
Page 3
3 quadra-fire • qv36db • 2017-900 rev. C • 5/05 table of contents safety and warning information ................................................ 2 service parts list ....................................................................... 4 section 1: approvals and codes ...............................
Page 4: Approvals and
7 quadra-fire • qv36db • 2017-900 rev. C • 5/05 appliance certification the fireplace model discussed in this installers guide has been tested to certification standards and listed by the applicable laboratories. Certification model: qv36db laboratory: underwriters laboratories type: direct vent gas...
Page 5: Getting Started
8 quadra-fire • qv36db • 2017-900 rev. C • 5/05 introducing the quadra-fire gas fireplace quadra-fire direct vent gas fireplaces are designed to op- erate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside. The information contained in this in...
Page 6
9 quadra-fire • qv36db • 2017-900 rev. C • 5/05 figure 1. Diagram of the qv36db 41 1/8 [1044mm] 38 [965mm] 36 1/8 [916mm] 25 1/4 [642mm] 34 5/8 [879mm] 8 5/8 [219mm] vent collars electrical access 26 7/8 [682mm] 12 3/4 [323mm] 3 1/2 [90mm] gas line access 2 1/8 [55mm] 6 7/8 [174mm] 14 1/4 [362mm] 8 ...
Page 7: Installing The Fireplace
10 quadra-fire • qv36db • 2017-900 rev. C • 5/05 3 installing the fireplace step 1. Locating the fireplace for space and clearance requirements for locating a fire- place within a room see figure 2. A b c d e 42” 22” 36” 51” 72” for minimum clearances, see the direct vent termination clearance diagr...
Page 8
11 quadra-fire • qv36db • 2017-900 rev. C • 5/05 framing should be constructed of 2 x 4 lumber or heavier. A. ............. 42”* b. ......... 38 1/2” c. ............... 22” d. ........ 42-3/4” e. ......... 27 7/8” figure 3. Framing dimensions step 2. Framing the fireplace fireplace framing can be bu...
Page 9
12 quadra-fire • qv36db • 2017-900 rev. C • 5/05 note: pipes overlap 1-1/4 inches at each joint. Figure 4. Dvp-series direct vent component specifications (5-inch inner pipe / 8-inch outer pipe) dvp90st 12-9/16 11-1/4 7-1/4 1-1/4 typ 1/2 typ 8-9/16 dvp36 dvp48 48 24 36 4 6 dvp4 dvp6 12 dvp12 2 min. ...
Page 10
13 quadra-fire • qv36db • 2017-900 rev. C • 5/05 figure 5. Vent system components and termination kits step 3. Installing the vent system a. Vent system approvals this model is approved to use dvp-series direct vent pipe components and terminations (see figures 4 and 5). Ap- proved vent system compo...
Page 11
14 quadra-fire • qv36db • 2017-900 rev. C • 5/05 figure 6. Straight up vertical venting straight up vertical venting v (ft.) 40' max. (12.4 m) cap v flue restrictor instructions 1. Remove exhaust shield using a 1/4” nut driver by removing the four screws securing it in place (see figure 7). Figure 8...
Page 12
15 quadra-fire • qv36db • 2017-900 rev. C • 5/05 horizontal venting kit no. H max. Run dvp-trap 24" (610 mm) figure 10. Corner installation note: this model is tested and approved to use 45° elbows in corner installations. However, 90° elbows will result in better performance. 45-degree elbow 90-deg...
Page 13
16 quadra-fire • qv36db • 2017-900 rev. C • 5/05 figure 12. Venting with one 90° elbow note: if a 90 o elbow is first attached to the unit, the maximum horizontal run is 3-feet (914mm). Venting with one (1) 90° elbow v (ft.) h (ft.) 1' min. (305mm) 5' max. (1.52m) 2' min. (610mm) 10' max. (3.1m) 3' ...
Page 14
17 quadra-fire • qv36db • 2017-900 rev. C • 5/05 venting with two (2) 90 o elbows v ft. H + h 1 (ft.) 1' min. (305mm) 5´ max. (1.52m) 2' min. (610mm) 10´ max. (3.1m) 3' min. (914mm) 15´ max. (4.65m) 4' min. (1.22m) 20´ max. (6.2m) v+h+h 1 = 40' max.(12.4m) h+h 1 = 20´ max. (6.2m) v+v 1 +h = 40' max....
Page 15
18 quadra-fire • qv36db • 2017-900 rev. C • 5/05 figure 15. Venting with three 90° elbows venting with three (3) 90° elbows 1´min. (305mm) 2´max. (610mm) 5´max. (1.52m) 2´min. (610mm) 4´max. (1.22m) 10´max. (3.1m) 3´min. (914mm) 6´max. (1.86m) 15´max. (4.65m) 4´min. (1.22m) 8´max. (2.48m) 20´max. (6...
