Quantum DXI6500 Planning Manual - page 18
18
DXi6500 and DXi6700 Specifications
DXi6500 and DXi6700 Site Planning Guide
Caution: To safeguard backups and to avoid potential data loss in the event of a
power outage, Quantum recommends that you connect the DXi6500 or
DXi6700 to an uninterruptable power supply (UPS) with a minimum UPS
capacity rating that meets the power requirements stated above.
Performance
Characteristics
Table 10
lists the performance characteristics of the DXi6500 and DXi6700 system.
Table 10 Performance
Characteristics
Performance Characteristics
DXi6500 and DXi6700
Product family
Adaptive ingest performance of up to 3.5 TB / hour (depending on model).
Average AC Current
Node
570 Watts, 5.7A @ 100 VAC, 1945 BTU/hr
570 Watts, 2.4A @ 240 VAC, 1945 BTU/hr
Expansion Module
230 Watts, 2.3A @ 100 VAC, 785 BTU/hr
230 Watts, 1.0A @ 240 VAC, 785 BTU/hr
Inrush Peak AC Current
Node
1100 Watts, 11.0A @ 100 VAC
1120 Watts, 4.7A @ 240 VAC
Expansion Module
300 Watts, 3.0A @ 100 VAC
420 Watts, 1.75A @ 240 VAC