Page 16
19 quadra-fire • qv36db • 2017-900 rev. C • 5/05 venting with three (3) 90° elbows v (ft.) h (ft.) 1' min. (305mm) 5' max. (1.52m) 2' min. (610mm) 10' max. (3.1m) 3' min. (914mm) 15' max. (4.65m) 4' min. (1.22m) 20' max. (6.2m) note: h + h 1 = 20' max. (6.2m) v + v 1 + h + h 1 = 40' max. (12.4m) v (...
Page 17
20 quadra-fire • qv36db • 2017-900 rev. C • 5/05 figure 17 b. Installing vent components after determining which set of starting collars will be used (top or rear), follow venting instructions accordingly. Venting out the rear vent remove the installed rear seal cap from the rear starting collars by...
Page 18
21 quadra-fire • qv36db • 2017-900 rev. C • 5/05 figure 19 • continue adding vent components, locking each succeed- ing component into place. • ensure that each succeeding vent component is secure- ly fitted and locked into the preceding component in the vent system. • 90° elbows may be installed an...
Page 19
22 quadra-fire • qv36db • 2017-900 rev. C • 5/05 5. Install firestops for horizontal runs - firestops are required on both sides of a combustible wall through which the vent passes. Note: model dvp-trap does not need an exterior firestop on an exterior combustible wall. To install firestops for hori...
Page 20
23 quadra-fire • qv36db • 2017-900 rev. C • 5/05 figure 25. Ceiling firestop (ceiling side) if the area above the ceiling is an attic, position and secure the firestop on top of the previously framed hole. Note: keep insulation away from the vent pipe at least 1 inch (25mm). Figure 26. Attic firesto...
Page 21
24 quadra-fire • qv36db • 2017-900 rev. C • 5/05 v = vent terminal x = air supply inlet = area where terminal is not permitted figure 28. Vent termination minimum clearances a = 12" ....................... Clearances above grade, veran- da, porch, deck or balcony b = 12" ....................... Clea...
Page 22
25 quadra-fire • qv36db • 2017-900 rev. C • 5/05 for vertical terminations - to locate the vent and install the vent sections: • locate and mark the vent centerpoint on the underside of the roof, and drive a nail through the centerpoint. • make the outline of the roof hole around the centerpoint nai...
Page 23
26 quadra-fire • qv36db • 2017-900 rev. C • 5/05 step 4. Positioning, leveling, and securing the fireplace • place the fireplace into position. • level the fireplace from side to side and from front to back. • shim the fireplace with noncombustible material, such as sheet metal, as necessary. • secu...
Page 24
27 quadra-fire • qv36db • 2017-900 rev. C • 5/05 • insert insulation from the outside of the fireplace and pack the insulation tightly to totally seal between the pipe and the outer casing. • at the gas line access hole the gap between the supply piping and gas access hole can be plugged with non- c...
Page 25
28 quadra-fire • qv36db • 2017-900 rev. C • 5/05 step 8. Wiring the fireplace note: electrical wiring must be installed by a licensed electrician. Caution: disconnect remote controls if ab- sent for extended time periods. This will pre- vent accidental fireplace operation. • this appliance does not ...
Page 26
29 quadra-fire • qv36db • 2017-900 rev. C • 5/05 step 9. Finishing figure 35 shows the minimum vertical and corresponding maximum horizontal dimensions of fireplace mantels or other combustible projections above the top front edge of the fireplace. See figures 2 and 3 for other fireplace clearances....
Page 27
30 quadra-fire • qv36db • 2017-900 rev. C • 5/05 installing the trim combustible materials may be brought up to the specified clearances on the side and top front edges of the fireplace, but must never overlap onto the front face. The joints between the finished wall and the fireplace top and sides ...
Page 28
31 quadra-fire • qv36db • 2017-900 rev. C • 5/05 step 12. Lighting the appliance standing pilot ignition a. This appliance (standing pilot version) has a pilot that must be lighted by hand. When lighting the pilot, follow these instructions exactly. B. Before lighting smell all around the appli- anc...
Page 29
32 quadra-fire • qv36db • 2017-900 rev. C • 5/05 4 maintaining and servicing your fireplace fireplace maintenance although the frequency of your fireplace servicing and main- tenance will depend on use and the type of installation, you should have a qualified service technician perform an appli- anc...
Page 30
33 quadra-fire • qv36db • 2017-900 rev. C • 5/05 troubleshooting with proper installation, operation, and maintenance your gas fireplace will provide years of trouble-free service. If you do experience a problem, this troubleshooting guide will assist a qualified service person in the diagnosis of a...
Page 31
34 quadra-fire • qv36db • 2017-900 rev. C • 5/05 symptom possible cause corrective action 3. (continued) f. High limit switch is defective or has reached its maximum temperature. Allow the unit to cool. If the burner remains lit after the fireplace warms up, the switch is good. 4. Frequent pilot out...
Page 32: Lifetime Warranty
35 quadra-fire • qv36db • 2017-900 rev. C • 5/05 lifetime warranty limited lifetime warranty the hearth & home technologies limited lifetime warranty guarantees that the following components will work as designed for the lifetime of the stove or hearth & home technologies will repair or replace them...